answersLogoWhite

0


Best Answer
Copy

I'm going to assume you are referring to residential construction because rules for commercial and industrial settings can be different. Also rules differ by geography (i.e. Canada specifies a maximum of 8 outlets on a 15 amp circuit, USA code is silent on the issue but for practical purposes, more than about 10 will likely lead to poor performance. Some code also specifies max loading of a 20 amp circuit at 80% making 10 outlets the practical limit if using 20 amp outlets on that circuit.

To expand on the previous answer a little, there is a large margin of safety in the construction of these components but if you think about it, you are placing a component that is rated at 15 amps into a 20 amp circuit. That outlet is potentially the weakest link in the circuit and could act like a fuse. If any of those 15 amp outlets are overloaded, it might overheat and fail before the circuit breaker. This is a recipe for a fire. You may think now that you'll remember to only plug in light loads, but these things have a habit of growing.

You can plug typical small home appliances (lamp, stereo, TV, etc.) into a 20 amp outlet so the only benefit in using the 15 amp outlet is the minor cost savings at installation. If it were my building, I wouldn't risk it.

If I can't talk you out of doing this and it's allowed by your applicable code, make sure you don't daisy-chain the circuit through the outlets. (In other words, don't run your 12-2 wire in one side of the outlet and out the other side.) Instead, use a pigtail (short piece of wire) to tap off your line to each individual outlet.

<><><>

In the United States you can run 20 amp breakers with 15 amp outlets but not in Canada. And for how many? About 10 to be on safe side as long as they are all low amp usage appliances. TVs, steros, fans, lamps.

<><><>

You can run 20 amp breaker with 12-2 wire as long as you make sure you use the 12-2 wire that is rated at 20 amp.


Whilst this was not your exact question it is worth saying IT IS NEVER SAFE to run a 20 amp load through a 15 amp receptacle. It is only rated to handle up to 15 amps.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.

User Avatar

Wiki User

โˆ™ 2009-11-24 09:15:55
This answer is:
๐Ÿ™
0
๐Ÿคจ
0
๐Ÿ˜ฎ
0
๐Ÿ˜‚
0
User Avatar

Add your answer:

Earn +5 pts
Q: Can you use 15A outlets on a 20A circuit with 12-2 wire and a 20A breaker and how many outlets would this allow?
Write your answer...
Submit

Related Questions

Is a ground fault indicator outlet installed at the breaker box?

There are tow places to put a Ground Fault Circuit Interrupter. There is a GFCI breaker which would be installed in a breaker box and a GFCI outlet that can be installed anywhere. Most GFCI outlets allow you to connect regular outlets to the GFCI and those outlets will also be protected.


How many outlets and lights on a 60 amp breaker?

It would be quite unusual to have a single 60 amp circuit with outlets and lights. You would have to use very heavy wire to each light and outlet. Typical lighting circuits would be protected by 15 amp breaker and a circuit with general purpose receptacles would have a 20 amp breaker. A typical lighting circuit might have 10 to 12 fixtures and receptacle circuit might have 8 outlets. If you don't know how to size a circuit get an electrician.


Why would a circuit of electrical outlets not work - the breaker is OK?

Somewhere you have a loose or broken connection.


What would cause three outlets to be low voltage and all the others in the room to be fine?

its an overload on the circuit breaker the 3 outlets are on.. many times groups of outlets are on different circuit breakers.. even though they are in the same room... especially if some are on a gfi outlet


Why would be no power in bedroom?

Blown fuse or circuit breaker. Wires loose on another outlet in that run feeding that bedroom's outlets.


How many wall outlets can you have in a circuit using a A breaker?

Assuming this is not an office of a place where lots of the outlets will be used to power items that draw lots of current on a 15 amp circuit wired with 14/2 wire I would limit it to no more than 10 outlets and lights combined. On a 20 amp circuit wired with 12/2 wire I would limit it to a 14 outlets and lights combined. There is no limit in the code. You just use common sense based on what is going to be used on this circuit.


How do you repair circuit breaker?

Only the manufacturer would be qualified to repair a circuit breaker. Any breaker in your home would be cheaper to replace than repair.


What causes a circuit breaker to switched off?

The need to de energize the circuit the breaker is feeding is a cause to have a circuit breaker switched off. If you are referring to a breaker tripping off, the cause would be from an overload condition being applied to the circuit, the breaker sensing it and shutting the circuit off.


Can you replace a 20 a breaker with a 25 a breaker?

For typical residential house wiring 12 AWG wire is required for a 20 Amp breaker. If you change out the breaker for a 25 A breaker you would have to rewire the circuit with 10 AWG. In that case you could up the breaker to 30 Amps. All outlets and switches should be rated at the same voltage and current as the breaker.


What is an example of a parallel circuit in your home?

A good example would be a number of electrical outlets wired to a single circuit breaker. The receptacles are said to be wired in parallel. If you plug in a toaster, a lamp, and a hair dryer, they would all receive the same voltage from the breaker. Unplugging the toaster would not affect the other two appliances. This is one of the main attributes of a parallel circuit.


What would cause a circuit breaker heating element to trip off?

There are two conditions that would cause a breaker to trip off. One is an overload of the circuit and the other is a short circuit on the circuit. The heating element within the breaker is what monitors for circuit overloads.


How many outlets can you put on a 30A breaker?

Generally speaking--zero. 30amp circuits are usually for special use, dedicated, one appliance circuits. Normal outlets in U.S. are not rated for 30 amps. Normal outlets on a 30amp circuit would be a fire hazard.


Can you wire more then one outlet per breaker?

they do it everyday it would cost to much otherwise You can put up to 12 outlets on a circuit. On a circuit count you have to include receptacles, switch boxes and fixture boxes.


Why would a whole room of wall outlets not work?

It would because the outlets are connected by a series circuit.


What would cause a short periodic low hum to come from a circuit breaker?

A bad circuit breaker. Replace it.


Why would circuit breaker fail?

circuit breaker do get fail if and only if the relay does not respond to the fault occurring in the system !!


When A circuit breaker acts as a switch creating a parallel circuit when current is too high?

No. circuit breakers are in series with whatever lines they are protecting. They are never put in parallel with the protected loads (this would defeat the purpose). Circuit breakers open resulting in an open circuit / no power to outlets when they trip.


What is an example of a circuit interrupter?

An example of a circuit interrupter would a fuse or circuit breaker.


How many oulets in a 15 amp breaker circuit?

Branch circuit loading In Canada the CEC states that there shall be not more than 12 outlets on any 2-wire branch circuit. These outlets shall be considered to be rated at not less than 1 amp per outletWhere the connected load is known, the number of outlets shall be permitted to exceed 12, provided that the load current does not exceed 80% of the rating of the over current device protecting the circuit. For example on a 15 amp breaker, 15 x 80% = 12 amps, hence the standard of 12 outlets on any 2-wire branch circuit.On a 20 amp breaker, 20 x 80% = 16 amps. So from a 20 amp breaker this allows 16 outlets on a 2-wire branch circuit as long as the outlets are not considered to be rated at less than 1 amp per outlet.The definition of an outlet is a point in the wiring installation at which current is taken to supply utilisation equipment. What this means is that if a light switch and a fixture outlet were on the same 2-wire branch circuit they would be subtracted from the maximum count of 12 receptacle outlets on the circuit which would leave 10.If the light fixture draws 3 amps plus the switch outlet, then the total circuit outlet count would be reduced to 8 receptacle outlets (12 &ndash; 3 &ndash; 1 = 8).On a standard specification home most electricians will wire one circuit per room, the outlet count usually never reaches the maximum of 12 outlets.


What would happenif you put an 8 amp circuit-breaker in a power circuit?

The circuit would be protected up to 8 amps before the breaker would trip. Any more that 8 amps and the circuit would open and shut the circuit off.


What if your circuit breaker started tripping with no change of things plugged into an outlet Does this mean the circuit breaker needs to be replaced?

Circuit breakers can degrade over time but it would be better to get a competant electrician to do it. It might also mean you have too many things plugged into one outlet. Sometimes one circuit breaker may protect several outlets so it might be tripping because of a change in another outlet. ELECTRICTY IS DANGEROUS!!!! Don't do it yourself.


Why would a circuit breaker switch spark?

the circuit breaker spark when it comes an over load, loss contact,but the probable cause is loss contact...and also the circuit breaker is going to be damage or destroyed.


Explain whether or not a fuse or circuit breaker should be conected in parallel to the circuit is protecting?

If you were to connect a fuse or circuit breaker in parallel with a circuit, it would create a short circuit and immediately melt (fuse) or trip (circuit breaker). These devices must be connected in series with the load.


How many outlets can be on one circuit or branch?

Branch circuit loading In Canada the CEC states that there shall be not more than 12 outlets on any 2-wire branch circuit. These outlets shall be considered to be rated at not less than 1 amp per outlet Where the connected load is known, the number of outlets shall be permitted to exceed 12, provided that the load current does not exceed 80% of the rating of the over current device protecting the circuit. For example on a 15 amp breaker, 15 x 80% = 12 amps, hence the standard of 12 outlets on any 2-wire branch circuit. On a 20 amp breaker, 20 x 80% = 16 amps. So from a 20 amp breaker this allows 16 outlets on a 2-wire branch circuit as long as the outlets are not considered to be rated at less than 1 amp per outlet. The definition of an outlet is a point in the wiring installation at which current is taken to supply utilization equipment. What this means is that if a light switch and a fixture outlet were on the same 2-wire branch circuit they would be subtracted from the maximum count of 12 receptacle outlets on the circuit which would leave 10. If the light fixture draws 3 amps plus the switch outlet, then the total circuit outlet count would be reduced to 8 receptacle outlets (12 -- 3 -- 1 = 8). On a standard specification home most electricians will wire one circuit per room, the outlet count usually never reaches the maximum of 12 outlets.


Can you use any other brand of circuit breaker in conjunction with a Challenger circuit breaker?

A Murray or similar breaker would work but most inspectors want the brand breaker to match the brand panel.