answersLogoWhite

0


Best Answer

Yes, an outlet is required in any wall over 2 ft long except a 2 ft wall behind a door.

User Avatar

Wiki User

6y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Is a receptacle required in a hallway in a home that is 8 ft long?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Electrical Engineering

Can you change a 50 amp receptacle to a 15 amp receptacle?

Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.


What is the proper type of meter for testing a GCFI receptacle?

Any electrical meter which measures volts or a standard plug tester. (the ones which plug into the receptacle and light up indicator lights) As long as the receptacle measures 110-120V between the hot and neutral, and measures 110-120V between the hot and ground, then it is wired correctly and supplying correct voltage with ground reference. To determine if the GFCI is "tripping" or opening the circuit when it should, simply press the test button. If it doesn't trip, (or reset correctly with the reset button) replace the device.


Can you install two 220v receptacles for a welder in two different areas of your shop on the same circuit?

Technically no. In the USA the NFPA electrical code requires a separate circuit for each large appliance receptacle- there are a few exceptions (such as a heater and AC on same circuit) - I don't think the welder is one of the exceptions. In practice, as long as only one receptacle is used at a time, it will work fine Make sure that the wire size is correct for the current (amp) draw. This is taken off of the welder nameplate. Size the breaker to protect the wire size. If more that one welder gets plugged in the breaker will trip.


Can you use a 15amp outlet on a 20amp circuit?

No. You aren't allowed to install a device rated greater than the circuit is rated.The 20 amp receptacle would allow you to plug in 20 amp loads (which is why it is different than a 15 amp receptacle), and plugging a 20 amp load into a 15 amp circuit would cause an overload and the 15 amp circuit breaker would trip.ADDITIONThis may still be open for discussion. According an electrician from RKO Electric, you can in fact install a 20 Amp GFCI receptacle on a 15 Amp breaker. Apparently, the breaker will trip well before the receptacle is able to pull 20 Amps of current into the line. Please see the following link from another website: http://en.allexperts.com/q/Electrical-Wiring-Home-1734/20-amp-GFCI-outlets.htm2003 NEC Code Book says:210-21(b)(1), p.70-42: A single receptacle on an individual branch circuit shall have an ampere rating of not less than that of the branch circuit. To me this indicates that if there's only one receptacle on the circuit, you can't have an outlet rated for less than the circuit, but it neither mentions nor prohibits oversizing the receptacle.210-21(3), p.70-42: Where connected to a branch circuit supplying two or more receptacles or outlets, receptacle ratings shall conform to the values listed in table 210-21(b)(3)... which says: 15amp circuit, not over15amp receptacle (


How do you wire a switch receptical outlet with no other fixture.?

The wording of your question is a bit difficult to understand. I'm not sure what you mean by a "switch recepticle outlet." If you mean a switch/receptacle combination device, and you want the switch to operate the receptacle, first you must remove the brass bar that connects the two brass screw terminals. This can be easily done with any set of pliers small enough to get hold of the bar. By moving it back and forth a few times it will simply come off. Next connect your green or bare wire to the ground screw of the device. Then connect your neutral coming into the box to the nickle (or silver) screw terminal next to the receptacle. Then connect a black wire (or any color wire other than white, gray, green, or orange) from the switch leg terminal of the switch (most likely a black screw) to the brass terminal of the receptacle. Make this wire long enough to work with. There is no reason to make it so short you can't work with it if trouble shooting is ever necessary. And finally connect your hot wire coming into the box to the brass terminal on the switch. If all this makes absolutely no sense to you, find a competent electrician to do it for you. We do these kinds of things in our sleep. (Just kidding, of course.)

Related questions

Is a receptacle required in a hallway in a home when the hallway is 8 ft long?

no,only if its 10ft or more.


Is it ok to have two hallway runners for a long hallway?

it depends how "long" the hallway is, if its really long, it may be necessary.


What is a long hallway is called?

A corridor is another name for a hallway.


Is the long slot on a duplex receptacle hot or neutral?

The long slot on a duplex receptacle is the neutral pin.


What does corridore mean?

A corridor is a long hallway or passageway, usually with rooms down both sides of it.


What are the ratings and certificates for Dark Arts in a Long Plastic Hallway - 2009?

Dark Arts in a Long Plastic Hallway - 2009 is rated/received certificates of: Canada:14A


How do you get the square footage of a hallway when the hallway is 10 feet wide and 75.3 feet long?

Multiply. 10 x 75.3= 753


What are the release dates for Office Problems - 2013 Long Hallway 1-2?

Office Problems - 2013 Long Hallway 1-2 was released on: USA: 21 January 2013


What is a hallway?

It refers to Kubrick's "The Shining." The character, Danny, is riding his tri-cycle down a very long winding hallway in a large hotel.


In as cell process what is a ER?

A passage way like a long hallway


How many 1 ft by 1 ft tiles are needed to cover the floor of a hallway that is 138 ft long and 9 ft wide hallway?

1242


Can you change a 50 amp receptacle to a 15 amp receptacle?

Yes as long as you change the 50 amp breaker to a 15 amp breaker. You will be hard pressed to get the 50 amp #6 wire under the terminals of the 15 amp receptacle.