Q: How many current carrying conductors can you have in a conduit before you have to start derating amparage?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

The calculation used to determine amperage of a conductor based on the total number of conductors in a conduit is called A derating B voltage drop C conduit fill D conductor fill?

derating


How many current carrying conductors are allowed in a raceway before derating?

You can put three ccc's in a conduit (any size conduit) before you derate. Keep in mind that for single phase loads (lighting, receptacles) the neutral is also counted as a current carrying conductor. This derating factor does not apply to nipples 24 inches long or less. See NEC Table 310.15(B)(2)(a) for full details on derating regarding ccc's.


Can you use existing PVC conduit run from basement to 8th floor for 120v circuits for chillers?

The simple answer to your question is yes. But there are limits to how many wires can be in any conduit, and the current carrying capacity of the conductors can be affected by distance, ambient temperature, and how many conductors are contained in the same conduit. Other things to consider are, Can you physically fit the wires in there? Would it be easier to run a new conduit? Do you have the manpower necessary to get the work done?


Does the Nec allow grounding electrode conductor to be run in conduit that has other conductors in the conduit and what code section?

No, the bare copper grounding conductor can not be in a conduit with other conductors. It can be in conduit by itself to provide mechanical protection for the wire.


What is the definition of electrical capacity?

The amount of conductors per conduit size example code says 3 number 4 conductors in a 1'' conduit


What size conduit for four 4 cables?

Conduit sizing is based on the number of conductors that are drawn into it. Without the number of 1000 MCM conductors, an answer an not be given.


Can branch circuits from a panel be pulled in the same conduit if not exeeding the conduit fill requirements?

Yes. The thing that has to be closely watched is the load on the conductors. The conductors will have to be de-rated as the code only gives amperage rating for three conductors in a raceway. So watch the connected amperage to each load and fill the conduit accordingly. This supersedes the conduit fill requirements rule.


What is a conduit?

A conduit is a set of closed canalization circular or not that assures the free passage of conductors and ensures their continuous protection.


Can a three phase circuit be installed in the same conduit or in different conduits?

The conductors of any three phase circuit must be run in the same conduit. If the circuit requires a neutral, it must also run with the conductors in the same conduit. (If they were to be run in more than one conduit or raceway, the circuit would not operate properly.)


How many 12 thhn conductors are allowed in half inch conduit?

9


When do you derate wires in conduit I know the code says more than 3 current carrying conductors but is there a length of conduit run when you should start to derate?

There are two things here to keep in mind. If you are trying to add more conductors to an existing conduit run use the cross sectional area of the conduit to see if more wires can be fitted. The second thing that's relates to length is the voltage drop at the load. To size the conduit work backwards from the load amperage to size the wires. If a long distance is involved a voltage drop calculation will be needed. Then select the conduit size to accommodate the wires recommended for that load amperage. The length of conduit run is not brought into the equation on de rating wire size it is always about keeping the voltage up at the load end of the run by increasing the wire size and selecting the proper conduit size for that wire.


Can multiple feeders be in same conduit?

Yes they can. If the feeders are of different sizes, then a conduit fill calculation must be made to ascertain that the conduit does not become overfilled. Cross sectional areas of the conductors are found and it is then determined what the conduit cross sectional fill will allow.