answersLogoWhite

0


Best Answer

From the 2011 NEC, Section 250.130 states, in part, "For replacement of non-grounding-type receptacles with grounding-type receptacles...connections shall be permitted as indicated in 250.130(C)."

Section 250.130 (C) states in its entirety,

"(C) Nongrounding Receptacle Replacement or Branch

Circuit Extensions. The equipment grounding conductor

of a grounding-type receptacle or a branch-circuit extension

shall be permitted to be connected to any of the following:

(1) Any accessible point on the grounding electrode system

as described in 250.50

(2) Any accessible point on the grounding electrode conductor

(3) The equipment grounding terminal bar within the enclosure

where the branch circuit for the receptacle or

branch circuit originates

(4) For grounded systems, the grounded service conductor

within the service equipment enclosure"

(5) For ungrounded systems, the grounding terminal bar

within the service equipment enclosure"

Now for some of my thoughts. It sounds like what you got was adequate. It was correct except for he should have used green or bare conductor, not white, unless he used green tape near the end of the conductor to designate it as green. This tape would be inside the box but I would have marked it outside the box also if it is visible.

I would have run this conductor as close as possible and preferably attached to the existing circuit conductors.

Looping the conductor as you have stated is not the best installation, in my view, but if you have at least 6 inches from the entry of the conductor to the grounding terminal and another 6 inches before it leaves the box, this is ok. The code does not require this 6 inches if the conductor isn't spliced but in your application it should be since, in my view, it should have been spliced.

Solid or stranded is of no significance.

While I have quoted the 2011 NEC in my answer, I do not expect this has changed any in recent years.

The use of the word "bonding" by your electrician was technically incorrect but "bonding" and "grounding" are sometimes used synonymously. They are different but often look alike to the untrained eye. Even electricians often misuse these terms and fail to understand the difference. It takes someone like myself who is a little anal retentive to use the terms properly.

I hope you will acknowledge my answer as I am particularly interested to know if you got it.

User Avatar

Wiki User

12y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What does the National Electrical Code NEC say about running separate ground wires?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Related questions

How far from the ground do you have to be when you are running electrical wire in the walls of an unfinished basement?

There is no minimum. It only has to be protected from damage.


Can you ground a wall outlet by running a jumper wire from the neutral terminal to the ground screw?

Not correctly , It will show on a tester that it is grounded but you should run a separate ground for it to be properly grounded


How can lighting be a barrier for communication?

Yes, the electrical current running through the ground is enough to dirupt a radio signal.


What voltage is on running lights on Jeep Liberty?

The electrical system is 12 volt negative ground. Really about 13.6 volts while the engine is running, though.


Do you need to ground ceiling fans?

Answer for USA, Canada and countries running a 60 Hertz supply service.The electrical code states that all electrical equipment must be grounded.


Is a ground fault required in a basement?

Yes, If it is unfinished. Reference National Electrical code NFPA 70 for additional details.


What is the color of the ground terminal in any electrical equipment?

Green is the usual colour that represents ground in electrical equipment.


Can groundwire be together with neutral wire at the dyer?

Ground and neutral should only be connected at the main electric panel to prevent parallel neutral currents. If it is a new installation, you must provide four wires (two hots, 1 neutral, & 1 ground) and connect to the four separate (appropriate) places on the dryer. If it is an existing installation and it only has three wires (two hots and a neutral) connect the neutral to both the neutral and ground connection of the dryer (the National Electrical Code allows this exception for older homes). Call a qualified electrician to do any electrical work.


When an isolated ground is required does this mean a separate ground uninterupted from the main service panel or can you take separate grounds to the outlets that require isolated grounds from a sub p?

Answer for USA, Canada and countries running a 60 Hertz supply service.An isolated ground return to the panel means that the wire used for the isolated ground must have insulation on it. This is so that the isolated ground does not touch any adjacent metallic parts of the electrical system until it is placed on the ground block in the distribution panel. On isolated ground receptacles this is accomplished by using a three wire feeder. Black and white wires used as normal receptacle connections. The red wire with a green identifier tape installed to the isolated ground terminal of the receptacle and the bare ground wire to the green frame screw of the isolated ground receptacle.


What year was the last Ford with running boards?

The last Ford passenger car with running boards was 1948. The 1949 Fords had a new "narrower" look without the separate low fenders. The ground clearance was not changed much.


In a typical electrical panel installation the main ground wire is connected directly from a ground rod driven into the ground to the?

The ground wire should come from the ground rod and to the main electrical panel grounding terminal.


Can plastic work as an electrical ground?

Electrical grounds are composed of copper.