An isolator (disconnector in US terminology) is a switch designed to isolate a section of line afterthat line has been de-energised using a circuit breaker, allowing maintenance work to be carried out on the de-energised section.
It's function is to provide a visual break between an energised line and a section of de-energised line and, therefore, is usually one of a pair (one at opposite ends of the de-energised section).
Isolators are generally not designed to break load currents (and definitly NOT fault currents!!), so the line must be de-energised using a circuit breaker before the isolator is opened, and the isolator must be closed before the circuit breaker is then used to reclose the line.
The higher-voltage line will have longer insulators and the line conductors will be further apart. And the symbol for kilovolt is 'kV', not 'kv'.
Multiples of 11 kV are used in many countries. The idea is to deliver a round number of volts so you add on 10% to allow for line losses. So 10 kV becomes 11 kV. In practice lines are operated without a 10% voltage drop now because it represents an unacceptable waste of energy, but we have stuck with 11 kV etc. Common supply voltages used for area distribution are 6.6 kV, 11 kV, 33 kV, 66 kV and 132 kV.
Star (or 'wye') connected alternators have a phase voltage of 6.35 kV, and a line voltage of 11 kV. Incidentally, it's 'kV', not 'KV'.
132kV substation is part of transmission and distribution of power in which the transmission voltage is 132kV. The substation is for stepping down or stepping up of the voltages to the required voltage. the substation also serves as a place where the transmission lines can be isolated, controlled and monitored. The substation consists of different equipment that is used to regulate, monitor and distribute the required power.Another AnswerIn the UK, 132 kV voltages are considered to be the lowest transmission voltages. Other transmission voltages are 275 kV and 400 kV. A '132-kV substation' is normally one in which this voltage is stepped down to a primary distribution voltage, usually 33 kV but, sometimes, 66 kV. As the previous answer points out, substations contain transformers, switchgear, busbars, and protection equipment.
KV is the abbreviation for kilovolts. The prefix kilo means thousands, so 220 kv means 220 kilovolts, or 220,000 volts.
It isn't. In the UK, transmission and distribution voltages are 400 kV, 275 kV, 132 kV, 66 kV, 33kV, and 11 kV.
A 132 kV substation is normally called a grid substation. It would normally use two or more 132/33 kV transformers rated at 90 MVA, or two or more 132/11 kV transformers rated at 30 MVA.
The safety distance from a 132 kv powerline is 1.4 metres
The standard voltage for transmission is about 115 to 1,200 kV (long-distance transmission). The extreme high voltages are measured more than 2,000 kV and it is exists between conductor and ground.Answer for UKThe standard transmission voltages in the UK are 400 kV and 275 kV. Primary distribution voltages are 132 kV and 33 kV, and secondary distribution voltages are 11 kV and 400 V. These are all line voltages -i.e. voltages measured between line conductors.
The higher-voltage line will have longer insulators and the line conductors will be further apart. And the symbol for kilovolt is 'kV', not 'kv'.
In the UK a line of pylons carrying the supergrid at 400 kilovolts can carry up to about 2000 Megawatts. Pylons also carry circuits working at lower voltages, 275 and 132 kV, 66 kV in some places, and on small pylons 33 kV.
Multiples of 11 kV are used in many countries. The idea is to deliver a round number of volts so you add on 10% to allow for line losses. So 10 kV becomes 11 kV. In practice lines are operated without a 10% voltage drop now because it represents an unacceptable waste of energy, but we have stuck with 11 kV etc. Common supply voltages used for area distribution are 6.6 kV, 11 kV, 33 kV, 66 kV and 132 kV.
If I'm interpreting the question accurately, a "line isolator" is an insulating standoff for transmission or distribution cable. A bus isolator is an insulating standoff for tubular or bar bus as is normally seen in a substation switching yard.
400KV transmission line surge impedence loading is depent upon the conductor type but its arount 600mw400KV transmission line surge impedence loading is depent upon the conductor type but its arount 600mw.Permissible Line Loading as per CEA Standards+/- 500 kV HVDC bi-pole line=Pole Capacity X Number of Pole in service765 KV line having 4 X 686 sq. mm conductor =2250 MW per circuit765 KV line having 4 X 686 sq. mm conductor operating at 400 kV =614 MW per circuit400 KV line having 2 X 520 sq. mm conductor with shunt reactor =410 MW per circuit400 KV line having 2 X 520 sq. mm conductor without shunt reactor =533 MWper circuit400 KV line having 2 X 520 sq. mm conductor operating at 220 kV =155 MW per circuit220 kV line =132 MW per circuit132 kV Line =50 MW per circuitsource:http://www.mahatransco.in/oa/draft_procedure_calculation_transmission_availability.shtm
Ground clearance132 kv - 6100 mm220 kv - 7015mm400 kv - 8840mm765 kv - 15000mm
It used to be a convention to add 10% to allow for transmission losses, so the voltages were always described as 11 kV, 33 kV, 66 kV and 132 kV. Later standards in the UK grid are 275 kV, which is a multiple of 11, and 400 kV which is not.
Star (or 'wye') connected alternators have a phase voltage of 6.35 kV, and a line voltage of 11 kV. Incidentally, it's 'kV', not 'KV'.