Since sufficient feedwater is not supplied into the economizer
though the heat is absorbed from flue gas at the boiler start-up
and low load operation, steaming may occur in the economizer.
Therefore the economizer recirculation line is provided between the
furnace downcomer and the economizer inlet feedwater piping. This
line provides the recirculation flow between the drum, the
downcomer and the economizer so as to prevent steaming in the
economizer. Economizer recirculation valve is only opened at
initial stage of the boiler start-up.