Divide your wattage by your voltage to get your amperage.
4500/240=18.75 Amps
12ga. wire "can" handle 20amps, however, You should only load a wire to 75% it's max. You are beyond 15amps, so 10ga. would be a good idea, and may be required by your local building codes. Remember, in a brownout (voltage drop) the amp draw will go up. You want to keep below 75% load to allow for this.
On 12ga. wire you would be at 93.75% of it's 20amp rating. (Dangerous)
On 10ga. wire you would be at 62.5% of it's 30amp rating. (Safe)
On 8ga. wire you would be at 46.875% of it's 40amp rating. (Overkill)
If you use 8ga., make sure the conductors will actually fit into the terminals on your breaker.
If you house doesn't have true 120v/240v power, the amperage will be higher. For example, if you power is actuall comming in at 110v/220v, the ater heater will draw 20.45amps. This would exceed the rating of the 12ga. wire, and raise the load on the 10ga. and 8ga. to 68.16% and 51.12% respectively.
Regardless of the wire size you choose, use a 20amp breaker (25amp if you voltage is less than 240). If the water heater draws more than 20amps, you could have a problem. The wire is not the only thing that can burn your house down.
Correction to above. If voltage decreases in a resistive circuit, wattage will go down, as will current draw. Resistance stays the same.
a # 12 wire is inadequate
a typical 60gal electric water heater takes 20 amps
this is a permanently connected permanently installed load
this is too much for #12 wire it will never see less than 20A
you must use the next larger size wire #10
20A fuse will blow in 20 minutes with 20A load it must be next larger size
30A fuse will protect #10 wire
25A fuse will carry 20A for indefinite period
if you have several people who like to shower with warm water you will see 20A for 5 hour periods
<<>>
New homes will be wired for a 40 gallon tank. This will be a # 12 wire rated at 20 amps on a two pole 20 amp breaker. A 4500 watt tank will draw 4500/240 = 18.75 amps.
I would run 10 AWG wire and use a 30 A 240 Volt Breaker.
The wattage of the water tank is needed to size the breaker and the wire to feed the tank.
20 amp is perfect, 15 is fine
The wire size is dependent upon the wattage size of your water heater. The higher the wattage the larger the wire size. A standard 3000 watt heater will use a two pole 20 amp breaker connected to 2C #12 wire.
Yes the wire size is larger for that size breaker but will not effect the 30 amp breaker protection of that circuit.
To answer this question the wattage of the heater is needed.
The wattage of the water tank is needed to size the breaker and the wire to feed the tank.
10/3 wire with 30 amp double pole breaker from panel box to water heater.
Assuming you are referring to a 240 volt residential hot water heater you will need to install 10/2 NM cable (Romex) with ground from the service panel to the water heater wired to a 30 amp circuit breaker in the service panel. If you cannot see the water heater from the service panel you will need to install a service disconnect at the water heater.
20 amp is perfect, 15 is fine
Usually 30 amp
The wire size is dependent upon the wattage size of your water heater. The higher the wattage the larger the wire size. A standard 3000 watt heater will use a two pole 20 amp breaker connected to 2C #12 wire.
Yes the wire size is larger for that size breaker but will not effect the 30 amp breaker protection of that circuit.
32amp 30ma rcbo
To answer this question the wattage of the heater is needed.
15 amp
Look on the heater and see what amps it is pulling. That will determine the wire size and breaker size. It must be on a dedicated circuit. 15 amps = AWG # 14 wire with 15 amp breaker 20 amps = AWG # 12 wire with 20 amp breaker 30 amps = AWG # 10 wire with 30 amp breaker 40 amps = AWG # 8 wire with 40 amp breaker
The average size water tank is 4500 watts. The generator's supply will be large enough to operate the water tank. Larger tanks over 5000 watts will not heat correctly.