Phase to phase voltage is 1.732 (the square root of 3) times the phase to star point (neutral) line voltage.
e.g. if the line voltage is 220V
phase voltage = 1.732x220 = 380V (approx)
Additional AnswerYou might also like to know that the line voltage leads the phase voltage by 30 electrical degrees. And, incidentally, the correct expressions are 'line-to-line' not 'phase-to-phase', and 'line-to-neutral' not 'phase-to-neutral' (think about it, a line voltage is measured from the junctions between adjacent phases, so they cannot be 'phase to phase'!)
A star-connection is associated with a three-phase, four-wire, system which comprises three line conductors and a neutral conductor. The voltage between any two line conductors is called a line voltage, whereas the voltage between any line conductor and the neutral conductor is called a phase voltage. For a balanced system, the line voltage is 1.732 time the phase voltage. So, when a 400/230 V system is being discussed, the line voltage is 400 V and the phase voltage is 230 V.
The standard three-phase distribution transformer in the UK is a delta/star connection with a rated primary line voltage of 11 kV, and a nominal secondary line voltage of 400 V, giving a secondary phase voltage of 230 V.So, the secondary provides a three-phase, four-wire, system comprising three line conductors and a neutral conductor. The line-to-line (line voltage) voltage is 400 V and the line-to-neutral (phase voltage) voltage is 230 V.There are not 'three types' of supply obtained from this arrangement.
The power of all three phases can be transmitted on three conductors.A star connection, as opposed to a delta, provides a grounding reference. Also, for ground faults on the secondary (assuming no delta third winding, or source third winding) will be a direct ratio similar to phase faults, instead of 57%. Another reason is to avoid the inherent phase shift involved in a delta/star configured transformer.Another AnswerA 'star-connected' secondary is the standard European connection for a three-phase distribution transformer, as it provides a line voltage of 400 V together with a phase voltage (i.e. line to neutral) of 230 V.
On a three phase system with a line to line voltage of 13800, a wye connection will give you a voltage of, 13800/1.73 = 7977 volts to ground.
High voltage transmission and distribution lines utilise three-phase electricity. There are two commonly-used connections used in this system, termed a 'delta' and a 'star' (or 'wye') connection. A delta connection provides three energised conductors, termed 'line conductors', while a star connection provides three energised conductors ('line conductors') together with a neutral conductor. However, in the case of a star connection, provided the load is balanced, no current flows through the neutral conductor. In the case of high-voltage transmission and distribution lines, their loads are very close to being balanced, so there is no need to provide a neutral in the case of a star-connected system, as any slight imbalance can be compensated for in slightly different line currents.
In a high voltage installation, with the same power, current drawn is small compared to those in low voltage. However it requires a thicker insulation, thus cost of insulation is significant compared to the conductor cost. By using a star connected winding, the insulation voltage required is equal to line to neutral connection, otherwise if it is connected in delta the insulation rating has to be provided for a line to line connection. Despite having a higher current, the total cost is still lower compared to using a higher insulation rating.
In a distribution transformer's star-connected secondary, the common point of connection is called the 'star point' and is connected to earth. The star point then provides the neutral connection for the transformer secondary, providing a return path for any unbalanced currents due to an unbalanced three-phase load.This arrangement provides a four-wire distribution system, comprising three line conductors and one neutral conductor (in addition, there are various methods of providing an earth connection to consumers). The line-to-line voltage is called a line voltage (in the UK, 400 V), while a line-to-neutral voltage is called a phase voltage (in the UK, 230 V). The line voltage being 1.732 x phase voltage.
It isn't. It's the other way around. The line voltage is 1.732 times the phase voltage. The figure results when you vectorially add the relevant phase voltages.
normally delta connection wired in 3 phase induction motor. during starting wiring is in Star and after running normal speed changeover to delta .beacause starting time its phase voltage equals less root3 times of line voltage ,line current and phase current equals. in Delta phase voltage and line voltage equals, and phase current equals root3 times line current
In star the voltage from line to neutral is 1/sqrt(3) times the nominal voltage, while the load current equals the line current. In delta the voltage between lines is the nominal voltage, while the load current is 1/sqrt(3) times the line current (for a balanced load). So a delta load needs 3 times the resistance compared to a star load of the same power.
Probably the reason is in the different voltages between the star and delta connection voltages. An electromagnetic brake designed for the lower voltage of the star connection would burn out or open when introduced to the higher voltage of the delta connection.
in low voltage connection in wye (star conncetion) 415v high voltage connection in delta 480v
The standard three-phase distribution transformer in the UK is a delta/star connection with a rated primary line voltage of 11 kV, and a nominal secondary line voltage of 400 V, giving a secondary phase voltage of 230 V.So, the secondary provides a three-phase, four-wire, system comprising three line conductors and a neutral conductor. The line-to-line (line voltage) voltage is 400 V and the line-to-neutral (phase voltage) voltage is 230 V.There are not 'three types' of supply obtained from this arrangement.
The voltage phase shift between primary and secondary connections in a transformer is 180 electrical degrees.
On a three phase system with a line to line voltage of 13800, a wye connection will give you a voltage of, 13800/1.73 = 7977 volts to ground.
The power of all three phases can be transmitted on three conductors.A star connection, as opposed to a delta, provides a grounding reference. Also, for ground faults on the secondary (assuming no delta third winding, or source third winding) will be a direct ratio similar to phase faults, instead of 57%. Another reason is to avoid the inherent phase shift involved in a delta/star configured transformer.Another AnswerA 'star-connected' secondary is the standard European connection for a three-phase distribution transformer, as it provides a line voltage of 400 V together with a phase voltage (i.e. line to neutral) of 230 V.
Star 220 v and delta 400 i star 58 percent only voltage applied delta 400v appliedAnswerThese figures do not represent three-phase, four-wire, system voltages, because if the line voltage were to be 440 V, then the phase voltage would be 254 V; or, if the phase voltage were to be 220 V, then the line voltage would be 381 V.
High voltage transmission and distribution lines utilise three-phase electricity. There are two commonly-used connections used in this system, termed a 'delta' and a 'star' (or 'wye') connection. A delta connection provides three energised conductors, termed 'line conductors', while a star connection provides three energised conductors ('line conductors') together with a neutral conductor. However, in the case of a star connection, provided the load is balanced, no current flows through the neutral conductor. In the case of high-voltage transmission and distribution lines, their loads are very close to being balanced, so there is no need to provide a neutral in the case of a star-connected system, as any slight imbalance can be compensated for in slightly different line currents.