You get a short circuit.
In a wye system the voltage between any two wires will always give the same amount of voltage on a three phase system. However, the voltage between any one of the phase conductors (X1, X2, X3) and the neutral (X0) will be less than the power conductors. For example, if the voltage between the power conductors of any two phases of a three wire system is 220v, then the voltage from any phase conductor to ground will be 110v. This is due to the square root of three phase power. In a wye system, the voltage between any two power conductors will always be 1.732 (which is the square root of 3) times the voltage between the neutral and any one of the power phase conductors. The phase-to-ground voltage can be found by dividing the phase-to-phase voltage by 1.732 answer from ground and any phase
There is only one ground wire needed on any motor, single or three phase.
There probably isn't really any "ground" on Saturn; most likely it goes directly from the gas phase to a liquid-like critical phase as you get deeper. If there is a solid core, it's probably small and very far down.
After the rainstorm, the water in the puddle will be heated by the sun. As the water at the top of the puddle heats up, it will be converted to the gaseous phase and enter the air as water vapor. Any contaminants that are present in the puddle will be left behind on the ground.
During the G2 phase of the cell cycle, the cell continues to grow and prepare for DNA replication. It is a checkpoint phase where the cell checks for any damage or errors before moving on to the next phase of the cycle. If conditions are favorable and the cell is healthy, it will proceed to the S phase for DNA replication.
There are two types of connections in three phase systems. One is a delta connection where there is no connection to ground, so you should not get any voltage to ground. This is classed as a three phase three wire system. In this type of system any one of the phase wires could become grounded and no one be the wiser. Code requires that grounding lights be added to a delta system to visually show what the phase condition is in relationship to ground. The other type of system is a wye or star point connection. This is classed as a three phase four wire system. In this type of connection the coil ends are all joined together and grounded. You would have voltage between the phases and a lower voltage to ground. The voltage to ground would be the phase voltage divided by 1.73.Yes. If there is no voltage between a hot and a ground, either the hot isn't really a hot or the ground isn't really a ground.AnswerThere is always a potential difference between a line conductor and ground, regardless of whether it is a three-wire system or a four-wire system. This is due to the capacitance between line and ground.
Neutral will be closest to protective earth ground. In the US, neutral is white. we can check using tester ,when tester is connected to phase only lamp of the tester glows and when it is connected to the nuetral the lamp does not glow. another method is, connect the voltmeter to any one of the terminal and ground if the voltmeter shows 110v 0r 220v then it is phase and the other is nuetral.
From one phase to the next you should see 208 Volts.From any phase to ground you should see 121 Volts.AnswerYou are very unlikely to come across a two-phase machine, as two-phase a.c. systems are archaic. A two-phase system has two phase voltages that are 90 degrees out of phase with each other, and was used many years' ago. These days, you have either single phase or three phase. So it's probably safe to say that there are no two-phase motors about, these days!
Voltage is checked with a volt meter. It doesn't have to be 3 phase. It is used to test any potentials across phase to phase, line to neutral, line to ground or across resistances. Be careful when testing live voltages as a misplace of the meter probes could cause an arc flash that could give you three degree burns to any exposed skin.
To convert a three-phase three-wire system to single-phase, you should ground one of the phases using a grounding rod or electrode. However, please note that this method may not adhere to electrical codes and safety regulations. It is advised to consult with a qualified electrician before attempting any modifications to your electrical system.
You use a megger. This allows you to check what the condition of the insulation of the motor windings are. An ohms check on each phase should be an easy way if it reads OPEN then there's your bad phase. Otherwise there are diffrent types of 3 phase motors, could be the brushes, commutator, sliprings, many many things.
The Wye (also know as Star - especially in the motor rewind industry) is a 4-wire system which provides two different supply voltages. The center-point of the Wye is the system neutral and is usually solidly grounded. Where it is desirable to limit the phase-to-ground fault magnitude the center-point of the Wye may be connected to ground through and neutral grounding resistor or a current limiting reactor. Because the system is tied to ground it is easy to provide system ground fault protection. Three-phase loads can be connected phase-to-phase and singlephase loads can be connected from any phase to the system neutral. On a wye system, the phase unbalance currentis carried by the system neutral. On a Wye system the line current is equal to the phase current i.e. ( ILine 1 = IPhase A) and the line-to-line voltage is equal to the vector sum of two individual phase voltages i.e. (E Line1-2 = E PhaseA + E PhaseB' ). In a Wye system the phase-to-phase voltage is 1.732 x the phase-to-ground voltage. Some typical Wye system voltages are: 120/208Y, 277/480Y, 2400/4160Y, 4160/7200Y, 7200/12470Y, 7620/13200Y,and 19920/34500Y