Want this question answered?
A breaker is based on wire size, as the breaker protects the wire and not the load. This is a voltage drop question. A #3 copper conductor will limit the voltage drop to 3% or less when supplying 60 amps for 110 feet on a 110 volt system.
your house has 220 you must use a 2 pole breaker. your wiring will change ,not a do it your selfer call someone
You cannot connect directly unless the espresso machine specifies it can operate at the lower voltage. If the machine were to operate you would be doubling the current. If you installed a transformer or converter to up the voltage you would have to ensure that you didn't overload the 110 volt circuit. Best bet is to have an electrician install a dedicated 220 volt circuit.
The size breaker you use is determined by the size wire used in the circuit. If you use AWG #12/2 wire then use a 20 amp breaker. If you use AWG # 14/2 then use a 15 amp breaker.
On a 110 volt circuit, Black is hot, White is neutral, Green or bare Copper is ground. . Connect Black to the gold screw, White to the silver screw, and bare copper ground to the Green ground screw on the receptacle. On a 220 Volt circuit Black & Red are both hot, each carrying 110 volts for a total of 220. White is Neutral and ground is Green or bare copper.
Wiring to the circuit breakers is 220 volts. The circuit breaker box has 2 110 Volt lines. If you connect two black lines together from one side nothing happens. If the these two black wires are from different circuit breakers you may have a safety issue by back feeding the electricity. If you connect 2 different 110 volt lines you will end up with a short. This ends up as a 220 volt short.
2.3 kw per hour on a 110-120 volt circuit.
Most of the breakers in a panel will be 120 VAC. Double height breakers are 240 VAC. A triple height breaker probably indicates you have 3-phase power in the panel.
There is a direct short after the switch.
It should work okay.
If it is a 110 volt light it can safely run on a 20 amp circuit with AWG # 12 wire.
NO - that is dangerous.
if the nameplate says 120 volt, then yes. but might trip breaker if the circuit is overloaded and or only 15 amps
No. You need to rewire the circuit from the electric panel.
They are in tandem because they power a 220 VAC circuit, rather then a 110 VAC circuit.
A breaker is based on wire size, as the breaker protects the wire and not the load. This is a voltage drop question. A #3 copper conductor will limit the voltage drop to 3% or less when supplying 60 amps for 110 feet on a 110 volt system.
15000btu is the largest and that's a 115 volt basically the same ,you just need a higher breaker is all