For parallel operation of let's say two Transformers, following limiting conditions must be met.
1- The turn ratios must be same.
2- The percentage impedance must match.
3- The X/R ratios must be same.
The load sharing is done according to the kVA ratings and %Z of the transformers. The formula is as under:
load taken by TF1 = ((kVA1/%Z1)/((kVA1/%Z1)+(kVA2/%Z2)))*total load
Similarly,
load taken by TF2 = ((kVA2/%Z2)/((kVA1/%Z1)+(kVA2/%Z2)))*total load
An example will make the concept easier.
For example we have to parallel a 1000kVA TF of 5%Z with another of 1200kVA having 5.5%Z to supplay a load of 800kVA.
load taken by TF1= ((1000/5)/((1000/5)+(1200/5.5)))*800= 382.6kVA
load taken by TF2= ((1200/5.5)/((1000/5)+(1200/5.5)))*800= 417.4kVA
Transformers are sized by the secondary connected load. If the wattage of the load is not given, use the following equation to find it. Watts = Amps x Volts.
The object that uses electricity in a circuit to make something happen is known as the load. Usually the load is rated in watts.
Fully loaded - 2.62 amps at 11kV. The no load depends on the transformer design, but it will usually be significantly less than the full load amps (not sure on this size, but on larger transformers it is typically ~.05 - .1% full load, so you'd be looking at ~2.5 mA RMS). The connection type is not important. Transformers are very efficient, thus there is not a whole lot of loss in the "average" transformer. The actual loss will depend on the design criteria of the transformer.
If the load is not grounded and has no connection to neutral then nothing should happen. This begs the question of why you would do such a thing. If you touch any metal part on the load you will likely get a shock.
It depends what herb and you'll probably just end up with a load of water with floating herbs
advantages for automatic load sharing of transformer with protective analysis
Transformers Autobots happened in 2007.
Transformers Decepticons happened in 2007.
it would be the end of transformers
Transformers Comic UK happened in 2007-07.
Paralleling transformers will increase the effective capacity available to the load. There are important requirements before transformers can be paralleled, so it's simply not the case of connecting any two transformers in parallel.
All transformers have a power rating given in kVA which determine the maximum load that can be connected to that transformer.
i think it is high value resistance as it is used in Transformers to get the output voltage.
Transformers are designed to run at specific voltage levels, and they are designed to handle a maximum load (known as "full load"); this load is usually based on the amount of current that can be pushed through the transformer without overheating, so if 1/2 voltage is applied, full load would be 1/2 of normal. Some "complicated" transformers may have other limitations (dual voltage transformers may have two different full loads specified, and they may not be directly proportional relative to voltage).
The transmission of electrical energy requires very high voltages (for a given load, the higher the supply voltage, the lower the load current). To increase/reduce these voltages, you need transformers. Transformers are AC machines; they do not work with DC.
Invade-a-Load happened in 1987.
No load current depends on the design of the transformer, and what voltage it is energized at. It will typically be below 1% of full load, and can be significantly below 1% for utility sized transformers.