A three-phase 4-wire system has three live wires and a neutral, which is earthed at at least one point at the transformer.
All current-carrying wires are insulated in this system, for safety. The voltage on the neutral might be zero or only a volt or two, but under fault conditions its voltage could be much higher.
Yes, as long as it is the same size wire or larger as the hot and neutral wires.
There are two aspects to consider: 1. There are several different standard voltages and connections used by the power company in three phase service. 2. Depends if the voltage is measured phase-to-phase or phase-to-ground/neutral. The three phase-to-phase (A-B, B-C, C-A) voltages should be roughly equal. In typical service, they may be 208V or 240V. The phase-to-neutral voltages are sometimes intentionally different. For example, some 3-phase service has a "high leg" that is 208 volts with respect to ground (called a 3 phase high leg delta connection), while the other two legs are 120V with respect to ground, so that you can operate 120V, 240V and 3-phase loads from the same utility service. The important thing is you should always measure before connecting equipment. 208V will fry most 120V electronics.
240 volt delta systems were used a lot in automotive garages and small manufacturing facilities. This system works great for motor loads because of the phase to phase voltage of 240 vac, motors run better (lots of motors were manufactured to operate on 240 only) on the higher voltage compared to 208 vac. Also the availability of 120 vac on the same system was a plus, however on a delta system you have one phase with a higher voltage to ground (high leg) usually about 190 vac. You have to be careful not to use this phase in certain applications.
Three-wire transmission is used on balanced three-phase systems when the current is known to be equal in all three phases, for example when supplying a three-phase motor. A fourth neutral wire is used when the system is liable to have unequal currents or when multiple single-phase supplies are connected to it.
In industrial wiring 'three phase' green or bare copper is the norm for a ground. In home wiring 220/110 single phase, bare copper is the ground
I have never heard a fault type referred to as a "disconnect installation fault". In general there are a few types of faults - phase to ground or ground faults, phase to phase, phase to phase to ground, three phase, and three phase to ground. I'm guessing what you're referring to is a fault on a disconnect switch. Disconnects are used to isolate equipment. When a disconnect faults, it usually faults to ground.
Yes, as long as it is the same size wire or larger as the hot and neutral wires.
A "three-phase system" is a polyphase system having three phases. The term "polyphase system" just means a system having multiple phases. If it is used by itself, "a polyphase system" doesn't mean "a three-phase system".
US homes use a 240 volt single phase 'Edison' system. It is a 3-wire (4 with the ground) system. Phase to phase measures 240v, while each phase to neutral measures 120v.
5000 volt
Phase is just like as +ve terminal & neutral is just like -ve terminal in equivalent dc circuit. In AC, lines the higher voltage terminal is called phase & lower voltage terminal is known as neutral.
from ground
It dosen't.
A CT is a current transformer, used to measure current flow in a conductor. Neutral is power return, usually grounded at the distribution panel. A neutral CT, then, is a device that measures the current flow in the neutral conductor. In a three phase star system, each phase returns current to neutral, but the three phases cancel each other out, resulting in effectively zero current in neutral. The neutral CT is used to detect an imbalance in the system, perhaps caused by a ground fault or by some failure in one of the phase loads. In a single phase, single ended system, there is current on neutral, so the value of a neutral CT is not so great. If you also had a hot CT, you could compare and detect imbalance between hot and neutral, which would be an indication of a ground fault. (Actually, a ground fault current interrupting device, also called a GFCI, usually compares current in hot and neutral simultaneously, because both conductors are wound together as the sensing transformer primary - any perceived current is a ground fault.) In a single phase, double ended system, such as the 120/240 split phase system used in the US, a current CT could indicate ground fault or a system imbalance but, usually, imbalance might be a normal situation as various loads are turned on and off.
In England and Europe yes, 240 volts is the star point voltage of a 416 volt three phase four wire system. In North America no, it is not normal to have 240 volts to ground. On a single phase system that is used in homes it should only be 120 volts. In control panels that use 240 volts as a control voltage and one side of the control transformer is taken to ground, only then would you find the 240 to ground. This connection is used to trouble shoot the control panel by allowing one of the voltage tester leads to be connected to ground while the other lead can be used to probe for voltages at terminal points.
As long as the second wire is insulated at both ends you can't have any problems.
From one phase to the next you should see 208 Volts.From any phase to ground you should see 121 Volts.AnswerYou are very unlikely to come across a two-phase machine, as two-phase a.c. systems are archaic. A two-phase system has two phase voltages that are 90 degrees out of phase with each other, and was used many years' ago. These days, you have either single phase or three phase. So it's probably safe to say that there are no two-phase motors about, these days!