Phase to Phase voltage

Correction to the above answer:

There is no such thing as a 'phase-to-phase' or 'phase-to-ground' voltage. The correct terms are 'line-to-line' (or 'line voltage') and 'line-to-ground' (or 'phase voltage'). Transmission-line voltages are line-to-line (or 'line') voltages.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Is transmission voltage a phase to phase voltage or a phase to ground voltage?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What is the Phase to phase voltage of 66KV earthed cable?

Nominal transmission and distribution voltages are line voltages. So '66 kV' is a line-to-line voltage. Note that there is no such thing as a 'phase-to-phase' voltage -the correct term is 'line-to-line'. Using the term, 'phase-to-phase', indicates a lack of understanding of a.c., which is not uncommon! Incidentally, the symbol is 'kV', not 'KV'.


How do you calculate phase voltage of a three phase four wire system?

Phase voltage is determined by the wiring of transformer that serves the building. To test phase voltage use a volt meter and put one probe to ground and the other to each phase and observe the reading, this will give you a phase to ground voltage reading. Next test phase to phase (1 to 2, 1 to 3, and 2 to 3) to see if it's 208, 240, 277, or 480. Only licensed electricians should perform these tests. DAW


What will happen if you use phase to phase voltage for a single phase device?

Phase to phase, two wire is classed as single phase. If the voltage from the phase to phase match the device's operating voltage, then connecting the device will allow it to operate.


What voltage would be measured from any phase to ground on a 480 volt 3 phase wye system?

A voltage of 277 is the line to neutral (ground) voltage of a 480 volt wye three phase system. L1- N, L2 - N and L3 - N will give you 277 volts. L1 to L2. L2 to L3 and L3 to L1 will give you 480 volts.


What is considered high voltage in a 3 phase system?

There are two aspects to consider: 1. There are several different standard voltages and connections used by the power company in three phase service. 2. Depends if the voltage is measured phase-to-phase or phase-to-ground/neutral. The three phase-to-phase (A-B, B-C, C-A) voltages should be roughly equal. In typical service, they may be 208V or 240V. The phase-to-neutral voltages are sometimes intentionally different. For example, some 3-phase service has a "high leg" that is 208 volts with respect to ground (called a 3 phase high leg delta connection), while the other two legs are 120V with respect to ground, so that you can operate 120V, 240V and 3-phase loads from the same utility service. The important thing is you should always measure before connecting equipment. 208V will fry most 120V electronics.

Related questions

Why do you have voltage to ground but not voltage phase to phase?

There is phase to phase voltage in 3 phase system.AnswerYou don't get voltage 'phase-to-phase'; it's 'line-to-line'!


Phase to ground voltage?

There is such a thing, what is your question?


If in the three phase connection phase to phase voltage is 400v what will be the phase neutral voltage?

The formula to use is, phase voltage /1.73 = phase to neutral (ground) voltage.CommentThere is no such thing as a 'phase to phase', or 'phase to neutral' voltage. The correct terms are 'line to line' and 'line to neutral'. So the above answer should read: line voltage/1.73= line to neutral voltage = phase voltage.


Why there is two voltage rating on the same cable like 300V or 500V?

The first figure indicates the phase to neutral or ground voltage and the second is the phase to phase voltage. i.e. Vph-ph = 1.732Vph-n


How many volts in a single phase?

that would depend on the voltage depends on the area of the world that you live in. every country has different transmission voltages. in India we have single phase transmission voltage of 220V, where as in the USA it is 110V


Is the voltage in a three-phase system stated by the phase-to-phase or phase-to-ground voltage e.g. 500kV or 290kV?

The voltage in a three phase delta system is stated by the phase to phase voltage. If it is a wye connection the phase to neutral is represented by the two voltages. e.g. 120/208, 240/415, 277/480, 347/600, 7225/12500, etc.


Should there be voltage between ground and each hot of a three phase power system?

There are two types of connections in three phase systems. One is a delta connection where there is no connection to ground, so you should not get any voltage to ground. This is classed as a three phase three wire system. In this type of system any one of the phase wires could become grounded and no one be the wiser. Code requires that grounding lights be added to a delta system to visually show what the phase condition is in relationship to ground. The other type of system is a wye or star point connection. This is classed as a three phase four wire system. In this type of connection the coil ends are all joined together and grounded. You would have voltage between the phases and a lower voltage to ground. The voltage to ground would be the phase voltage divided by 1.73.Yes. If there is no voltage between a hot and a ground, either the hot isn't really a hot or the ground isn't really a ground.AnswerThere is always a potential difference between a line conductor and ground, regardless of whether it is a three-wire system or a four-wire system. This is due to the capacitance between line and ground.


What is arcing ground?

Arcing Grounds is a phenomenon which is observed in ungrounded three phase systems. In ungrounded three phase systems operating in a healthy balanced conditions, capacitances are formed between the conductors and ground. The voltage across these capacitances is the phase voltage


High voltage current is needed for transmission but is low voltage is more useful?

A: Power transmission is in the range of 500 kilo volts as someone can tell the hi towers are far above ground and each phase is separated by ceramic insulators. Low voltage is necessary to manage these power safely to homes and business. That is why transmission becomes distributions and finally local power to us.


How do you wire a 110 V DB board from a 220 V 3 phase transformer supply?

In a wye system the voltage between any two wires will always give the same amount of voltage on a three phase system. However, the voltage between any one of the phase conductors (X1, X2, X3) and the neutral (X0) will be less than the power conductors. For example, if the voltage between the power conductors of any two phases of a three wire system is 220v, then the voltage from any phase conductor to ground will be 110v. This is due to the square root of three phase power. In a wye system, the voltage between any two power conductors will always be 1.732 (which is the square root of 3) times the voltage between the neutral and any one of the power phase conductors. The phase-to-ground voltage can be found by dividing the phase-to-phase voltage by 1.732 answer from ground and any phase


What is the three phase voltage in Pakistan?

Pakistan has a 220 v 50 Hz domestic supply and the three-phase voltage is sqrt(3) times higher, or 381 v. Higher voltage are also used for three-phase power transmission.


Is transmission line voltage phase to phase?

Yes usually it would be phase to phase voltage because most transmission lines are set up in a delta configuration. This means that there is no neutral conductor to use as a reference. So any voltage would be measured with reference to another phase.CommentLet's get the terminology correct. The voltages between the three 'hot' lines of a three-phase, three- or four-wire, system are called 'line voltages' even though, in the case of a delta-connected system, they are numerically-equal to the corresponding phase voltages. Therefore, we call the conductors 'line conductors', not 'phase conductors'.There is simply no such thing as a 'phase-to-phase' voltage. Just think about it; you can only measure a voltage acrossan individual phase, so how can you possible measure a voltage 'phase-to-phase' -I mean, where would you place a voltmeter to do that?For a delta system, the line voltage (or line-to-line) voltage is numerically equal to the phase voltage (notphase-to-phase). For a star (or 'wye') system, the line voltage is equal to 1.73 x the phase voltage.