answersLogoWhite

0


Best Answer

No matter whether we're describing a three-phase service or a a single phase service, the bare copper "earth" or "ground" wire normally carries no current. Its purpose is to provide an emergency path for current if ever there is any accidental contact between a hot wire and the external (or internal) metal parts of any electrical device which a user may be able to touch. The electrical device can be a motor, a water heater, an air conditioner unit or any other kind of appliance.

By carrying away the excess current in a fault condition - which should cause the protecting fuse to blow or the circuit breaker to trip - the "ground" or "earth" wire protects the building and its occupants because the power should be cut off before anyone gets electrocuted or any overloaded circuit wiring or appliances catch on fire.

The neutral is the normal "return" wire. In systems where the load is supplied from only one hot (or "live") wire, the neutral completes the circuit and carries current back from the load to the power station. In "Y-" or "star-connected" three-phase circuits the neutral doesn't normally carry any current if all three phases are properly balanced.

If the three phases actually have unbalanced loads - which can easily happen if each phase is being used to provide power to different single-phase circuits, each with their different loads - then some current will flow in the neutral wire and will result in unbalanced 3-phase currents flowing back to the power station.

All the neutral and ground (or "earth") wires in a building are tied or linked together at the incoming service main breaker panel. This is the only place they should ever be tied together because it is "upstream" of all the fuses and/or circuit breakers protecting the hot (or "live") wires for the various circuits installed in the building.

Warning: we must never assume that a neutral is safe to touch: it has to be checked with a voltmeter or a voltage indicator to be sure it is not "live". This is because a neutral wire is designed to carry current under normal circumstances.

So, if a neutral wire going back to the incoming main breaker panel has not been properly connected - or suffers a deliberate disconnection or some accidental damage which causes it to break - then it and any neutral wires connected to it further downstream will go live up to the break because of being connected to the downstream loads which still have hot feeds coming into them!

That is why we should never use a neutral as a substitute for a proper, separate, ground or "earth" wire.

<><><>

If some external accidental damage or electrical breakdown of the wiring's insulation occurred anywhere to the house wiring, to a socket outlet or to an appliance, these things could be very dangerous if there was no such protective wire.

For example, if there was no protective ground or earth wire, a fault could happen that is of a kind which did NOT draw enough extra current to blow a fuse or make the main circuit breakers on the incoming supply panel "trip" to cut the current off - but the wiring could still catch on fire and/or someone could be electrocuted!

Neutral wires are the return paths to the power generation station for current it supplies to the house or building via single live or "hot" wires in the branch circuits.

For more information please click on the Related Questions below.

<><><>

As always, if you are in doubt about what to do, the best advice anyone should give you is to call a licensed electrician to advise what work is needed.

Before you do any work yourself,

on electrical circuits, equipment or appliances,

always use a test meter to ensure the circuit is, in fact, de-energized.

IF YOU ARE NOT ALREADY SURE YOU CAN DO THIS JOB

SAFELY AND COMPETENTLY

REFER THIS WORK TO QUALIFIED PROFESSIONALS.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

14y ago

The neutral is a live conductor intended to allow the flow of current from the load . An earthing conductor is intended to allow the flow of current in fault conditions only when a metal part ( not part of the electrical system eg a metal handle on a cooker ) becomes live .

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

well first of all we must understand difference between neutral and ground (earthing in some cases, but preffered as grounding when it is on any other planet than earth).

neutal is provided in any system to complete the circuit or to run the device we are connecting it to.

the ground is provided for protection purpose in case of motor or electrical device rises to potential ,it can harm the operator of it so we provide the ground wire to it (with lower resistace than human body obviously) thus making it possible to flow the current through it in case the outer body of motor rises to a potential and saving operator.

In a 3 phase system (say star or Y connected) the mid point is the point which should have no potential at all in a balance system so a wire is provided from it to carry out the current in case of unbalancing of system .

the grouding (earthing in some cases) dictated earlier is called equipment grounding while which discussed in later part is known as system groundig.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

Phase and neutral are both conductors. The load circuit receives (so to speak) power from the phase conductor, and returns (so to speak) power back to the neutral conductor. In this fashion, a complete series circuit is formed between the distribution power transformer, the load, and the two conductors connecting them.

The only difference between phase and neutral is that neutral is grounded at the distribution panel. This is a single point ground so, technically, no current flows on ground. The purpose of the ground is to place a limit on the voltage present at any point of the circuit with respect to ground, and also to be able to detect and protect against a ground fault.

This answer is:
User Avatar

User Avatar

Wiki User

13y ago

The neutral conductor provides a return path for single-phase loads and you would expect to find neutral current flowing as a normal condition.

The ground conductor provides a return path for fault current when a hot conductor accidentally comes in contact with a grounded object. This is a safety feature of the wiring system and you would never expect to see grounding conductor current flow during normal operation.

At one point in the wiring system, the neutral conductor and the ground conductor are connected together, but they still serve different purposes.

This answer is:
User Avatar

User Avatar

Wiki User

14y ago

In a three phase power system, ground is at ground voltage, and the neutral, depending on whether it is grounded or not, may or may not be at ground potential (it may be "floating").

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the difference between neutral and ground in a three phase system?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

Can a 3 wire system create neutral voltages due to Harmonic distortion?

Yes, a 3 wire system can create neutral voltages due to harmonic distortion. Neutral voltages can also be caused by load imbalance between the two hots. It is normal for neutral to have a voltage differential relative to ground. Neutral is, after all, a current carrying conductor. In a well balanced system, however, there is little (theoretically zero) current in neutral.


What cause current on the neutral line in a three phase?

Current on neutral in a multi phase system is caused by imbalance between the phases. Question: Are you talking about neutral or ground? The two are very different. Although neutral is grounded, it is expected to be a current carrying conductor, so current on neutral is normal, so to speak. Ground, on the other hand is a protective circuit that is not supposed to have any current on it at all.


What is the difference between cropping system and farming system?

difference between farming system and cropping system


In the electrical system of the US what is the difference between the neutral and the PE Ground?

US NEC: The neutral conductor is an insulated grounded conductor used as the current return in a circuit. The color designation for neutral is white. The protective ground (PE, protective - earth) is a non-insultated grounding conductor used to shunt fault current to ground, tripping the protective device. The color designation for PE ground is green. Neutral and PE ground are tied together at the distribution panel. PE ground is also connected to a solid earth ground, such as grounding rods driven into the earth. Downstream of the distribution panel, PE ground is never used to carry operational current. Any current flow on PE Ground, other than parasitic current, is considered a ground fault, which must be corrected. In fact, GFCI (Ground Fault Current Interrupting) breakers will trip when neutral current does not match hot current, an indication of PE ground current flow.


Single Phase 240 120 Volts AC a test meter placed across black wire and Ground wire will read what?

Answer for USA, Canada and countries running a 60 Hertz supply service.A test meter across black and ground in a 120/240 split phase system should read about 120 volts. Note, however, that ground is not the correct reference point; neutral is the correct reference point, and the meter should be connected across black and white, or red and white, or red and black. This is because the ground connection is a protective earth ground, not intended to carry current. Since ground and neutral are tied together at the distribution panel, you might expect them to have no potential difference, but impedance in the conductors will result in a voltage drop across neutral, biasing the voltage seen between hot and ground, as opposed to hot and neutral.

Related questions

What is the difference between neutral point and earthing?

Earthing point is where conductor is directly connected to ground and its potential is always zero. Neutral is a return path in single phase system and in three phase system Neutral point will have zero potential if all the loads are balanced in the system. In un balanced three phase system even neutral point will have some potential


What is meant by neutral grounding reactor?

Neutral-earthing reactors or Neutral grounding reactors are connected between the neutral of a power system and earth to limit the line-to-earth current to a desired value under system earth fault conditions.


Can a 3 wire system create neutral voltages due to Harmonic distortion?

Yes, a 3 wire system can create neutral voltages due to harmonic distortion. Neutral voltages can also be caused by load imbalance between the two hots. It is normal for neutral to have a voltage differential relative to ground. Neutral is, after all, a current carrying conductor. In a well balanced system, however, there is little (theoretically zero) current in neutral.


How can you connect a system working with 60Hz 1 Hot wire 1 neutral wire and a ground wire to my utility system that works with 60Hz two hot wires and a neutral wire?

Your 2-wire system is actually connected to one "side" of the 3-wire system. In your utility's 3-wire system you have 2 hot wires that are attached to each end of a tranformer winding and the neutral is attached in the middle and grounded. Typically in the US this gives you 240v (or something similar) between hot leads and 120v from each hot lead to neutral or ground.


What cause current on the neutral line in a three phase?

Current on neutral in a multi phase system is caused by imbalance between the phases. Question: Are you talking about neutral or ground? The two are very different. Although neutral is grounded, it is expected to be a current carrying conductor, so current on neutral is normal, so to speak. Ground, on the other hand is a protective circuit that is not supposed to have any current on it at all.


What besides the neutral system should be bonded to the ground?

Answer for USA, Canada and countries running a 60 Hertz supply service.Nothing but the neutral bus should be bonded to the ground electrode.


Is it OK illegal or dangerous to connect the neutral to ground to make the circuit work?

If you have to connect the neutral to ground to make the circuit work then you have an open neutral in your circuit. Be careful in handling the neutral as there can be voltage potential on the neutral if a load is connected. In a properly wired home that has been inspected by the local electrical inspector the neutral should be bonded to the ground at the main service distribution point. There will be a green screw that projects through the neutral bus and is threaded into the back of the electrical panel. This should be the one and only place in the whole electrical system where this neutral to ground connection takes place. Dangerous!!!!! The ground is the safety to prevent you from getting shocked due to a malfunctioning piece of equipment. By using the ground for a neutral you will be energizing the entire ground system of you house or business. Thus anything with metal on it and a ground wire going to it will be electrified if the ground fails at the breaker box or building ground rod. Do you want to take this risk? Not I..........


What is the difference between cropping system and farming system?

difference between farming system and cropping system


Difference between system software and operating system?

difference between operating system and system software?


Should there be power from common to ground in wall socket?

120 volt wall outlets. Their could me a small voltage between neutral and ground,up to around 1.5 volts. What you are measuring is the voltage drop on the system at that point in the system. You see the neutral and the ground are at the same level some where up stream (service panel). The neutral is under the same load as the phase conductor, and the neutral will drop voltage same as the phase. This is in fact the way I measure voltage drop, (neutral to ground.) However don't get fooled by high imped. meter, They have a way of ghosting a voltage. Or floating high, You get a reading but the voltage is really not their.


In the electrical system of the US what is the difference between the neutral and the PE Ground?

US NEC: The neutral conductor is an insulated grounded conductor used as the current return in a circuit. The color designation for neutral is white. The protective ground (PE, protective - earth) is a non-insultated grounding conductor used to shunt fault current to ground, tripping the protective device. The color designation for PE ground is green. Neutral and PE ground are tied together at the distribution panel. PE ground is also connected to a solid earth ground, such as grounding rods driven into the earth. Downstream of the distribution panel, PE ground is never used to carry operational current. Any current flow on PE Ground, other than parasitic current, is considered a ground fault, which must be corrected. In fact, GFCI (Ground Fault Current Interrupting) breakers will trip when neutral current does not match hot current, an indication of PE ground current flow.


What is the function of neutral in electrical system?

See related link. The neutral wire provides the electric current a return path back to the electrical generation system. It is connected to earth ground, and should have no electric potential in relation to earth ground.