answersLogoWhite

0


Best Answer

KV, kilovolts, or kilojoules per coulomb is not the same thing as KVA, kilovoltamperes, or kilojoules per second, and no direct comparison exists. Please restate the question.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is difference between KV and KVA for transmission line?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

How do you specify the rating of the shunt?

1)may be voltmeter or clipon meter will be connected across the winding. 2)or in motor winding we must find amp current and aramture resistance nd then find the ratings 3)formula is rated kva of motor*1000/base kva for transmission line.


How does kvar work?

kvar can be calculated as follows the a product KVA andt the sine of the angle between the KVA and KW.


What is the line current in HT line of 11 KV?

it is depends on the rating of distribution transformer,e.g if there is 100 kva, then it will take 5.25amp.


How do you convert kva to kw and currents?

3 phase kVA = V*I*sqrt(3) Where voltage is line to line, and current is the actual RMS current flowing in the a wire. kW = V*I*sqrt(3)*Cos (phi), where phi is the angle between the voltage and current; Cos (phi) is also known as the power factor. kVA is the vector sum of kW (real power) and kVAR (reactive power). As the equations above suggest, you must know the voltage to correctly calculate the current.


Relation between kva and fault level?

There isn't enough information here. Available short circuit fault level can be given as a KVA value for different types of faults, but I assume the questioner is looking for a relationshiop between (transformer?) KVA and available short circuit current - If my assumption is correct, there is no direct correlation without knowing the transformer positive and zero sequence impedances. If these are known, you can assume the source impedance is infinite, and calculate the maximum short circuit current through the transformer as follows: lowside fault current for a 3 phase fault on the lowside of the transformer: lowside kV (line to line) / (1.732 x per unit positive sequence impedance x scalar to real impedance), where scalar to real impedance is equivalent to lowside kV (line to line) ^2 / base kVA. For a L-G fault, do the same with zero sequence impedance.

Related questions

What is the difference between a 1.5KVA and a 3KVA transformer?

The 3 kVA transformer will weigh double the 1.5 kVA transformer.


How do you convert kav to kilowatt?

By "kav", I'm assuming you mean "thousand-ampere-volts" ... usually represented as "KVA". Watts = (Volts) x (Amperes) x (power factor on the line) KW = KVA x (power factor on the line). The power factor on the line is the cosine of the phase difference between the voltage and current waveforms on the line.


How many kVA equal kvar?

For normal power factors (pf=80%), you have 0.8 kW for every kva. In general however, kW = pf x kVA. Where pf is the power factor, it is the cosine of the angular difference between the voltage and the current of a circuit in alternating current circuits.


How do you specify the rating of the shunt?

1)may be voltmeter or clipon meter will be connected across the winding. 2)or in motor winding we must find amp current and aramture resistance nd then find the ratings 3)formula is rated kva of motor*1000/base kva for transmission line.


Is 6.5kW greater generator than 6.5 kva generator?

Yes of cours1 kw =1.25 kva wich mean6.5 kw =8.12 kvaif you have generator 8.12 kva it give you 6.5 kw=============================Answer #2:1 kw does not necessarily = 1.25 kvaThe relationship between KW and KVA depends on the nature of the load you'repowering, and is called the "power factor". It describes how closely the voltageand current peaks coincide in time. If the load has any inductive or capacitxivereactance, then the voltage and current waveforms become separated in time.The "KVA" is the product of the full voltage and full current without regard fortheir "phase difference", but the "real" power in KW is the KVA multiplied by thecosine of the phase angle. So if there's any inductance or capacitance present,then the KW is less than the KVA. But if the load is pure resistive, then thevoltage and current on the line are in phase, the angle between them is zero,and the KW and KVA are equal.When everything is just exactly perfect, and there is no reactance on the load orthe line, then your 6.5 KVA generator can just exactly supply 6.5 KW of load, withnothing to spare. More commonly, of course, a generator with somewhat morethan 6.5 KVA capacity is required in order to supply 6.5 KW of 'real' power.


Is 1 kva 1 kw?

Yes, if the power factor (cosine of the phase-angle between voltage and current)is ' 1 '. In order for that to be true, the total load impedances on the line have tobe pure resistive, with zero reactance.All of this stuff applies only on an AC line. On a DC line, voltage and current arealways in phase, the power factor is 1, and KVA = KW .


How does kvar work?

kvar can be calculated as follows the a product KVA andt the sine of the angle between the KVA and KW.


How calculate kvar?

kvar can be calculated as follows the a product KVA andt the sine of the angle between the KVA and KW.


How do convert KVA to KW?

kVA = kW divided by (power factor). The power factor is the cosine of the angle between voltage and current.


What is the line current in HT line of 11 KV?

it is depends on the rating of distribution transformer,e.g if there is 100 kva, then it will take 5.25amp.


How do you convert kva to kw and currents?

3 phase kVA = V*I*sqrt(3) Where voltage is line to line, and current is the actual RMS current flowing in the a wire. kW = V*I*sqrt(3)*Cos (phi), where phi is the angle between the voltage and current; Cos (phi) is also known as the power factor. kVA is the vector sum of kW (real power) and kVAR (reactive power). As the equations above suggest, you must know the voltage to correctly calculate the current.


Difference between two part tariff and three part tariff?

1.two part tariff= maximum demand+energy consumption (150 kva + any greater than 150 kva consumption) 2.three part tariff=maximum demand+energy consumption+ any energy charge (150 kva + any greater than 150 kva consumption + out source any energy charge ) unlimited usage of tariff is nothing but three part tariff