Full load starting current is typically in the region of 5or 6 times the full load motor current;.
FLA: Full Load Ampere. Its the current drawn by the motor when the motor is running at full load FLA = kW / (1.732*V*pf*efficiency*100)
According to 2011 nfpa 70 nec Motor conductors are sized with the flc- full load current or the nameplate rating fla- full load amperes
Because full speed is unloaded. As you load the motor, speed decreases, and slip increases, with an accompanying increase in current.
While starting a motor from standstill to its rated speed, the motor has to overcome the inertia and generate enough torque to over come it. In the process the motor takes higher current during the starting. Once started and set in motion the current reduces ti its normal value. Full load current is lower than the starting current normally.
whenever the load increases,the current drawn by the motor to do or to fulfill the required energy to the load. so the current will increase generally.Increase in load will cause the full utilization of motor,so speed of rotor will decrease.
As the no load current is the current due to core losses of the motor which is very small .in no load terminals are open circuited no current flows through it, a small current flows which is due to core
3phese 460 volt 75 kw a/c drivi full load current
The ratio is between 30% to 40 %
FLA: Full Load Ampere. Its the current drawn by the motor when the motor is running at full load FLA = kW / (1.732*V*pf*efficiency*100)
Across the line starting of a motor can be as high as 300% of the full load amps.
According to 2011 nfpa 70 nec Motor conductors are sized with the flc- full load current or the nameplate rating fla- full load amperes
Because full speed is unloaded. As you load the motor, speed decreases, and slip increases, with an accompanying increase in current.
While starting a motor from standstill to its rated speed, the motor has to overcome the inertia and generate enough torque to over come it. In the process the motor takes higher current during the starting. Once started and set in motion the current reduces ti its normal value. Full load current is lower than the starting current normally.
decrease in starting and running torque and speed is almost constant from no load to full load. it's because the field voltage is consant and current is varied.
What is the continuous current of 10HP star delta motor
whenever the load increases,the current drawn by the motor to do or to fulfill the required energy to the load. so the current will increase generally.Increase in load will cause the full utilization of motor,so speed of rotor will decrease.
The first thing you have to do is find the full load amps of the motor. The wire size feeding the motor has to be 125% of the full load current. The breaker is usually 250% of the full load current. If the voltage and amperage had been added to the question the exact breaker size could have been calculated.