Yes - a 3 phase load (in a balanced network) that consumes 270A would have a flow of 90A down each phase
Single-phase, 2.5 amps; three-phase 1.443 amps.
It means 225 amps on each phase.
This depends on what voltage the range is rated for and if it is single phase or three phase. At 220 volts single phase it is about 60 amps, 240 v single phase , 53 amps and at 480 v three phase about 15 amps.
180 amps. Assuming the panel will be loaded only 80%.
For a single phase 3 HP motor at 208 volts the amperage is 18.7 amps. For a three phase 3 HP motor at 208 volts the amperage is 10.5 amps. This figure is derived at by taking the full load amps at 230 volts and adding 10%. As the voltage goes down the amperage goes up. For 200 volt motors 15% is added to the FLA of a 230 volt motor.
Single-phase, 2.5 amps; three-phase 1.443 amps.
It means 225 amps on each phase.
50 Amps Single Phase 20 Amps Three Phase
This depends on what voltage the range is rated for and if it is single phase or three phase. At 220 volts single phase it is about 60 amps, 240 v single phase , 53 amps and at 480 v three phase about 15 amps.
180 amps. Assuming the panel will be loaded only 80%.
This 480-v three-phase transformer probably has a 208-v three-phase secondary which has 120 v from each line to neutral. In that case the primary current is 0.433 times as much as the secondary current, so 100 amps in the secondary means 43.3 amps in the primary.
To answer this question a voltage needs to be stated and whether the load is three phase or single phase. Without the voltage the amperage can not be calculated. For single phase, Amps = kva x 1000/voltage, for three phase, Amps = kva x 1000/1.73 x voltage.
If all three legs of the system are balanced then zero amps will flow all the way up to 100 amps if only one leg of the three phase system is used. The neutral in a wye three phase system carries only the unbalanced current. This is why in services for a three phase four wire system you are allowed to reduce the size of the neutral conductor.
135 A at 120 v single-phase is 16.2 kVA. With a 208 v three-phase supply you get three single-phase 120 v supplies, so the same kVA is produced with a balanced load of 45 amps on each phase.
21.739 a 21.739 a
A voltage of 240 volts is not a common three phase voltage. Single phase kva of 240 voltas and 50 amps is I x E/1000 = 240 x 50 = 12000/1000 = 12 kVa -- Assuming the 240 volts is phase to phase voltage, and this is a three phase application: KVA = V*I*sqrt (3) = 20.78KVA
For a single phase 3 HP motor at 208 volts the amperage is 18.7 amps. For a three phase 3 HP motor at 208 volts the amperage is 10.5 amps. This figure is derived at by taking the full load amps at 230 volts and adding 10%. As the voltage goes down the amperage goes up. For 200 volt motors 15% is added to the FLA of a 230 volt motor.