A transformer's 'no load' current is not 'high'. On the contrary, it is zero!
'No load' means that there is nothing connected to the secondary (output) of the transformer -i.e. it is an open circuit. So a transformer's secondary 'no load' current is zero! The primary current still has to provide a magnetising current, but that current will be very small.
Don't forget, a 'light load' means little current is drawn, so the load must have a high resistance; a 'heavy load' means lots of current is drawn, so the load must have a low resistance.
there is current flow in the primary winding only not in secondary winding, primary current due to the energization of the core. it is considerably less.
AnswerWhen we describe a transformer having a 'no-load current', we are describing the current flowing in the primary winding when the secondary winding is open circuited and, therefore, not supplying a secondary current.
The primary 'no-load current' (Io) is determined by dividing the primary supply voltage by the impedance of the primary winding. This impedance is made up of a resistance that is very small in comparison to its inductive reactance and, therefore, the no-load current lags the supply voltage by very nearly 90 degrees. This current can be resolved into a magnetising current (Im), which lags the supply voltage by 90 degrees and is responsible for setting up the magnetic flux in the core, and a current (Ii) which is in phase with the supply voltage, and supplies the losses in the transformer.
No loaded condition the current on the primary side provides only core or iron loss.
there is no current at the secondary winding.
The no load current of a transformer is mostly due to eddy current losses in the iron core.
Mostly eddy currents in the transformer core.
It is a transformer with No load attach to it.
2 to 5% of full load current
To calculate the no load current from transformer & core loss is also calculated.
If the load current is too high, the power lost in the transformer windings will be too high and it will overheat. If the voltage is excessive, the power lost in eddy currents in the magnetic core will be too high and it will overheat.
When the value of the load resistance in a transformer is changed, it will affect the current flowing through the circuit. Increasing the load resistance will decrease the current, while decreasing the load resistance will increase the current. This change in current will in turn affect the voltage across the load and the efficiency of the transformer.
load
It is a transformer with No load attach to it.
2 to 5% of full load current
No load current is energizing current. This is effectively "lost" power, power used in the transformer to energize the core. It, therefore, should be small!
is it primary current ?
To calculate the no load current from transformer & core loss is also calculated.
No load current, in a transformer for example, is the current necessary for exciting the transformer. If you wish to keep it energized, and you need to keep it energized at full voltage, there is nothing you can do to reduce this other than replace the transformer with one that has lower no load current. If you are referring to a different piece of equipment, you may need to specify what you are meaning by "no load current".
When the secondary of a transformer is opened, there is no longer any load on the transformer. There will be some current flowing in the primary winding, which is needed to induce the voltage in the secondary. This primary current is referred to as the "no load" current, and is indicative of the core losses in the transformer.
If the load current is too high, the power lost in the transformer windings will be too high and it will overheat. If the voltage is excessive, the power lost in eddy currents in the magnetic core will be too high and it will overheat.
When the value of the load resistance in a transformer is changed, it will affect the current flowing through the circuit. Increasing the load resistance will decrease the current, while decreasing the load resistance will increase the current. This change in current will in turn affect the voltage across the load and the efficiency of the transformer.
No load current depends on the design of the transformer, and what voltage it is energized at. It will typically be below 1% of full load, and can be significantly below 1% for utility sized transformers.
The secondary current is determined by the load, not by the transformer. For example, if the secondary voltage is 50 V and the load is 100 ohms, then the secondary current will be 0.5 A. If the load is 25 ohms, then the secondary current will be 2 A. It is important that a continuous secondary current doesn't exceed the rated secondary current of the transformer.