Several answers are possible here (this sounds like a test question, by the way). NEC 210.19(A)(4) says that branch circuits that are not for cooking appliances specified in 210.19, or specific-purpose loads specified in 210.2 shall not be smaller than #14 copper (#12 aluminum). 310.5 says that all wiring 0-2000 volts shall be minimum #14 unless otherwise permitted elsewhere in the code. There are perhaps other references too, these are two that come to mind.
depends on the amperage. 14 AWG for 15 amps, 12 AWG for 20 amps, 8 AWG for 50 amps.
10 AWG can be solid. 8 AWG and larger should be stranded. 2008 NEC 310.3 2011 NEC 310.106(C)
14 AWG
The one with the smallest thickness (highest AWG number) and longest length has.
NEC 310.16 conductor ampacities NEC 240.4(D) For residential installations the smallest wire to be used is 14 AWG (15 amps rating) and for commercial installations the smallest wire to be used is 12 AWG (20 amp rating)
NEC Section 310.4 requires a 1/0 AWG and larger be used in parallel.
The larger the AWG number the smaller the wire. 10 AWG wire can carry more current than 12 AWG wire.The wire sizes of 24 and 26 are the smallest that are used in the electrical.See related links below
not unless the wire is exceptionally small, if if is 12 AWG or even 14 AWG you will be ok unless you are using it for a transmission line (unlikely) The smallest wire you can use safely is a 21 AWG wire but that's not a wire used in the walls
depends on the amperage. 14 AWG for 15 amps, 12 AWG for 20 amps, 8 AWG for 50 amps.
10 AWG can be solid. 8 AWG and larger should be stranded. 2008 NEC 310.3 2011 NEC 310.106(C)
According to appendix C of the NEC, 3 #2 awg are permitted in a 1" EMT.
14 AWG
Under modern code, the 14 AWG copper conductor is the smallest branch-circuit wiring size, based upon 15A overcurrent protection.
I think you mean either what is the correct size or minimum wire size needed when a branch circuit is protected by a 20 A breaker. The size is 12 American Wire gauge (AWG). 14 AWG is used for 15 A circuit and 10 AWG for a 30 A breaker. The lower the gauge the larger the cross-section of the wire.
There is no rating for #14 wire in the electrical code book. This is because #12 aluminium wire is rated at 20 amps and that is the minimum of home wiring circuit wiring in aluminium. It is not, if at all, used anymore. #10 at 75 or 90 degree C is rated both at 30 amps. #8 at 75 or 90 degree C is rated both at 45 amps.
You should use 14 AWG wiring on all 15 amp circuits.
30 amp wired with AWG # 10 wire.