The neutral, or 'star point', of a star (or 'wye') connected transformer secondary is grounded (earthed) in order to ensure that the phase voltages are balanced -i.e. each of the line-to-neutral voltages are identical. If the star point was not earthed, and the load currents were unbalanced (due to an unbalanced load, supplied by that transformer), then a situation called a 'floating neutral' would arise, causing the transformer to have different line-to-neutral voltages (both in magnitude and phase).
In addition to this, the presence of harmonic (multiples of the mains' frequency) currents can cause the potential of an unearthed neutral point to 'cycle' or 'oscillate'. This phenomenon of 'oscillating neutral' is avoided by allowing any harmonic currents pass to earth, thereby saving the circuit from voltage unbalances due to these harmonics.
You connect neutral and earth ground together at a distribution transformer because neutral is supposed to be at ground potential. The two are also connected at each distribution panel. Even so, current return is via neutral, not ground - any other path reflects a ground fault, which is an unsafe condition. The purpose in connecting neutral to ground is so that faults in devices that cause hot to ground current paths either trip a GFCI breaker, or they trip an ordinary breaker for the case where fault current is high. Excessive hot to neutral currents also trip breakers - instantaneous for short circuits - and timed for moderate overloads that last beyond the inrush time limit. If you did not connect neutral to ground, and all of the local grounds were also open, then the hot legs could rise to the primary voltage. In a 13.2kv US system, the primary is 7.6kv to ground, star configuration. That amount of voltage inside a building, connected to devices expecting 120, 240, or 480 volts, would be catastophic and extremely hazardous.
The transformer secondary is considered a separately derived system and is treated like an electrical service. The neutral and grounding conductor are bonded at the main service disconnect, so on a separately derived system you do the same. Also in the event this may be on a control transformer, by bonding the neutral to ground, a short to ground on the ungrounded conductor would blow a fuse and prevent electrical shocks and injury.
Protective earth ground and neutral are connected together at a utility distribution transformer, and again at a distribution panel, for two reasons...
The connection creates one half of the circuit that might be completed in the event of a ground fault in the circuit. This protects the circuit, the load, and people by tripping the protective device.
The connection also prevents leakage current in the transformer from raising the potential of the secondary to the potential of the primary. If all of the earth grounds were removed, the voltage in the secondary circuit could become very high. In the US, for a typical primary voltage of 13.2KV and a secondary voltage of 120/240V, the secondary (common mode) voltage could become 7.6KV, a lethal voltage.
Power Transformers are three-phase transformers used in the electricity supply system. If the secondary is star (wye) connected, it is necessary to earth (ground) the star point (neutral point) because an unearthed star point could result in a 'floating neutral', which could cause unbalanced phase voltages. An earthed secondary winding also provides protection to the secondary circuit from an insulation breakdown between the primary and secondary windings.
To protect transformers against ground fault currents
It makes sense to earth one of the supply wires, for safety, and that one is called the neutral.
step up transformer neutral is grounded:
1) To avoid leakage current.(body earthing)
2) Balancing the phase difference( neutral earthing).
In order to maintain balanced phase voltages when the transformer supplies unbalanced loads.
This terminology usually refers to pad mounted transformers. A "radial feed " transformer is a transformer that has one bushing for the high voltage cable line. The high voltage cable terminates into the transformer through the transformer's bushing. There is no second bushing for the high voltage cable to continue further down the line. This type of transformer is usually on the end of a loop feed circuit. This is different from a "loop feed" transformer whose incoming cables are terminated at the primary bushings. On this type of transformer there is a second bushing which connects to the outgoing primary voltage cables that allows the primary to feed another transformer. Each pad mount transformer's secondary feed usually supplies enough power to connect up to four homes.
Yes
It is the terminal on the megger that the ground cable connect to when testing a device to ground.
An 'RMU' is a 'ring-main unit', a type of switchgear used to connect distribution transformers to an underground, secondary-distribution (11 kV in the UK), cable ring-main system. It enables the transformer to be disconnected from the ring main, and it also enables the ring main itself to be 'split' where the RMU is installed. Each of the three switches within an RMU usually incorporates an 'earth' (ground) position, which will enable either the transformer itself, or the ring main to be earthed for safety reasons before any maintenance work can proceed.
Primary : 4 Secondary : 3/0 <<>> To answer this question correctly a voltage must be stated.
Parking brake cable? Connect to the cable from the opposite side and the emergency brake cable from the control inside the cab. Self-adjusting cable? Connects to the "star wheel" and the brake shoe return spring inside the drum
You would need what is called a crossover cable. It is basically an ethernet cable with 2 of the wires swapped on one end. This swapping is usually done inside a switch but has to be physically done on the cable if you are trying to connect direct. You also have the option of using special USB cables to connect computers directly.
This terminology usually refers to pad mounted transformers. A "radial feed " transformer is a transformer that has one bushing for the high voltage cable line. The high voltage cable terminates into the transformer through the transformer's bushing. There is no second bushing for the high voltage cable to continue further down the line. This type of transformer is usually on the end of a loop feed circuit. This is different from a "loop feed" transformer whose incoming cables are terminated at the primary bushings. On this type of transformer there is a second bushing which connects to the outgoing primary voltage cables that allows the primary to feed another transformer. Each pad mount transformer's secondary feed usually supplies enough power to connect up to four homes.
Yes
crossover cable is used to connect two switches.
Yes, you can connect a PS3 to an HDTV by a component cable or an HDMI cable.
Always connect the positive (RED) cable first.
It is a cable that can connect to other cables
ROLLOVER Cable
No, just connect the cable to the cable modem and then connect the modem to the computer.
Connect a audio cable from the Audio Out connectors on the cable box to the AUX In Audio connectors on the stereo receiver.
No. You need to connect the ethernet cable to a modem or router. You can disconnect the PC ethernet cable from the modem and connect an ethernet cable from the Xbox 360 to the modem until you purchase a router.