Assuming that the extension cord is plugged into a normal household receptacle rated at 15 amps the cord will handle 15A x 120V = 1800 watts. If the cord is of any length, at that wattage, you will feel the cord start to get warm like a heating cable.
No. However, a longer extension cord has higher resistance for a given wire gauge or size compared to a short extension cord and the voltage at the load device may drop so low that it doesn't work properly. This may also be accompanied by a noticeable rise in the temperature of the extension cord. As a rule, use the shortest extension cord that will get the job done. If the extension cord must be long, use one that has heavy gauge wire to minimize voltage drop at the load.
#16 <<>> To load an extension cord to 1725 watts depending on the length of the cord, the bare minimum should be #14. A better size cord and my recommendation would be a #12 wire size extension cord.
A #12 copper wire is rated at 20 amps. On an extension cord, unless it has user installed ends, the rating of the three blade cap is only 15 amps. Either way the extension cord should only be loaded up to 80% of the wire rating. 20 x .8 = 16, 15 x .8 = 12.
The best extension cord is a short one so that voltage drop does not occur. The cord should be able to reach the supply receptacle and be just long enough to reach the car. Do not use a 50 foot cord and roll it up if the vehicle is just 10 feet away. This cord should have a wire size so that is can handle the load of the block heater. A #12 AWG extension cord will handle a 200 watt block heater very nicely.
Yes, as long as the extension cord is rated for the load. Most microwave ovens use 1000W or more, some less. A standard two wire extension cord would be unsafe. There are, however, extension cords which have the proper gauge of wire and the necessary 3-prong outlets which a microwave would need to operate safely.
When the outlet is more than 40 feet away, or when you are operating 2 or more tools from it.
No. However, a longer extension cord has higher resistance for a given wire gauge or size compared to a short extension cord and the voltage at the load device may drop so low that it doesn't work properly. This may also be accompanied by a noticeable rise in the temperature of the extension cord. As a rule, use the shortest extension cord that will get the job done. If the extension cord must be long, use one that has heavy gauge wire to minimize voltage drop at the load.
#16 <<>> To load an extension cord to 1725 watts depending on the length of the cord, the bare minimum should be #14. A better size cord and my recommendation would be a #12 wire size extension cord.
Yes, but precautions need to be taken to ensure that the extension cord is substantial enough to handle the current being passed through it.
Any extension cord that has the capacity to carry the amperage that the TV draws. Any extension cord that the hardware store sell will be sufficient to do the job.
A #12 copper wire is rated at 20 amps. On an extension cord, unless it has user installed ends, the rating of the three blade cap is only 15 amps. Either way the extension cord should only be loaded up to 80% of the wire rating. 20 x .8 = 16, 15 x .8 = 12.
Resistance in the length of wire that makes up the extension cord causes voltage to drop. But it needn't be a problem with the right extension cord. For an electric drill, up to a 25 foot cord of 16 gauge wire will cause a voltage drop so small as to be negligible. For 50 feet, switch to a 14 gauge cord. For heavier power tools (circular saw in particular) you should use a 14 gauge extension from the get-go.
You can plug an extension cord into another extension cord. A extension cord is to help make doing something easier.
form_title= Extension Cord form_header= Install extension cords in your office. What size extension cord do you need?*= _ [50] What color extension cord do you need?*= _ [50] Do you need a 3 prong extension cord?*= () Yes () No
I don't know about the warranty, but the unit will run fine using an extension cord IF you buy one that is heavy-duty. Look for a cord that is 12 gauge or even 10 gauge. If you use a 14, 16, or 18 gauge cord (these may be too small), the unit could be damaged.
There are several variables:First and most important, what will be the current draw? If the total number of amps exceeds the rating of either the power strip or the extension cord you're creating a fire hazard.Second, the wire gauge and length of the extension are important. You will loose voltage over distance and that is a function of the current draw, wire type and wire gauge. If you're trying to run 20 amps, don't use any less than a 12 gauge extension cord up to a maximum of 100 Ft. 15 amps, minimum 14 gauge.
The best extension cord is a short one so that voltage drop does not occur. The cord should be able to reach the supply receptacle and be just long enough to reach the car. Do not use a 50 foot cord and roll it up if the vehicle is just 10 feet away. This cord should have a wire size so that is can handle the load of the block heater. A #12 AWG extension cord will handle a 200 watt block heater very nicely.