answersLogoWhite

0


Best Answer

The 'hot' wire delivers current from the power station into the load, which could be any electrical appliance such as, for example, a fridge, a light or a motor.

The 'neutral' wire is there for the specific purpose of carrying the current coming out of the load back to the power station. If the neutral wire was not there, there would not be a complete electrical circuit from the source (power station) to the load and back to the source.

In normal operating conditions the connection from the neutral wire to the Earth does not carry any current.

There should always be 0 V (zero volts) between the neutral wire and the Earth. i.e. no potential difference should ever exist between the neutral wire and the Earth.

The "neutral to earth" connecting wire is fitted to ensure that no part the neutral side of the circuit can develop a high voltage above Earth. If that connecting wire wasn't in place and the circuit had no other protection device (such as a GFCI or RCD) fitted, a very dangerous electrical shock hazard could be present which could electrocute the people using the appliance.

That is why any grounding wires, fitted either to the appliance or to the breaker box, should never ever be cut or removed.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

12y ago

Kirchoff's Current Law states that the signed sum of the currents entering a node is zero. If the neutral point is the node, then, in a balanced system, hot matches hot, resulting in no current through neutral. Any imbalance, either due to neutral to hot current flow that is not balanced by neutral to opposite hot current flow, or due to ground fault, will result in a current flow on neutral, so that the sum of zero is maintained.

When you think about this, remember that the law said "signed" and "entering". When you analyze a circuit, simply be consistent in your usage. For instance, in a balanced system, current entering the neutral node from one hot side is considered positive, and the current entering the neutral node from the other hot side is considered negative, i.e. it is leaving, not entering.

Ground fault will, of course, "change the rules", because you no longer have only three paths to that neutral point node. In fact, that is how ground fault current interrupters (GFCI's) work - they measure outbound current and compare it to inbound current - they must be equal and opposite, i.e. they cancel each other out - otherwise there is another path - a ground fault - and the device trips.

This answer is:
User Avatar

User Avatar

Wiki User

11y ago

Unbalanced neutral current does not flow to earth unless in case when there is a neutral to earth contact on the consumer side of the supply.

In such case, the earth leakage protection unit will then be activated because there's an imbalance between the currents flowing through the three lines, of a three phase power supply, and the neutral. The imbalance come about because part of the neutral current is flowing back to the supply through the consumer earth continuity conductor. The sum of currents flowing to the consumer must be equal to the sum of currents flowing back from the consumer.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Why doesn't current flow through the neutral to earth?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Why dont you use earth wire place of neutral?

Earth is neutral, but only at the distribution panel and upstream from it. Downstream of the distribution panel, earth and neutral shall not interchange or cross connect their connections or their roles - earth is protective ground - and neutral the current carrying return conductor.


What is the permissible neutral current?

I think you mean "what is the permissible imbalance between live and neutral current" All current supplied by the live wire should exit via the neutral. Any imbalance leaving via Earth is detected by an earth leakage circuit breaker . They trip at about 30 mA.


Is a neutral considered a current carrying conductor?

No, in a three phase balance load, there should not be any current through Neutral conductor. If it is a 2 wire, single phase system, the Neutral will carry the same current as live conductor if the system has no Earth fault, leak.


What is the reason for using a neutral current transformer on a transformer?

A current transformer is primarily used at the neutral point of a transformer for earth fault protection. A neutral current transformer will measure any ground fault current which will essentially flow from the star point of the transformer. A fault-detection device other devices is connected to the current transformer and, if the fault current exceeds a certain trigger value, the fault-detection device will give a trip command to an earth-fault relay to disconnect the supply of electricity to the transformer.


In the electrical system of the US what is the difference between the neutral and the PE Ground?

US NEC: The neutral conductor is an insulated grounded conductor used as the current return in a circuit. The color designation for neutral is white. The protective ground (PE, protective - earth) is a non-insultated grounding conductor used to shunt fault current to ground, tripping the protective device. The color designation for PE ground is green. Neutral and PE ground are tied together at the distribution panel. PE ground is also connected to a solid earth ground, such as grounding rods driven into the earth. Downstream of the distribution panel, PE ground is never used to carry operational current. Any current flow on PE Ground, other than parasitic current, is considered a ground fault, which must be corrected. In fact, GFCI (Ground Fault Current Interrupting) breakers will trip when neutral current does not match hot current, an indication of PE ground current flow.

Related questions

What would happen if the live and neutral wires were crossed in a 3 pin household plug?

Current in a standard house is AC (alternate) so it doesnt matter if the live and neutral are crossed. Should the earth and live be crossed then the earth leakage would trip


What will happen without a neutral wire?

Current needs a return path to earth to flow. The neutral carries this flow. Therefore, no neutral and no current flow.


What happened if no neutral you can use a ground?

system will b damaged or destroyed in case of failures.............if we provide neutral d short ckt current passed through earth directly ,with out disturbing the system


How do you reduce neutral to earth voltage in three phase system?

It is done by connecting the neutral to earth at the transformer that produces the three-phase supply. If the three phase wire supply equal currents, there is no current in the neutral wire and its whole length stays at earth potential, but if there is current in the neutral it produces a small voltage on the neutral at places away from the transformer.


What is the neutral current?

I think you mean "what is the permissible imbalance between live and neutral current" All current supplied by the live wire should exit via the neutral. Any imbalance leaving via Earth is detected by an earth leakage circuit breaker . They trip at about 30 mA.


Why dont you use earth wire place of neutral?

Earth is neutral, but only at the distribution panel and upstream from it. Downstream of the distribution panel, earth and neutral shall not interchange or cross connect their connections or their roles - earth is protective ground - and neutral the current carrying return conductor.


What is meant by neutral grounding reactor?

Neutral-earthing reactors or Neutral grounding reactors are connected between the neutral of a power system and earth to limit the line-to-earth current to a desired value under system earth fault conditions.


What is the permissible neutral current?

I think you mean "what is the permissible imbalance between live and neutral current" All current supplied by the live wire should exit via the neutral. Any imbalance leaving via Earth is detected by an earth leakage circuit breaker . They trip at about 30 mA.


Why do outlets have 3 holes?

Live, neutral and earth. The supply is carried on the live and neutral, and the earth normally carries no current, but if there is a fault the earth is there as a safety factor and in some conditions it carries enough current to blow the fuse and make the circuit safe.


What is a restricted earth neutral system?

appropriate resistance is to be inserted between the neutral point of the transformer and the earthing mat to restricted earth fault current. for this purpose a sensitive earth leakage relay is used. in the event of a fault, fault current returning to the system neutral trips an earth leakage relay and disconnects the supply. anand r. ambekar


What is neutral inversion?

If the consumers metalwork is not bonded to the neutral a direct earth fault would result in a current of 20 amps flowing.This fault current will probably be carried by a 16 amp fuse or citcuit breaker and returned to the neutral via electrodes this will force the neutral conductor up to a potential of 200 v above earth this is known as neutral inversion


Is a neutral considered a current carrying conductor?

No, in a three phase balance load, there should not be any current through Neutral conductor. If it is a 2 wire, single phase system, the Neutral will carry the same current as live conductor if the system has no Earth fault, leak.