The wire size and the circuit breaker for a 125 hp motor must consider the length of lead wire to the motor (essentially the distance of the motor from the supply).
125 hp is a VERY large motor and would be used only in industrial applications. You will need to consult a technician for proper advice, but the general answer to your question follows:
The current draw on such a large motor would be approximately 300 amps. That is very large, and would require a wire size of 0000 AWG or 750M. 0000 AWG is 0.46 inches (11.68 mm) in diameter. As you can see, the wire is very large. It is not something you could install yourself.
If the motor is a three phase the most likely voltage the motor operates on will be 480 volts.
Read the specification plate on the motor to determine the amount of current that the motor uses, as well as the voltage and phase. Most likely, it will be a 3 phase motor, so you can't simply connect it to your house wiring, but without sufficient information, it is impossible to tell you all of the specifics. <<>> The code book rates the amperage of a three phase 40 HP motor by different voltages. at 200 volts - 120 amps, 230 volts - 104 amps, 460 volts - 52 amps and 575 volts - 52 amps. A breaker for a motor has to be sized to 250% of the motors full load amps. Also the wire size for a motor has to be 125% of the motor full load amps.
Two scenarios are that the motor could be a three phase motor. These three phase motors are manufactured in smaller sizes. The other scenario is that the motor is a 208/220 volt single phase motor. It will operate on 208 volts by taking two legs of the three phase supply for its operation.
Yes, most large motors are three phase. Usually single phase motors only go up to 10 HP. Larger than this and the wire size and contactors used to control the motors becomes extreme. For example a single phase 10 HP motor on 115 volts draws 100 amps. The same single phase motor on 230 volts draws 50 amps. The same 10 HP motor on three phase system draws the following amperage; 230 volts is a 28 amp draw, 460 volts is a 14 amp draw and 575 volts is a 11 amp draw. As you can see the higher the voltage becomes, the smaller the wire feeder size is needed and much smaller size contactor can be used to control the motor.
yes . A change of motor would be required. The motor windings would have to be totally different. three hot leads instead of two. And three phase would have to come from your provider.
To answer this question the voltage of the motor must be given. Watts is the product of amps x volts. Amps = Watts/Volts. Once this is found the motor breaker needs to be larger to allow for the inrush start current.
208 volts is not a common single phase voltage but you could just size your breaker to the capabilities of the conductor. 208 is normally a phase to phase voltage <<>> Many 230 volt motors can be connected to lower voltage supplies. These motors can be connected to supplies of 208 and 200 volts. The code requirement is that the 230 volt full load amperage of the motor be increased by 10% and 15% respectively for wire sizing and breaker selection. To answer the question you will need a two pole 15 amp breaker.
500 amp breaker with 250 mcm cu conductors, NEC list this motor as drawing 192 amps X 250% = 480amps go to the next standard size of breaker which would be a 500.
It is probably a three phase 50 Hz motor.
On a three wire supply system if you connect the two 110V wires together and they are across the phase they will short out and trip the breaker. If the two 110V wires are supplied from across the phase and connected to a motor then the motor will run. If the 110V wires are on the same phase nothing will happen.
I would go with 20 amp 3 pole 15 amp will also do
The equation for amperage is Amps = Watts/Volts = 10000/240 = 41.6 amps. It is not stated if this is a motor load or not. If it is a motor load then the feeder has to be rated at 125% x 41.6 = 52 amp wire. Also if it is a motor load then the breaker will have to be 250% x 41.6 = 104 amps. A 100 amp breaker will work and still be within the electrical code ruling. Otherwise for 41.6 amps a 50 amp breaker will be sufficient.
Yes, if the motor is rated 240 volts 3 phase.There is such a thing as 240 volt 3 phase power.However if you are asking if you can use 240 volts single phase on a three phase motor, then the answer is no.
If the motor is a three phase the most likely voltage the motor operates on will be 480 volts.
Read the specification plate on the motor to determine the amount of current that the motor uses, as well as the voltage and phase. Most likely, it will be a 3 phase motor, so you can't simply connect it to your house wiring, but without sufficient information, it is impossible to tell you all of the specifics. <<>> The code book rates the amperage of a three phase 40 HP motor by different voltages. at 200 volts - 120 amps, 230 volts - 104 amps, 460 volts - 52 amps and 575 volts - 52 amps. A breaker for a motor has to be sized to 250% of the motors full load amps. Also the wire size for a motor has to be 125% of the motor full load amps.
Would have to know the current rating of the motor or each of the phases on the motor when running. 3 Phase motors usually use mucvh less current than their single phase counterparts. My son has a lot of 3 phase equipment in his shop and most of them run under 5 amps per leg. But you really need those specs from the motor.
1. What voltage is the circuit? 2. What is the overcurrent device (breaker/fuse) rating? 3. What is the branch circuit wire size? The wire must be sized to carry the full breaker rated ampacity The branch circuit should not be loaded to greater than 80% of the breaker's rating. Volts X 80% of breaker amps = watts available. Single phase motors rule of thumb is 1100-1400 watts per HP. The precise maximum HP will depend on the current draw of the exact motor you choose, motor ratings do vary. On a 120v, 20a circuit for instance, 2HP is about it. On a 240v, 70a circuit, you can get up to a 14HP motor or so. Theoretically, with enough amps and volts, you could put a million HP motor on single phase, so it's really a matter of what motors are available for your particular voltage as well as how many amps you have available.