A balanced three phase system is where the currents into the loads placed on all three phases of the service are reasonably close to each other in amperage.
Another opinion
A 'balanced' three-phase system describes a three-phase load in which each phase current is identical in both magnitude and phase. If the phase currents are only 'reasonably close', then the load is not balanced.
In a three phase system, if the current in all three phases are same, then it is a balanced system.
A balanced three phase load is where the current flowing in all three phases of the load are reasonably close to each other.Another answerWhen the voltage and measured current draw do not deviate by more than 2 percent under load.AnswerA balanced three-phase load is one in which each of the three loads is identical in all respects (magnitude and phase). Further to the first answer, the three line currents must not all be 'reasonably close', they must be identical -i.e. the same value and phase relationship.
If the three legs of a three phase source are A, B, and C, then you can connect them in delta configuration as AB, BC, and CA to get the three phases.If the three legs are properly balanced, and you have a neutral/ground leg N, then you can connect them wye configuration as AN, BN, and CN to get the three phases.AnswerWith a three-phase, three-wire, system supplying a deltaconnection, the phase voltages are numerically equal to the line voltages.A three-wire system's load can also be connected in wye(star), in which case you will obtain the phase voltages between any one line and the neutral or star point of the load connection. In this case, providing the load is balanced (i.e. identical in all respects) the phase voltage will be 0.577 times the value of the line voltage.
three phase load is said to be balanced when the impedance and power factor of each load is equal.in this condition phasor sum of currents and phase voltages add up to zero.
yes.
In a three phase system, if the current in all three phases are same, then it is a balanced system.
In a properly balanced three phase system, there is negligible current on neutral. If there is substantial current on neutral, then the system is not balanced and/or something is wrong.
The current carried by the neutral of a three phase four wire system is the un balanced current. If the three phase system was completely balanced on all three phases there would be no need for a neutral, eg a three phase motor. This neutral current will be less that the phase current so a reduction in the neutral size is allowed.
Earthing point is where conductor is directly connected to ground and its potential is always zero. Neutral is a return path in single phase system and in three phase system Neutral point will have zero potential if all the loads are balanced in the system. In un balanced three phase system even neutral point will have some potential
A delta-connected system is described as being a three-phase, three-wire, system, and doesn't have a neutral. But a balanced star (wye) connected load (e.g. a three-phase induction motor) doesn't actually require a neutral.
Three-wire transmission is used on balanced three-phase systems when the current is known to be equal in all three phases, for example when supplying a three-phase motor. A fourth neutral wire is used when the system is liable to have unequal currents or when multiple single-phase supplies are connected to it.
Line, phase, neutral are terms used to describe the conductors in a three-phase system. The three live wires are called 'lines', and less correctly, 'phases'. Neutral is used for the fourth wire which in a balanced system carries no current.
If all three legs of the system are balanced then zero amps will flow all the way up to 100 amps if only one leg of the three phase system is used. The neutral in a wye three phase system carries only the unbalanced current. This is why in services for a three phase four wire system you are allowed to reduce the size of the neutral conductor.
There is a lot of confusion amongst consumers that an Unbalanced LoadStabilizer is generally superior to a Balanced Load Stabilizer. To clarifythis myth certain fundamental principles connected with Transformersare given below:1. Definition of Balanced and Unbalanced loads:a. A Three phase Loads on a 3 phase supply system is a Balancedload because it draws equal current from each phase. Three phaseMotors, Converters; Rectifiers using 3 phase input supply arecommon examples of Balanced loads.b. A single phase / 2 phase loads on a three phase system is calledUnbalanced load. Normally Unbalanced loads have to use aneutral wire in the system. The 2 phase loads may not require aneutral.
For a given load, a three-phase system requires around 75% of the volume of copper required by a corresponding single-phase system and, so, is more economical. A three-phase supply also delivers power more or less continuously, whereas a single-phase supply delivers power in pulses. Finally, three-phase motors are self-starting and physically smaller than single-phase machines of the same power rating.
A balanced three phase load is where the current flowing in all three phases of the load are reasonably close to each other.Another answerWhen the voltage and measured current draw do not deviate by more than 2 percent under load.AnswerA balanced three-phase load is one in which each of the three loads is identical in all respects (magnitude and phase). Further to the first answer, the three line currents must not all be 'reasonably close', they must be identical -i.e. the same value and phase relationship.
Because a three-phase system needs half the amount of wire to transmit power compared to three single-phase systems. With a balanced three-phase system the three live wires are phased so that the sum of the currents is always zero, which means that if the three neutral wires are combined, the current in the neutral is zero. Therefore the original three neutral wires can be removed, leaving only the three live wires. In practice a neutral wire is still included in three-phase four-wire systems when the load is potentially unbalanced, as for example in neighbouring houses which use different phases of a three-phase system for their individual single-phase supplies.