If they're connected one at a time ... first one and then the other ... then each one has 120 volts
across it while it's connected to the supply.

If they're connected across the supply at the same time in parallel, then of course they have the
same voltage across them, because their ends are common.

If they're connected across the supply in series, then the voltage across the 50-ohm load is 40 volts,
and the voltage across the 100-ohm load is 80 volts.

User Avatar

Wiki User

14y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

14y ago

No. The voltage would be split between the two loads - in this case, 1/3 of the voltage for the 50 Ohm load, and 2/3 of the voltage for the 100 Ohm load.

No. The voltage would be split between the two loads - in this case, 1/3 of the voltage for the 50 Ohm load, and 2/3 of the voltage for the 100 Ohm load.

No. The voltage would be split between the two loads - in this case, 1/3 of the voltage for the 50 Ohm load, and 2/3 of the voltage for the 100 Ohm load.

No. The voltage would be split between the two loads - in this case, 1/3 of the voltage for the 50 Ohm load, and 2/3 of the voltage for the 100 Ohm load.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

No. The voltage would be split between the two loads - in this case, 1/3 of the voltage for the 50 Ohm load, and 2/3 of the voltage for the 100 Ohm load.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: Would a 50 ohm load and a 100 ohm load connected to a 120 volt supply have the same voltage?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Is a relay defect and open load the same?

A relay is basically a controllable switch that connects a supply voltage to a load. If the relay is switch such that the load is not connected, that could be considered an open load. If it is switched the other way the load will be connected to its supply voltage. A defect in a relay would be something that caused it not to function correctly. It could be in the switch portion of the supply portion of the relay. Hence you are referring to different things and a defect may or may not cause the load to be open.


Why instruments are connected on low voltage side of the transformer while performing no load test?

since we need to get desired or rated voltage, so if it is connected in high voltage side of the transformer, voltage supply will be more, and hence the current will be more than the required amount. this is the reason why the instruments re connected at the low voltage of the transformer while performing no load test.


What is open circuit voltage when load is connected?

As load is conected in circuit , so thre is no open circuit therefore there would not be any open circuit voltage.


What is the effect on the supply current if the capacitor removed?

It depends on how the capacitor is connected and whether the supply voltage is a.c. or d.c. Assuming you are talking about a power-factor improvement capacitor (connected in parallel with an inductive load, supplied with a.c.), then the supply current will reduce.


How to figure out ampreage in a circuit?

For a d.c. circuit, you divide its supply voltage by the resistance of its load. For an a.c. circuit, you divide its supply voltage by the impedance of its load.

Related questions

Is a relay defect and open load the same?

A relay is basically a controllable switch that connects a supply voltage to a load. If the relay is switch such that the load is not connected, that could be considered an open load. If it is switched the other way the load will be connected to its supply voltage. A defect in a relay would be something that caused it not to function correctly. It could be in the switch portion of the supply portion of the relay. Hence you are referring to different things and a defect may or may not cause the load to be open.


What is the load side of a transformer?

The load side of a transformer feeds the device, such as a light or motor. It is the output of the transformer. The input, or line side, provides the voltage that is to be transformed, either up or down, to supply the load side.AnswerA transformer's primary winding is connected to the supply voltage, and the secondary winding is connected to the load.


What is the term for the transformer winding to which the load is connected?

The load is connected to the transformer's secondarywinding, while the primary winding is connected to the supply. The terms, 'primary' and 'secondary', do NOT relate to voltage levels.


What are the primary winding and secondary winding of a transformer?

The primary winding is the winding connected to the supply, while the secondary winding is the winding connected to the load. The terms, 'primary' and 'secondary' are unrelated to voltage levels.


Why instruments are connected on low voltage side of the transformer while performing no load test?

since we need to get desired or rated voltage, so if it is connected in high voltage side of the transformer, voltage supply will be more, and hence the current will be more than the required amount. this is the reason why the instruments re connected at the low voltage of the transformer while performing no load test.


What happens to voltage in a step down?

The voltage induced into the secondary winding will be lower than the voltage applied to the primary winding. The primary winding being the winding connected to the supply, while the secondary winding is the one connected to the load.


How do you check the under voltage relay?

The way you check to see if an under voltage relay is wired properly is to disconnect the electrical supply. If the device that is connected to the load side of the relay does not start up or energize when the electrical supply is reconnected, then the relay is connected correctly.


What is open circuit voltage when load is connected?

As load is conected in circuit , so thre is no open circuit therefore there would not be any open circuit voltage.


What will happen if single phase load is connected to three phase circuit?

To obtain a single-phase supply from a three-phase supply, the single-phase load must be connected either (a) between any pair of line conductors, or (b) between any line conductor and the neutral conductor. Of course, the voltage obtained from either of these connections must match the voltage rating of the load.


What is the effect on the supply current if the capacitor removed?

It depends on how the capacitor is connected and whether the supply voltage is a.c. or d.c. Assuming you are talking about a power-factor improvement capacitor (connected in parallel with an inductive load, supplied with a.c.), then the supply current will reduce.


Two technicians are discussing how to measure the voltage outputs of a power supply. Technician A says that the power supply must be connected to the system and turned on before voltage can be measu?

It does have to be turned on. A highly regulated PS will be the same under load as without a load. But it may not be able to supply the amps. Best connect it and test it. WHO WON?


. Two technicians are discussing how to measure the voltage outputs of a power supply. Technician A says that the power supply must be connected to the system and turned on before voltage can be measu?

It does have to be turned on. A highly regulated PS will be the same under load as without a load. But it may not be able to supply the amps. Best connect it and test it. WHO WON?