Yes, it is referred to as three phase four wire service.
You should never switch the neutral wire. The neutral of the appliance should be connected directly to the neutral wire leading to the service panel neutral bar.
Ground wire can be appropriately bonded to the neutral and cabinet at the service box by connecting the neutral and ground wires from the feeder wires to the neutral bus bar and the ground terminal located on the same cabinet at the service box. White wire (neutral) must be connected to bus bar and bare wire must be connected to ground terminal in the same cabinet.
On a 200 amp or any size service the ground wire is easily identified. Look in the distribution panel for the neutral bus bar. This is where the service neutral (white wire) is connected to the distribution panel. There you will see a bare copper wire connected to the same neutral bar. This is the ground wire that is connected to the ground rods out side of the house.
If single phase - 2 wire service > two wires If single phase - 3 wire service > three wires If three phase - 3 wire service > three wires If three phase - 4 wire service > four wires US residential service is usually single phase 3 wire service: Two hots and neutral.
Neutral is neither Hot nor ground. Neutral is the return wire for electrical service. It is a requirement , by law, that the Neutral Wire Feed into an electrical service box (main panel) be BONDED to the box and the Earth ground. Thie effectively makes the neutral in circuits out of the service panel equal to ground. But as it enters the service panel from the utility and meter pan, it is not ground. <<>> The only time that the neutral can have voltage on it is if it gets disconnected from the distribution point. Then the voltage that is supplied to the load will continue through the load and stop at the disconnection point. If you touch the uninsulated part of the neutral wire and touch any grounded equipment at the same time your body will act as a conductor for the load circuit. You will receive a nasty shock. This scenario is the only time that the neutral is "hot".
You should never switch the neutral wire. The neutral of the appliance should be connected directly to the neutral wire leading to the service panel neutral bar.
Ground wire can be appropriately bonded to the neutral and cabinet at the service box by connecting the neutral and ground wires from the feeder wires to the neutral bus bar and the ground terminal located on the same cabinet at the service box. White wire (neutral) must be connected to bus bar and bare wire must be connected to ground terminal in the same cabinet.
On a 200 amp or any size service the ground wire is easily identified. Look in the distribution panel for the neutral bus bar. This is where the service neutral (white wire) is connected to the distribution panel. There you will see a bare copper wire connected to the same neutral bar. This is the ground wire that is connected to the ground rods out side of the house.
If single phase - 2 wire service > two wires If single phase - 3 wire service > three wires If three phase - 3 wire service > three wires If three phase - 4 wire service > four wires US residential service is usually single phase 3 wire service: Two hots and neutral.
Because the white wire on a 120 volt circuit is the neutral wire that is connected to the silver screw on outlets and switches. It is connected to the neutral bar in the service panel.
Neutral is neither Hot nor ground. Neutral is the return wire for electrical service. It is a requirement , by law, that the Neutral Wire Feed into an electrical service box (main panel) be BONDED to the box and the Earth ground. Thie effectively makes the neutral in circuits out of the service panel equal to ground. But as it enters the service panel from the utility and meter pan, it is not ground. <<>> The only time that the neutral can have voltage on it is if it gets disconnected from the distribution point. Then the voltage that is supplied to the load will continue through the load and stop at the disconnection point. If you touch the uninsulated part of the neutral wire and touch any grounded equipment at the same time your body will act as a conductor for the load circuit. You will receive a nasty shock. This scenario is the only time that the neutral is "hot".
In the US, house wire has the BLACK wire connected to the HOT phase of the service input. The WHITE wire is connected to the NEUTRAL of the service input. Normally, both BLACK and WHITE wires are each connected to the 2 LOAD terminals. It is also normal that the WHITE service wire is connected to the wider spade outlet receptacle. The BLACK wire would then be connected to the shorter or narrower outlet spade receptacle. In wired screw lamp circuits, it is normal to wire the BLACK service wire to the center pad of the lamp socket and the WHITE wire to the screw shell of the socket. In switch circuits, it is normal to wire the BLACK service wire to the switch. The HOT service circuit is then opened or closed by the switch. Measuring voltage on your neutral means there is a break in neutral. If the neutral is broken you will measure voltage across the break or from the break to ground. Under this scenario you will measure the same voltage as you do on your hot wire and your load should not be working. Measuring voltage on your neutral less than on your hot wire may mean you have a problem where your neutral is supposed to be bonded to ground in your main service panel. In this scenario your load may be working but you need to check the bonding connection.
Not only in BC but in all of North America, the colour for a neutral wire is white.
You need to look at the regulations that apply in your country. If in doubt, use a neutral wire of the same size as the live wire or wires.
AWG # 3/0 copper.
no
a loose connection of a neutral wire