LRA (locked rotor amps) is not used to calculate the breaker size. Breaker's are used to protect the size of the conductor that is connected to it. Motor calculations are based on the motor's FLA (full load amps).Conductor size is 125% of the motor's FLA.

Breaker size is 250% of the motor's FLA.

This is the only occasion when the breaker is sized larger that the conductors maximum amperage rating. This is due to the motor drawing up to 300 to 600% of its FLA when starting.

If you state the motor's wattage, voltage or amperage this calculation can be calculated here.



User Avatar

Wiki User

9y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: LRA is 134 AMPS. what size breaker should be used?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

What size circut breaker for 10-2 wire?

A #10 wire has the capacity for 30 amps. No breaker larger than 30 amps should be used to protect the circuit.


What size amp circuit breaker should be used for a geyser?

Depends on how many amps it pulls and the size of the wire in the circuit.


What size breaker should be used for a dryer in Canada?

Minimally 30 AMPS


What size breaker should be used for a 3.6 kW oven?

3000 / 240 = Amps. You de-rate a breaker by 20 % for continuous load like an oven. You could get by with a 20 Amp breaker and 12 AWG wire. However, I would recommend 30 Amps and 10 AWG for an oven for the long run.


Should 25 amps breaker be replaced by 20 amps?

For typical residential house wiring 12 AWG wire is required for a 20 Amp breaker. If you change out the breaker for a 25 A breaker you would have to rewire the circuit with 10 AWG. In that case you could up the breaker to 30 Amps. All outlets and switches should be rated at the same voltage and current as the breaker.


What are the standard size circuit breaker amperages?

In North America the standard sizes for breakers are 15, 20, 30, and 40 amps. The 15 amp size breaker is used in general circuit wiring. The 20 amp size breaker is used for dedicated appliance receptacles, hot water tank and baseboard heating. The 30 amp size breaker is used for a clothes dryer. The 40 amp size breaker is used for the electric range.


What size breaker is used with 10 wire?

Don't go over 30 Amps with a 10 Ga wire.


What size amp circuit breaker should be used for a gas dryer?

Typical residential electric dryers are on 30 amp circuits, which means 10 gage copper wire. The circuit breaker should match the dryer cord rating, generally 30 amps.


If an electrician have a circuit that pulls a load of 10 amps what size breaker must that circuit be protected by?

If you are talking about a breaker in a house panel then a 15 amp breaker would be used. It is the smallest amperage breaker that you will find in a house panel.


What size breaker should be used for a TNIA-10 wire?

running wire 12-2 300ft w/9ea. 27watt lights what size breaker should be used


How do you calculate amp of circuit breaker to use on a 4800w oven?

Ovens typically run at 240 volts which will be a two pole breaker in your panel. Watts = volts x amps. 4800 / 240 = 20 amps. If by chance you are using 120 volts then double it to 40 amps. All wiring must conform to size of breaker used.


What size amp circuit breaker should be used for a 20 gallon 1500 watts water heater?

To answer this question the voltage that is to be used should be stated. If the tank is 240 volts then 1500/240 = 6.25 amps. A 2 pole 15 amp breaker with a #14 wire will work fine. If the working voltage is 120 volts then 1500/120 =12.5 amps. A single pole 20 amp breaker with a #12 conductor will work fine. The reason for the up size in wire for the 120 volt system is that conductors are only allowed to be loaded to 80% capacity. A #14 wire is rated at 15 amps x 80% = 12 amps which is just under the required amperage of the 1500 watt heater. A #12 wire is rated at 20 amps x 80% = 16 amps. The code book states that if the current of the load is over the capacity of the wire rating the next size conductor is to be used.