If the load requires a single circuit breaker, as most three phase loads do, you need a separate neutral for each. This allows you to check the balance between each phase and the other phases as well as neutral, in order to detect a ground fault.
It depends on the purpose of the three phase circuits - if this were CT cables, then yes, unless you intentionally over sized the ground wire. Otherwise this would cause unusually high voltage rise in the secondary of the CT during ground faults, which could lead to saturation (unless CT ratio is intentionally set high). As noted above, having separate neutrals helps to determine balance, although you can measure 3I0 from the phase currents for a similar relationship without actually looking at the neutral at all (some relays doe this for ground protection instead of directly measuring neutral current, see SEL's 351 for an example relay). No matter what, this would be highly irregular, and I wouldn't recommend scrimping on a neutral. In my experience, the more you move away from accepted practices (not to dampen ingenuity...), the more trouble you create for the future.
If the loads were strictly three phase then there would not be any neutral needed. If from a three phase distribution panel the loads were three single phase loads then you can use one neutral for the three phase wires. This is a code rule that has to be adhered to. A same N, B same N, C same N and only in this combination. Conduit fill 4 wires, two three phase four wire circuits, conduit fill 8 wires.
You can divide a three phase service into (3) single phase circuits providing you have a 4th neutral wire.
A delta-connected system is described as being a three-phase, three-wire, system, and doesn't have a neutral. But a balanced star (wye) connected load (e.g. a three-phase induction motor) doesn't actually require a neutral.
A 400/230-V three-phase generator hase three line terminals, together with a neutral terminal. The line voltage (i.e. the voltage between any pair of line terminals) is 400 V, while the phase voltage (i.e. the voltage between any line terminal and the neutral terminal) is 230 V.
As far as I understand, you don't need neutral line for connecting appliances that is 3-phase compilant. You only need the neutral line to connect a single phase appliance, which you connect along with one of the three lines.
Neutral current is the vector sum of the phase currents. You should be able to add up the phase currents from their polar quantities.
A three phase system will have 3 phase branch circuits and no neutral.
For a three phase distribution system there is one neutral. In North America the electrical code allows three individual branch circuits to connect with one neutral as long as the three circuits each use an individual phase leg. This differs from 120/240 volt single phase wiring where only two legs can be used with one neutral.
The conductors of any three phase circuit must be run in the same conduit. If the circuit requires a neutral, it must also run with the conductors in the same conduit. (If they were to be run in more than one conduit or raceway, the circuit would not operate properly.)
You can divide a three phase service into (3) single phase circuits providing you have a 4th neutral wire.
Yes, this is done on star (wye) systems where one neutral is used for three phase wires. e.g. 120/208 voltage system.
Yes, there is a difference between single phase and three phase circuits.
The neutral provides a path back to the source for the electricity. In a three-phase circuit, it is mainly used to carry the unbalanced load back to the source. In theory, a perfectly-balanced three-phase circuit would not need a neutral, but this is almost impossible to achieve in actual practice.
The current carried by the neutral of a three phase four wire system is the un balanced current. If the three phase system was completely balanced on all three phases there would be no need for a neutral, eg a three phase motor. This neutral current will be less that the phase current so a reduction in the neutral size is allowed.
In the US, the National Electrical Code (NEC) will allow you to install single phase and three phase systems in the same conduit.
A delta-connected system is described as being a three-phase, three-wire, system, and doesn't have a neutral. But a balanced star (wye) connected load (e.g. a three-phase induction motor) doesn't actually require a neutral.
a traditional rcd wont work as it uses the difference between the incoming active and neutral to detect current loss it has to read 0. In particular, an RCD alone will not detect overload conditions, phase to neutral short circuits or phase to short circuits. Over-current protection must be provided.
yes we can use as a single phase circuit because at practise directly the 3-phase circuit is made by combining the three single phase circuits