Probably...
What ratio? X/R? X0/X1? X0/R0? Xd /Xd''? etc.
Lt cables has own impedance which reduce the short circuit fault level
...of what? to a house, to a breaker (to lower fault current level?), to an amplifier circuit?
The maximum current that flows when there is a short circuit in the substation.CommentThis is not strictly-speaking true, as fault levels are expressed in MV.A, not in amperes, but it does allow the value of likely fault currents to be calculated.
You don't calculate the rated kV.A of a circuit breaker; it's determined by the manufacturer. It's important that a circuit breaker's rated kV.A exceeds the fault level kV.A at the point where the circuit breaker is located, otherwise it may fail to interrupt a fault current and, possibly, self destruct.
Electrons in a covalent bond come from the highest occupied energy level.
Trouble code P0463 means: Fuel Level Sensor A Circuit High Input
Of course it depends entirely on the ohm's resistance of the resistor. The higher the resistance, the lower the comparison to a short circuit.
Short circuit voltage is the voltage that has to be applied to the primaries of a transformer, so that the nominal current flows through the secondaries, when they are shorted. This value is important, if transformer secondaries shall be used in parallel. Ideally all transformers with parallel secondaries should have the same short circuit voltage. When their short circuit voltages are different, the transformer with the lower short circuit voltage will be loaded more than their relationship of power ratings would predict. The short circuit voltage is also important in the design of a transformer, because it predicts, how much the secondary voltage will drop at nominal output current. This knowledge helps the designer to find out, how many further windings the secondary needs for a certain voltage in relation to an ideal transformer. Short circuit voltage is also known as impedance voltage.
EQUIPMENT OUTPUT DERATION: Particular example is the Generator Set installed at 1000 meters above sea level the power output is derated due to pressure.
Unit of fault level is KA. Kilo amps
There isn't enough information here. Available short circuit fault level can be given as a KVA value for different types of faults, but I assume the questioner is looking for a relationshiop between (transformer?) KVA and available short circuit current - If my assumption is correct, there is no direct correlation without knowing the transformer positive and zero sequence impedances. If these are known, you can assume the source impedance is infinite, and calculate the maximum short circuit current through the transformer as follows: lowside fault current for a 3 phase fault on the lowside of the transformer: lowside kV (line to line) / (1.732 x per unit positive sequence impedance x scalar to real impedance), where scalar to real impedance is equivalent to lowside kV (line to line) ^2 / base kVA. For a L-G fault, do the same with zero sequence impedance.
Sure you could get one of these*P0460 Fuel Level Sensor Circuit Malfunction*P0461 Fuel Level Sensor Circuit Range/Performance*P0462 Fuel Level Sensor Circuit Low Input*P0463 Fuel Level Sensor Circuit High Input*P0464 Fuel Level Sensor Circuit Intermittent