Certainly,
100Watt of power requires only about 1 A at 115V
However, if you made a typo and intended to say two 1000 Watt heaters Then I would use a 25A. The 20A breaker would be ok, but will be on the cusp of tripping as the current would be closer to 18A. The typical 14AWG wiring in a house can carry up to 32Amps safely as a result the maximum circuit breaker to use would be 25Amps
<<>>
In the above answer it is stated that a #14 wire will carry up to 32 amps. This is completely false. A #14 wire is only rated at 15 amps. To carry 32 amps safely you would need to use a #8 wire which is three wire sizes larger that a # 14.
If you have contineous tripping on a breaker then there is a fault on the load of that breaker. Don't reset it any more. What is the breaker connected to?
If a 100 amp breaker keeps tripping there is an overload on the system.
A shunt trip breaker is installed like any other molded case breaker. The only difference is that it has an internal tripping coil that is usually connected to a C.T. The breaker is usually mounted in a MCC cabinet The top of the breaker is bolted to the MCC bus bars and the bottom of the breaker is connected to the load. The load conductors pass through the C.T.'s.
You need to remove everything connected to the breaker and see if it still trips. If it does it is in the wiring or possibly a bad breaker. Disconnect load from breaker and see if it still trips. If so replace the breaker. If it still trips and is not the breaker then you will have to start pulling each outlet from wall and checking after disconnecting each outlet.
A circuit breaker is designed so that it will trip when the electric current is too high. That is the purpose of a circuit breaker. If there is a metal piece on the circuit breaker that prevents it from tripping, it is useless. Perhaps someone has altered it.
Could be but you could also have a weak breaker that will no longer hold the load of your dryer. That is if your talking about your dryer breaker tripping. If your "main breaker" is tripping you have a different problem. Call an electrician in that case. A plugged up dryer shouldn't be tripping your main
A shunt trip breaker is installed like any other molded case breaker. The only difference is that it has an internal tripping coil that is usually connected to a C.T. The breaker is usually mounted in a MCC cabinet The top of the breaker is bolted to the MCC bus bars and the bottom of the breaker is connected to the load. The load conductors pass through the C.T.'s which induces a current into the circuit to trip the tripping coil in the breaker.
A circuit breaker will trip if it is faulty or if the connected circuit has a short circuit or a connected device is trying to draw more current than the breaker rating. If you disconnect the output wire from the breaker and it still trips, it is a faulty breaker. If the breaker is tripping immediately when it is turned on then start disconnecting elements of the circuit to see what might be causing the problem. If everything was working and now isn't, it is likely that the wire from the breaker is nicked where it exits the box and is shorting to the feedthru connector.
In an electrical context, 'tripping off' means the circuit breaker breaking the circuit because of a fault.
The electromagnet in the circuit breaker is used for instantaneous tripping if short-circuit condition arises. At defined current level the electromagnet develops the force high enough to cause the tripping of the mechanism.
it is connected in a box
The ambient temperature does have an effect on the tripping point of a breaker. If a breaker is operating at near capacity the additional ambient temperature will lower the breaker trip set point.