power = apparent power x cosine (phase angle)
reactive power = apparent power x sine (phase angle)
(where apparent power = supply voltage x load current)
kV is kilovolts, kW is kilowatts, kVA is kilovolt amps and kVAR is kilovolt-amps reactive. A common formula is kVA-squared = kW-squared + kVAR-squared.
kvar = kva*sin@
kvar = kva*sin@
For normal power factors (pf=80%), you have 0.8 kW for every kva. In general however, kW = pf x kVA. Where pf is the power factor, it is the cosine of the angular difference between the voltage and the current of a circuit in alternating current circuits.
It depends on the power factor of the load, but for a load power factor of 0.7 on a 2000 kVA transformer the real power and reactive power are both 1400 kilo (watts and VAR). So a 1400 kVAR capacitor on the load would restore the power factor to 1, allowing 2000 kW to be drawn instead of only 1400 kW.
kvar can be calculated as follows the a product KVA andt the sine of the angle between the KVA and KW.
The formula is that kW^2 + kVAR^2 equals kVA^2 or if you prefer, the kW and the kVAR are the two sides of a right angled triangle and the kVA is the hypotenuse. So here you have a 3-4-5 triangle times 140, in other words 420-560-700, and the kVAR is 420.
The KVAR will be 1249.75, the power factor is .7. KVAR = sqrt [ KVA^2 - kW^2 ]
{| |- | capacitance of the capacitor is mentioned in KVAR. Formula : KVAR = KW*tan@ FOR tan@, First note the power factor & KW without connecting capacitor. The noted power factor is in cos@.Convert the cos@ value in tan@. for ex. If power factor is 0.6, KW = 200 cos@ = 0.6 cos-1 (0.6) = 53.1 tan (53.1) = 1.333 200*1.333 = 266.6 KVAR if you use 266 KVAR capacitor, Then the power factor improves to unity (1.000). |}
The same way, as you convert Appels to Carrots ........... There is a formula: KVAr = KVA / KW or cos=KW/KVA > Yes, we are treating KW, KVA, & KVAr as the 3 sides in a 90 deg TRIANGLE ! KW= vertical katede KVAr = horizontal katede KVA = hypotenuse
kV is kilovolts, kW is kilowatts, kVA is kilovolt amps and kVAR is kilovolt-amps reactive. A common formula is kVA-squared = kW-squared + kVAR-squared.
kvar can be calculated as follows the a product KVA andt the sine of the angle between the KVA and KW.
kvar = kva*sin@
kvar = kva*sin@
Depending upon the connected load ( R, RL, RC or RLC) with a transformer, the power goes ou from a transformer may be of two types: 1. Active Power; measured in kW 2. Reactive Power; measured in kVAR If the rating will be in kW, then kVAR rating would not be accounted but if the rating is in kVA then it is possible for us to calculate the total active and reactive current as well as the powers, at a particular system voltage!
For normal power factors (pf=80%), you have 0.8 kW for every kva. In general however, kW = pf x kVA. Where pf is the power factor, it is the cosine of the angular difference between the voltage and the current of a circuit in alternating current circuits.
Rephrase your question so that it makes sense.