480V.
You should not need a wiring diagram. If the generator has a star point (wye) connection then the phase voltage to ground (star point) is 277 volts. 480/1.73 = 277.
% rate = 150/480 * 100% = 31.25%
The GCF is 30.
The Least Common Multiple (LCM) for 150 480 is 2,400.
When people talk about 480V systems, they mean 480 is the RMS voltage.
The Least Common Multiple of 150 and 480 is 2,400.
The Greatest Common Divisor of 150, 480 is 30.
Crank the generator excitation up to 480 or down to 460. For calculations I used 480 volts. A 60kW generator at 480 volts will put out, kW x 1000/1.73 x E x (pf(.9)) = 80 amps. It looks like the machine that is to be run off the generator is a dual voltage machine. Not knowing the HP of the machine wire it to the 460 volt connection. The inrush current might be a problem if the HP is high.
Well, if 80kW is your PEAK value, then you need an 80kw generator. If 80kW is your nominal current, you need to figure out what your peak current is. This will depend on the type of load. Is mostly motor loads? If so, your peak current may be significantly more than nominal, depending on the starting sequences of the motors. Clear as mud?
30
It depends upon the Generator system voltage. For 3 Phase, 600 Volt system, it will be 73 Amps For 3 Phase, 480 Volt system, it will be 90 Amps For 3 Phase, 208 Volt system, it will be 208 Amps
No. A 277 volt ballast needs the correct voltage to operate. The 277 voltage is derived from the star point voltage of a 480 volt three phase system (277/480). The 208 voltage is a three phase line voltage whose star-point voltage is 120 volts (120/208).