Best Answer

Yes. GFCI receptacles do not rely on a ground conductor to work. They sense any difference between current flowing in the hot wire and current returning in the neutral wire. Under normal circumstances, these two currents will be exactly the same. If there is a difference, then some of the current is flowing from the hot to somewhere else, possibly through a person to ground. This causes the GFCI to trip. The National Electric code even permits an old 2-wire receptacle with no ground wire to be replaced with a GFCI 3-prong receptacle. No ground wire is used, and the GFCI must be labeled "No Equipment Ground". See NEC Article 406.3(D)(3)(b) and (c). This is the only legal way to install a 3-prong receptacle in place of a 2-prong without running a new ground wire.

User Avatar

Wiki User

15y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Will a ground fault interrupter work at any outlet with only 2 wires?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Which electrical protective device is designed to detect a difference in current location in circuit wires?

A) Outlet plug B) Ground-Fault Circuit Interrupter (GFCI) C) Electricity Read Monitor D) Current Path Detector


What is single phase outlet?

It is an outlet that has one hot wire, such as a household receptacle, or two hot wires, such as a dryer outlet (in the US). If the outlet has three hot wires, it would be called a 3-phase or polyphase outlet. These would normally be found only in an industrial setting.


What is phase to earth fault?

Earth Fault Protection, also known as Protective Earth Ground, also known as the Grounding Conductor, or more simply, just Ground, is a connection ultimately to a system of grounding rods that are driven into the earth. Typically, that ground connection starts at the utility power pole, where the neutral of the distribution transformer is grounded.Neutral, also known as the Grounded Conductor (as opposed to the Grounding Conductor) is one of the conductors that transfer power to the load. It is grounded so that the other conductors, known as Hot, are never more than their specified voltage above ground, and also so that faults can trip the protective device (breaker or fuse) in the distribution panel.Normally, Ground is connected to the enclosure of the load, such as the casing of a motor. If an insulation failure or other fault in the motor were to result in a short circuit to the casing, there would be a current path to ground, preventing the casing from become an electrocution hazard, and also ensuring that high current flows through the protective device, tripping it.Sometimes, a fault to ground is not enough to trip the protective device, but it is enough to electrocute someone. The modern Ground Fault Current Interrupter (GFCI) breaker prevents this by comparing current on Hot against current on Neutral. By Kirchoff's current law, these two currents should be equal. If they are not, that means there is an alternate path, usually to Ground, and the GFCI trips.


What is ground fault protection?

GFI's (Ground Fault Interruptors) measure the difference between the hot conductor current and the neutral current. In a normal (no fault) circuit, every single milliamp of current flowing out of the hot should return through the neutral. In other words, the two currents should be equal. If there is a ground fault, at least some of the current flows from the hot. through the fault path, to ground. In this case the neutral current is less than the hot current by however much is flowing to ground. The GFI senses this difference and trips, opening the circuit. GFI's are designed to protect equipment from damage and trip at around 30 ma. of differential current. GFCI receptacles (Ground Fault Circuit Interruptors) like the ones you might find in your bathroom, and GFCI circuit breakers are designed to protect people, and trip much lower, around 5 ma.


How can you test the grounding system on a power tool?

connect the cord to a grounding outlet get a variable current source connect it to the ground terminal on the receptacle and the frame of the tool if its a 20 amp circuit and receptacle it should take 20a thru the grounding system without any problems like wires overheating or measure from the ground terminal to the tool frame it should be lees than .5 ohm the ohm meter does not test the ability of the grounding system to conduct a fault to ground before the circuit breaker trips there are testers capable of doing this all automatically with the tool on and off if the ohmmeter is not capable of testing at 20A the test should not be considered reliable

Related questions

Which electrical protective device is designed to detect a difference in current location in circuit wires?

A) Outlet plug B) Ground-Fault Circuit Interrupter (GFCI) C) Electricity Read Monitor D) Current Path Detector


What is meant by earth fault protection?

Earth fault protection is called ground fault protection in the US. It is a device that monitors the separation of the hot and ground wires in your house's electrical system. If it detects that the hot and ground have been connected with too low of resistance--like when you drop an appliance into water--it will disconnect the hot line so you won't get shocked. It's not intended to be used this way, but if you want an outlet you can switch on and off and you don't want to pull wire, install a ground fault protected outlet. If you push the "test" button the outlet will be switched off, and pressing the "reset" button turns it back on.


When wiring a range the outlet has a neutral ground and 2 hots you have three wires do you put the bare wire in the neutral or ground on the outlet?

the bare copper is always a ground


The GFCI outlet's reset button does not pop out when the test button is pressed it is already out and when I try to press it in it will not catch although it does have power?

This indicates either you have an active ground fault or the GFCI is bad. To check this out turn off power at breaker and remove GFCI outlet from wall box. Determine if it is powering other non-GFCI outlets. (It will have both input and output wires. If there are output wires remove them and check the outlet again with power and see if it resets. If it does you have a ground fault down the line somewhere. If it still doesn't work you likely have a bad GFCI.


Can you install two ground wires in the same raceway?

There should be no reason to install two ground wires in the same conduit. Code requires that only a single path should be required if it is to carry a fault current. This ground wire should be single and continuous from the device back to the distribution panel. It is the fault current that is carried on the ground wire that trips the breaker or fault protection device. Don't confuse grounding wires with bonding wires.


Why not hook ground to neutral since they are hooked on same spot in breaker box why not in outlet box.?

The "hot" wire and the neutral wire both carry current (the same amount, in fact) when a load is connected to complete the circuit. The ground wire never carries current except when a fault-to-ground situation occurs. Yes, neutral and ground wires should both be at ground potential, but NO they should not be connected at the outlet.


How you know if the wires black and white are mixed?

You use a known ground and check them for voltage. You can use an extension cord to reach from a ground to the wires you are testing. You are not putting it in an outlet, just to connect you to a ground.


What is a GFCI plug?

Ground fault circuit interrupter. Turns off the the power to the outlet, when the there is a leakage in current. example when you stick your finger in the outlet and the current leaks threw your body


When should you use an ungrounded outlet?

If the wiring system into which you are installing an outlet has no ground available, use an ungrounded outlet. In an ungrounded system, an outlet with a ground contact would allow the outlet user to mistakenly, and perhaps dangerously, assume that a ground was present. A suitable ground may be available as a ground wire accompanying the hot and neutral wires in the cable, or a ground may be available via conductive conduit and a metal outlet box. In any case, use a tester to confirm the integrity of the assumed ground. A voltage test from the hot wire to the ground should show the same voltage as between hot and neutral (the black and white wires respectively). If you are replacing an ungrounded outlet, you need not assume there is no ground present. You may find, in the box, ground wires that were not connected to the outlet. You may come across grounded outlets that have no ground wire attached because they rely on grounding via the mounting screws through the outlet ears to the metal box. This is a less reliable grounding method. It is better to buy a ground-wire "pigtail," fasten the wire directly to a hole in the metal box with the supplied screw, and attach the other end of the ground wire to the outlet via the outlet's ground screw.


What does gci stand for in gci training?

The GCI in GCI training stands for Ground Circuit Interrupter. This is one of those mechanics/technician kind of jobs that deal with electrical wires and such.


What is the function of GFCI?

A GFCI or Ground Fault Circuit Interrupter is designed to trip and stop the flow of electricity when there is a difference in the flow of electricity between the hot and neutral wires. Normally the difference will be near 0. If someone drops an appliance into the water this creates a situation where there is a difference and the breaker will immediately trip thus protecting people from electrocution.


GFCI plug trips when fan is turned on?

The Ground Fault Current/Circuit Interrupter (GFCI) detects current flowing to ground that should instead be flowing in the fan. This means somewhere in the fan the Hot wire has an unintended path to ground and is a shock hazard. You should check the wiring to the fan (with power off) and make sure there are no bare wires that could be causing your problem and if you don't see anything obvious you should replace the fan.