Most (if not all) city codes require outlets be wired with 12 gauge wire and a 20 amp breaker. Lights can be wired with 14 gauge and 15 amps.
One, or possibly a million. The question you need to ask youself is how do you intend to load this 15A circuit. It already has a light on it. Is that all? How much power does this use? What is the usage of these new outlets? How much power do you plan to draw off them?
Remeber power is the product of voltage and current. So your 15A 120V breaker can supply 1800W. Sum up everything you want to put on this circuit. If you plan on drawing more than 1000W regularly on this circuit you should consider using two or more circuits. Keep in mind you want a margin of error (I went with 800W) for large temporary loads such as vacuum cleaners and irons. Don't underrate your circuit, you will regret it later.
Another poster said in another thread that according to code "generally each duplex outlet may count for 180W" (Smseagle). So, to use this rule, you need to take 1800W, subtract the wattage of your security light, and divide the result by the remainder. The quotient, rounded down, is your answer.
Depends on what you plan to power with it. You can hook millions of outlets to one 15A breaker and it will work fine as long as you don't draw more than 15A off the circuit. You need to calculate your expected load and use that to determine how many circuits you need.
Electricians go with about 12 plugs or up to 15 combination of plugs and lights.
Yet the way best way to calculate is by adding the total watts "if known" which will be used on the circuit. The max the NEC code allows is 80% of the circuit,s capacity. So 15 x .8 = 12 amp x 120V = 1440watts.
A 15 amp breaker protecting # 14 wire.
It is unusual to have multiple outlets on a 30 Amp service. If you do this you need outlets rated at 30 amps and 10 AWG wire.
no
A disconnected or broken wire along the path somewhere. If you have 5 outlets (in a row) on a breaker and the wire breaks at the 3rd outlet, the first two outlets will still work but the others will not. Rodents are known to gnaw on wires and that can cause the break. Or maybe a wire just came loose from a recepticle.
The only determining factor is the size of the circuit breaker that you will be using. If the garage circuit will be protected with a 15 Amp breaker, you may use a 14 AWG wire. If the circuit will be protected with a 20 amp breaker, you must use a 12 AWG wire. Note too that garage outlets should be protected with a GFCI breaker or outlet. If you have any concerns regarding your ability to adequately design and install the garage outlets, please, for your own safety, contact a local electrician.
A 15 amp breaker protecting # 14 wire.
It is unusual to have multiple outlets on a 30 Amp service. If you do this you need outlets rated at 30 amps and 10 AWG wire.
All depends on how big your main breaker is and what size wire you are using,one 20 amp outlet needs #12 wire not more than 50feet away from main breaker
no
A disconnected or broken wire along the path somewhere. If you have 5 outlets (in a row) on a breaker and the wire breaks at the 3rd outlet, the first two outlets will still work but the others will not. Rodents are known to gnaw on wires and that can cause the break. Or maybe a wire just came loose from a recepticle.
No more than ten. If you used a 20-A breaker it would be up to 13.
Use a 15 amp breaker and 14 AWG wire and all switches and outlets rated at 15 amps or greater.
A 30 amp breaker is usually used for a dedicated 30 amp device. Ordinary 15 amp receptacles can not be connected to a breaker of higher trip capacity than the rating of the receptacle. The wire size for a 30 amp breaker is #10 AWG.
For typical residential house wiring 12 AWG wire is required for a 20 Amp breaker. If you change out the breaker for a 25 A breaker you would have to rewire the circuit with 10 AWG. In that case you could up the breaker to 30 Amps. All outlets and switches should be rated at the same voltage and current as the breaker.
The only determining factor is the size of the circuit breaker that you will be using. If the garage circuit will be protected with a 15 Amp breaker, you may use a 14 AWG wire. If the circuit will be protected with a 20 amp breaker, you must use a 12 AWG wire. Note too that garage outlets should be protected with a GFCI breaker or outlet. If you have any concerns regarding your ability to adequately design and install the garage outlets, please, for your own safety, contact a local electrician.
Hopefully just the black wires are on the breaker. Two circuits on one breaker. Shouldn't be a problem. It would depend on how many outlets or lights were on the breaker in total. Even then, there is very little chance of something drawing current from every outlet at the same time. The only thing is you can't put two wires under one breaker (by code). You would have to wire nut them with a pig-tail then just put the one wire under the breaker.
Ground wire connects to the ground bar, white wire connects to the neutral bar, and black wire connects to the breaker. Be sure and turn off main breaker before installing the wire or the breaker.