You are missing a very serious safety issue!
There MUST be a mechanical method to keep the main breaker in the home panel in the off position while the generator "back feed" breaker is on and vice versa.
For some of the newer panels, the manufacturers may make them or you can get these things on line from interlockkit.com.
They are easy to install and most importantly, they will protect utility line men from getting killed if someone were to accidentally turn on your house main while the generator is on. I am sure your local electrical code would require this or something similar like a full blown transfer switch.
<><><>
You can but it is very dangerous. If you plan to use it more than once then it would be a good idea to have an electrician install a new 4 prong outlet (including proper electrical wiring) and cord for the dryer. Although another alternative is to ask him to install a new 4 prong 220VAC plug outside the house which could be used for a welder and use this leg for your generator.
220VAC comes in several flavors, in this case the dryer is either a)2-hot 1-ground or b)2-hot 1-neutral with ground to the casing. The generator is 2-hot, 1-neutral and 1-ground. The breaker this is on then becomes the main breaker and if it is only rated at 50 amps then make sure all high draw items are turned off including the house main breaker and all 220V appliances. Usually with a 5000W generator, you can run 2 35" or smaller TVs, 2-3 ceiling fans, 2 refrigerator/freezers or one fridge and one deep freeze all simultaneously. Everything else like the electric water heater, AC unit, heat pump, well pump, stove-top range/oven MUST have their breakers turned off and if possible unplugged from the wall.
<><><>
As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.
Before you do any work yourself,
on electrical circuits, equipment or appliances,
always use a test meter to ensure the circuit is, in fact, de-energized.
IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB
SAFELY AND COMPETENTLY
REFER THIS WORK TO QUALIFIED PROFESSIONALS.
For convenience I install the receptacle just above the backboard of the dryer. This way if the dryer is to be moved out of its location it can be unplugged before the move is started. Sometimes the dryer is located in a confined space and it is hard to reach down to the floor level to unplug the dryer with out becoming an acrobat.
Yes, most definitely. Provisions for the ground wire in the dryer receptacle should be used. The feeder cable's ground wire is first grounded to the receptacle's junction box ground screw and then taken to the receptacle's ground terminal. The dryer plug configuration will match up to the dryers four wire plug in cable. When the plug is connected into the dryer receptacle the ground terminals of both devices will match and the ground wire will be continuous from the voltage source at the distribution panel and complete the circuit at the dryer. This low impedance electrical path will conduct any ground fault that could occur at the dryer and trip the feeder breaker of the dryer circuit, there by removing the fault current from the dryer circuit.
Check the wattage of the blow dryer and add 500 watt. This will be the size of generator you will need to use.
Yes there is a serious danger. The breaker should be tripping under this condition and not allowing the frame of the dryer to become electrically energized. It means that the ground wire is missing from the dryer receptacle or the dryer cord is not grounded to the machine. Shut the breaker off to the dryer and remove the dryer receptacle. Look for a bare copper wire. It should be bonded to the box and then to the receptacles U shaped pin hole. If this end is fine check the dryer end where the cord goes into the back of the dryer to make sure the green ground wire is connected to the frame of the dryer. If you don't feel competent of doing this get some electrical help as this condition needs to be repaired before you use the dryer again. If you were shocked and recovered, you will be OK You should report it though because it could kill someone, for example, if they had a heart problem of some kind.
A 30 amp dryer cord is the cord that comes attached to new clothes dryer. It is used to transfer the voltage from the wall receptacle to the dryer appliance. Earlier model dryers used to be hard wired directly from the distribution panel to the dryer. Hard wiring is no longer the case as people wanted to take there appliances with them when they moved from one home to another. New homes are now wired with 30 amp receptacles situated in the wall alcove where the dryer is to be situated. This allows the home owner to plug in the dryer without the hiring of an electrician to legally make the connection. Dryers that have been previously been hard wired can be upgraded with a 30 amp cord kit that can be purchased at any hardware store. Following the instructions included with the kits, any home owner can make the conversion and then connect their dryer into the dryer receptacle.
To install a dryer receptacle box in a laundry room, follow these steps: Turn off the power to the area where you will be working. Locate a suitable location for the receptacle box near the dryer. Cut a hole in the wall for the box using a drywall saw. Install the box securely in the wall. Connect the wiring to the receptacle according to the manufacturer's instructions. Secure the receptacle in the box and cover it with a faceplate. Turn the power back on and test the receptacle to ensure it is working properly.
To wire receptacles in series, connect the hot wire from the power source to the first receptacle, then connect a jumper wire from the first receptacle to the second receptacle, and so on for each additional receptacle in the series. Finally, connect the neutral wire from the power source to the last receptacle in the series.
A receptacle pigtail in electrical wiring is used to connect multiple wires together and then connect them to a single terminal on a receptacle. This helps to ensure a secure and reliable electrical connection, as well as to prevent overloading the receptacle.
For convenience I install the receptacle just above the backboard of the dryer. This way if the dryer is to be moved out of its location it can be unplugged before the move is started. Sometimes the dryer is located in a confined space and it is hard to reach down to the floor level to unplug the dryer with out becoming an acrobat.
The proper electrical requirement for a 30 amp dryer receptacle is a dedicated 240 volt circuit with a 30 amp circuit breaker and a 3-prong or 4-prong outlet.
Yes, most definitely. Provisions for the ground wire in the dryer receptacle should be used. The feeder cable's ground wire is first grounded to the receptacle's junction box ground screw and then taken to the receptacle's ground terminal. The dryer plug configuration will match up to the dryers four wire plug in cable. When the plug is connected into the dryer receptacle the ground terminals of both devices will match and the ground wire will be continuous from the voltage source at the distribution panel and complete the circuit at the dryer. This low impedance electrical path will conduct any ground fault that could occur at the dryer and trip the feeder breaker of the dryer circuit, there by removing the fault current from the dryer circuit.
Check the wattage of the blow dryer and add 500 watt. This will be the size of generator you will need to use.
Using a red wire nut hook the 3 wires (of the same color) together with a short piece of wire of the same color. You now have 4 wires tied together. Now take the other end of the short wire and attach it to the outlet on the correct screw Do the same with the other 2 wires Please keep in mind to make sure the wire nut has securely fastened the wires. Loose connections cause heat which cause fire If you do not completely understand this answer please contact a qualified electrician
Yes there is a serious danger. The breaker should be tripping under this condition and not allowing the frame of the dryer to become electrically energized. It means that the ground wire is missing from the dryer receptacle or the dryer cord is not grounded to the machine. Shut the breaker off to the dryer and remove the dryer receptacle. Look for a bare copper wire. It should be bonded to the box and then to the receptacles U shaped pin hole. If this end is fine check the dryer end where the cord goes into the back of the dryer to make sure the green ground wire is connected to the frame of the dryer. If you don't feel competent of doing this get some electrical help as this condition needs to be repaired before you use the dryer again. If you were shocked and recovered, you will be OK You should report it though because it could kill someone, for example, if they had a heart problem of some kind.
With an ozone generator
To connect a dryer to a gas line, you will need a gas line adapter.
Yes it can if you connect it with an 120v generator. But it depends on how powerful the generator is.