Ohms law says that watts are equal to volts times amps.

240v X 13.5a = 3240 va

VA / 1000 = Kva

So, your load requires 3.24 Kva. The transformer should have a rating greater than this as a safety factor, so you would choose the next larger size, in this case probably a 5 Kva transformer with a 480v primary and a 240v secondary.

Your local electrical codes may require a larger safety factor, so you would want to consult them before buying the transformer!

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

13y ago

240v x 13.5A = 3.24kVA, single phase transformer.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What KVA transformer is needed to convert 480v - 240v 13.5A load?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

Can you lower 277v to 240v?

With a transformer.


Can you convert a 120 volt Yamaha clavinova to 240 volts?

Electronic technician will convert in no time. You need 240v power transformer in place of same wattage 120V. Super easy.


What would the control voltage be for a transformer marked 240v 24vac?

A control transformer marked 240V - 24Vac would have a control voltage of 24 volts.


How can you convert 240v to 120v for ac?

Use a step down transformer 240 primary to 120 secondary. You must know what the connected load (amps) is so that you don't overload the transformer. Small transformers are rated in VA.


A transformer has a primary volt of 240v and a secondary volt of 48v what is the turn ratio?

3


If the loads were only 240v on a single phase 240v system with a center tapped transformer the neutral conductor would carry?

If a load were only 240 volt on a single phase 240v system with a center tapped transformer the neutral conductor would carry no current.


How do you convert a 4 prong 240V outlet to a 3 prong 240V outlet?

Disregard the neutral


Which is more efficient 12v or 240v downlight?

If they are both using the same watt globes the 240v is slightly more efficient due to small losses in the transformer.


A 240V to 480V Step up transformer with a load of 85 amps at 480v what amperage will the transformer draw if the primary is 240V?

Since this transformer has a ratio of 1:2 the load current on the 480V side just has to be doubled. 85 x 2 = 170A on the primary. 40.8 KVA transformer. To prove this just find the KVA of both sides and they should be equal.


Convert 140va at 240v equals amps?

0.583333333333


Can a 240V - 110V stepdown transformer be reversed to take a primary load of 180V to secondary 240Volts?

No


Can 240v tools be converted to 110v?

It would be better if you got a transformer and stepped up the voltage.