No, the National Electrical Code book (US) limits the current on a #12 AWG to 20 amps.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Can 30 amp breaker be put in number 12 wire?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

Can you put 20amp breaker on 10-2 wire?

Yes, you can. It will be fully protected as it can actually handle a 30 amp breaker.


Can you connect 14 gauge wire to 12 gauge wire on a 20 amp breaker if the 14 gauge is the end of the run and dedicated to lights?

yesAnother (corrected) answer.NO! The circuit breaker is there to protect the wiring from overheating. It wouldn't matter where on the circuit you decided to put the 14 gauge wire, you would need to change the breaker to 15 Amp if you did that. Using 14 gauge wire on a 20 amp circuit is a fire hazard and contrary to UBC. Contact your local building and zoning department to verify.


Can you use 6 gauge wire on A extension cord and put 30 amp plugs on it?

If your question is can you use a #6 flexible SOOW cord and put a 30 amp plug on it, then yes. The breaker that feeds the receptacle that the cord will plug into can be no larger than a 30 amp breaker. What limits the cord capacity to 30 amps is the ratings of the plug on the end of the cord.


Can 10 gauge wire be used on a 20 amp breaker?

NO! The circuit is being overloaded. Danger of fire will result from just changing the size of the fuse or breaker. A 30 amp breaker may be used with #10 wiring. #10 is rated for 30 amps. I would be hesitant to do this if the tripping problem is something new though.


Can you put a 20amp water pump and a 30 amp water heater on a 50amp breaker?

No, they each need their own breaker of the right amp. Neither of them would cause the breaker to trip if there was a problem.

Related questions

Can you put 20amp breaker on 10-2 wire?

Yes, you can. It will be fully protected as it can actually handle a 30 amp breaker.


Has anyone ever tried to experiment with 14 2 on a 20A breaker?

Its a safety thing. 20amps on that thin of wire will heat the wire up too much. Its a fact; not a story. 14 amp wire is not ok to put on a 20 amp rated device!!!! your wire will burn before the breaker will trip and will start a fire!!!!


240v nema6-50r outlet wired with 6 gauge wire and 50 amp breaker you need to run a heater with a nema 6-30p can you simply put a 30 amp receptical in place of the 50 amp receptical?

Not legally because the rating of the 30 amp receptacle would have a 50 amp breaker ahead of it. If you reduced the feed breaker to 30 amps and still use the #6 wire, this would be within the electrical code rules.


Can you connect 14 gauge wire to 12 gauge wire on a 20 amp breaker if the 14 gauge is the end of the run and dedicated to lights?

yesAnother (corrected) answer.NO! The circuit breaker is there to protect the wiring from overheating. It wouldn't matter where on the circuit you decided to put the 14 gauge wire, you would need to change the breaker to 15 Amp if you did that. Using 14 gauge wire on a 20 amp circuit is a fire hazard and contrary to UBC. Contact your local building and zoning department to verify.


Can you put a 20 amp breaker at 16 ga wire?

For most apps, the max amps for 16 ga is 25A, so yes.


Can you use 6 gauge wire on A extension cord and put 30 amp plugs on it?

If your question is can you use a #6 flexible SOOW cord and put a 30 amp plug on it, then yes. The breaker that feeds the receptacle that the cord will plug into can be no larger than a 30 amp breaker. What limits the cord capacity to 30 amps is the ratings of the plug on the end of the cord.


Can 10 gauge wire be used on a 20 amp breaker?

NO! The circuit is being overloaded. Danger of fire will result from just changing the size of the fuse or breaker. A 30 amp breaker may be used with #10 wiring. #10 is rated for 30 amps. I would be hesitant to do this if the tripping problem is something new though.


New shop 20 amp circuit 32 amp fixture how many fixtures can be put on circuit?

A 32 amp fixture can not be fed from a 20 amp breaker as the breaker will trip every time.


Can you put a 20amp water pump and a 30 amp water heater on a 50amp breaker?

No, they each need their own breaker of the right amp. Neither of them would cause the breaker to trip if there was a problem.


How does circuit breaker or fuse protect the house from fire?

The fuse is matched to the size wire in the circuit the breaker/fuse it is protecting. For instance, a 20 amp breaker/fuse is used in combination with AWG 12/2 wire. A 15 amp breaker/fuse would be used with AWG 14/2 wire. If there is too much current flow in the circuit caused by either overloading the circuit or by a short in the wires the wiring would overheat and catch fire if not for the breaker/fuse. The breaker/fuse is designed to detect this and to trip or blow and shut off all power flowing to that circuit and prevent a fire. This is why you should never install the wrong size fuse. Put a 20 amp fuse on a 15 amp circuit and it would not protect the circuit as it should.


What is the minimum amps for a 220 outlet?

The gauge of wire is referenced to the capacity of a wire to carry amperage and has nothing to do with the voltage. The voltage of a wire is determined by the type of insulation that surrounds the wire. The size of the wire is determined by the amperage of the load and the distance from the supply.


What size copper wire is needed to be used for a 120 volt outlet placed 56 feet from the house to a garage that i am wiring and should it be on a 15 amp or a 20 amp breaker?

I would use 12-2 with ground (Black, White, Bare). and use the 20 amp breaker. You could use 14-2 with ground and use a 15 amp breaker. It depends and what you are putting in the garage. We are also required by code to put GFCI outlets in garages. If you are putting the wire in the ground you need to use 12-2UF or 14.2UF which is made to be buried underground.