Yes a GFCI will work if the neutrals and ground are to together the main panel. This is considered the line side of feed side of the GFCI. Neutral and ground can not touch down stream from the GFCI or on the load side of the GFCI.
you can only put one wire under one lug for neutrals (grounded conductor). grounds (grounding conductor) can be doubled up as long as they are the same gauge under one lug
If the load is perfectly planned AND purely resistive the neutral current would be zero in a 3-phase 4 wire circuit. But that is extremely rare. Before nonlinear loads (fluorescent lighting, computers, dimmers, variable speed drives etc) 1/2 size neutrals were often used but now full size neutrals are used to cope with the increasing levels of 3rd harmonics resulting from modern equipment, which can lead to neutral currents approaching or even exceeding the phase current. With very high levels or harmonics, double size neutrals are being used in places