Best Answer

For the US, the two common values are 15 and 20 amps, with 20 being the most common in newer homes and 15 more common in older homes.

Which one is used is determined by what size of wiring is run. 15A breakers feed 14 AWG wire, and 20A breakers must use 12 AWG or larger.

If you simply replace a 15A breaker with a 20, you will create a fire hazard.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: How many amps is standard in a common household circuit breaker?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Movies & Television

How do you size circuit breakers?

If you are using 14AWG wire in your circuit, you will fuse with a 15 amp breaker as 14AWG maximum amperage is 15 amps to 100 ft of wire. If the wire run is longer than 100ft, then you would fuse for 10 amps max. If you are using 12AWG then it can carry 20 amps, etc. Longer than 100ft you would fuse for 15amps. note: 14AWG is called 14/2 and 12Awg is called 12/2 commonly.


Bus bar arrangements in sub station?

Burbars are the important elements in the electrical substation. Bus bars acts as nodal point in the substation which connects different incoming and outgoing circuits.Substations present in the power system performs various operations depends on the application such as stepping up the voltage, stepping down the voltage, high voltage transmission and switching stations to route the power to desired load center.Busbars in Substation:Busbars used in the substations are generally rectangular or circular cross section bars. These busbars can be either solid or hollow structures. Hollow circular cross section busbars are employes in EHV substations to reduce the corona effect.Switching Schemes:Switching schemes implies different methods employed to connect electrical circuits in the power system to transfer the electrical power in reliable manner. Switching schemes helps in deliver the electrical power to power system if any part of the system is faulty or under maintenance.Substations use different types of busbar arrangements or switching schemes depends upon the application, reliability of the supply and cost of installation. In every substations busbars plays a common role to connect different circuits. However switching is possible in the power system with the help of circuit breakers and isolators.Considerations for selection of busbar arrangement:Different types of busbar arrangements are employed based on the voltage, reliability of the supply, flexibility in transmitting power and cost. The other aspects considering in designing the busbars arrangements are:Simplicity in the designMaintenance of different elements without interruption in the power supplyFuture expansion feasibilityEconomical in cost of installation and operationDifferent busbar arrangements:Some of the switching schemes are busbar arrangements employed in the substations are listed below:Single Bus-bar arrangementDouble Main Bus-bar schemeMain and Transfer bus-bar schemeOne and half breaker schemeRing Main arrangement schemeSingle Bus-bar scheme:This is the simplest busbar scheme available which consists of single set of busbars connected to the generators, transformers and load feeders. All the feeders are connected by circuit breaker and set of isolators. This arrangement helps to remove the connecting elements (Generators, transformers, etc ) for maintenance by opening the circuit breaker contacts and further opening the isolators.Advantages:This busbar arrangement enjoys less cost of installationLess maintenancesimple operationDisadvantages:Fault on the busbar all the feeders connected to the busbars should be disconnectedwhen Busbar is under maintenance total supply and all feeders should be disconnectedLeast flexibility and reliabilitySee all 5 photosSingle busbar SchemeDouble Main Busbar Scheme:Normally in double main busbar scheme each circuit is connected to both the buses. In some cases half of the circuits can be connected and operated on each bus, in these cases bus or circuit breaker failure would cause loss to half of the circuits. In double main busbar arrangement one or two breakers can be provided for each circuit. Double main busbar and double breaker scheme provides high reliability in the case of fault or outage of one of the breaker.Advantages:Any circuit can be taken out of circuit for maintenanceFlexibility in connecting the feeder circuit to either of the busbarsDisadvantages:Most expensiveLoose circuits connected to busbar when fault occurs on the busbarDouble Busbar Single Breaker SchemeMain and Transfer Busbar SchemeMain and Transfer busbar scheme is similiar to single busbar arrangement with additional transfer bus connected. Tie circuit breaker is provided to tie both the main and transfer bus. During normal operation all the circuits are connected to the main bus. When circuit breaker connected to the circuit (transmission line) is required to trip for maintenance, tie circuit breaker connecting the main and transfer bus is closed. The relay protection for the circuits connected to the transfer bus is taken care by the tie circuit breaker.Advantages:Low initial costAny breaker can be taken of circuit for maintenanceDisadvantages:Requires one extra breaker for bus tieSwitching is somewhat complicated when breaker is under maintenanceMain and Transfer Busbar SchemeOne and Half breaker Busbar scheme:In One and half breaker scheme, two circuits are connected between the three circuit breakers. Hence One and Half breaker name was coined for this type of arrangement. Under normal operating conditions all the breakers are closed and both the busbars are energized. Any Circuit fault will trip two circuit breakers and no other circuit will be affected in this arrangement. When a busbar fault occur only breakers adjacent to busbars trips and no circuit will loose power. Two busbars can also be taken out of service with out affecting the power flow if the power source circuit ( alternator circuit) and receiving circuit (transmission line) available in the same bay.Advantages:Most flexible operation possibleHigh reliabilityBus failure will not remove any circuit from serviceDisadvantages:High costRelaying is somewhat complicated since the middle breaker must responsible for both the circuits on either direction and should operateone and Half Breaker SchemeRing busbar schemeIn this ring main busbar scheme arrangement, breakers are connected in ring and circuits are connected between the breakers. There will be same number of circuits as the number of breakers in the arrangement. During normal operation all the breakers are closed. During circuit fault two breakers connecting the circuit trips. During breaker maintenance the ring is broken but all the lines remain in service.Advantages:Low costFlexible operation for breaker maintenanceAny breaker can be taken out of service without interrupting loadPower can be fed from both the directionDisadvantages:Fault occur during maintenance will break the ringRelaying is complexBreaker failure during fault will trip one additional circuitRing Main Busbar Scheme


How current electricity moves in a circuit?

You need a source of electrical potential difference, also known as voltage (which is the technical term for what for you call "electric pressure"). The easiest and most common voltage source is a household battery. Hook up the positive electrode of the battery using a conductor (eg. a copper wire) to one end of your circuit and the negative electrode to the other end, and voila, you'll have electric current flowing through your circuit.


Is standard 100 keyboard common?

no. i have a 114 keyboard


Is a common anode better then a common cathode?

Neither one is "better" than the other, it simply means the circuit will have a different layout/components if you choose one over the other.

Related questions

What type of circuit is most common in household wiring?

The most common types of circuit breaker used are MCBs. (Miniature Circuit Breakers.)The most common type of breaker used in most every residence in the U.S.A. is the non-adjustable trip breaker.


What device protects an electrical circuit?

An example of a circuit protection device is a fuse. Another example is a circuit breaker.


What are the different kinds of electrical receptacle?

The most common types are the regular type, where the only over current protection is provided by the breaker panel. the other most common type is the GFCI (Ground Fault Circuit Interrupter) This type has a built in "circuit breaker" so when it senses a fault in the circuit it trips-this type is the safest as they are more sensitive than circuit breakers in the breaker panel.See related links below.


Is it possible that a circuit breaker can explode?

The definition of the word explosion is, a rapid expansion of gases. It may occur from physical or mechanical change. As there in no gases involved in a common circuit breaker the answer has to be a definite no. If a circuit breaker short circuits internally across the line the only thing that will happen is the safety protection up stream from the breaker will trip and take the faulted breaker off line.


How does a house use a series circuit?

The most common form of a series circuit in a house is a circuit breaker (optionally in series with an on-off switch) in series with a load, usually a light bulb.


What are the common sizes of circuit breaker panel for all electrical home?

200 amp is the most common size used in most homes.


What makes a circuit breaker go bad?

A circuit breaker can go bad from being tripped too many times. Many people don't understand that the tripping of a circuit breaker indicates a problem that needs to be corrected. They usually just reset the circuit breaker, leading to a very common second (or third, or fourth) trip. Circuit breakers tripping are for the prevention of fire due to excessive heat in the circuit. They're not supposed to be tripped repeatedly. This can wear the breaker out. Believe it or not, I've also seen circuit breakers fail to re-energize after being turned off. I speculate this was actually caused by the breaker never having been cycled (it was a main breaker), and the time elapsed since it was installed. Electrical equipment doesn't last forever. It's the same as anything else.


How do you tell if a household circuit breaker is defective?

Safety First! 1) Remove all load devices from the breaker circuit (unplug everything). 2) Reset breaker and observe. No problem, move to step three. 3) Add back one load device at the time. If it's winter, and the device that reproduces the problem happens to be a space heater, stop here, you solved the problem. Move the space heater to a less populated circuit. 4) If you add your I-Pod charger and the breaker trips, you could still need an licensed professional to investigate. In my experience (almost 39 years) doing electrical work, circuit overload is the most common cause.


What do circuit breakers and fuses have in common?

Both fuses and circuit breakers cut off a circuit from its power supply when the total current through the circuit exceeds the current rating of the fuse or circuit breaker, usually due to a short to ground or overloading of the circuit. Both use materials that respond to heat.


How a circuit breaker prevent from too much current flowing into device?

The current (in question) flows through both the circuit AND the circuit breaker [they are in series]. Within the circuit breaker when the current exceeds the preset limit it will open the circuit thus stopping all current flow. There are two common ways of doing this 1) magnetism - a coil pulls a switch open 2) thermal - a bimetallic strip bends away from its contacts, which opens the circuit.


Can you use two 15 amp single pole breakers in place of a double pole 30 amp breaker?

Yes. An everyday occurrence of this circuitry is in your kitchen counter split receptacles. The top half of the receptacle is a 15 amp circuit and from the same breaker the bottom half of the receptacle is another 15 amp circuit. A two pole single handle breaker is a common trip. If one of the circuits fed from the breaker faults the other connected circuit will shut off also. If you are talking about slot position in a breaker panel, you can remove the two pole breaker and install two single pole breakers.


What is a dedicated circuit?

A "dedicated" circuit is one to which only one device is or can be connected; therefore the circuit is "dedicated" to the device. A NON dedicated circuit will therefore be one to which multiple devices can connect, such as the wall outlets in your home. Multiple wall outlets are connected to a common circuit breaker, making that an example of a non-dedicated circuit.