The 2008 NEC code states that conduit must be strapped within 36" or 3 feet from every box or connector, then every 5 feet is acceptable from there.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the code for strapping EMT conduit from a box?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

When exist a junction box EMT conduit must be supported with how many inches?

When exist a junction box EMT, conduit must be supported within 18 inches.


How far from a junction box must emt conduit be strapped?

I always put the first EMT clip/strap 1 foot or 12 inches away from the junction box, then every 5 feet or so after that.


What is the maximum degree of bends allowed for 1 inch emt?

All conduit shall not have more than 360 degrees for it's length between either a box, cabinet, or conduit body. Couplings count as a continuation of conduit.


What is a 52151k box?

A 52151k box is an electrical junction box. The dimensions are 4" x 4" x 1 1/2" deep. They are mostly used in EMT conduit systems. They have no connectors just stamped knockout positions to allow for an EMT connector. The knock out positions are usually removed by punching them out with a screwdriver or using a pair of pliers to twist them out. The cover for the box has to be ordered separately.


What combinations of bends in a conduit run require the use of a pull box?

Code states no more that 4 - 90 degree bends in a conduit run between pull boxes.


What is a electrical pull box?

A pull box is a junction box that is placed in long conduit runs to make the pulling in of the wires easier. The code only allows 4 one quarter bends between pull boxes. If the conduit run incorporates more that 4 bends then a pull box has to be inserted into the run. The code allows up to the "equivalent" of four quarter bends or 360 degrees total before pull box is required.


When do you use a conduit bushing?

A conduit bushing is used when a conduit is terminated in a junction box or enclosure. Its purpose is to provide a smooth rounded surface so that when the wire is pulled into the conduit the insulation on the wire will not be damaged.


How many bends in a conduit run would be required before the use of a pull box?

There has to be a pull box between every four quarter bends in a conduit run.


How far apart should straps be place on electrical metallic tubing conduit?

Assuming your local jurisdiction adopts the NEC as code, EMT must be fastened within 3 feet of each termination point (box, cabinet, conduit body, etc.) and every 10 feet of conduit run. Where the (horizontal run) EMT passes through a hole in a framing member is allowed to count as a support in lieu of a strap. You can place fasteners closer if you want, but not further apart. There are two exceptions. #1 You can increase distance "within 3 feet of a termination" to 5 feet where structural members do not readily permit fastening within 3 feet. #2 For concealed work in finished buildings or prefinished wall panels where such securing is impractical, unbroken lengths (without couplings) of EMT shall be permitted to be fished. Reference 2005 NFPA 70 (NEC) 358.30(A)(B) Of course if you do not live in the US, or if your local municipality has adopted a different code or adopted the NEC with ammendments, your local law could be different. Check with the local building department to be sure.


What are the advantages and disadvantages of steel junction boxs?

There are no advantages or disadvantages over which type of junction box to be used on electrical wiring. As long as the junction box is of an approved type (CSA or UL approved). It is cost or location which dictates which boxes will be used. PVC boxes for home wiring are the cheapest. Aluminium or steel are usually used in rigid or EMT conduit systems. PVC again when the conduit system involves underground wiring. In large electrical installations it is the electrical engineer that states what the conduit system type is and what type of electrical junction boxes that must be used.


When running flexible conduit it is required to strap the inches from a box coupling or connector and requires a strap every feet thereafte?

When runing flexible conduit it is required strap the it inches from a box coupling or conector


When running flexible conduit it is required to strap the it inches from a box coupling or connector and requires a strap every feet thereafter?

When runing flexible conduit it is required strap the it inches from a box coupling or conector