The relation of "minimum" to "phase" in a minimum phase system or filter can be seen if you plot the unwrapped phase against frequency. You can use a pole zero diagram of the system response to help do a incremental graphical plot of the frequency response and phase angle. This method helps in doing a phase plot without phase wrapping discontinuities.
Put all the zeros inside the unit circle (or in left half plane in the continuous-time case) where all the poles have to be as well for system stability. Use the angles from all the poles, and the opposite of the angles from all the zeros, to a point on the unit circle to calculate phase, as that frequency response reference point moves around the unit circle. Now compare this plot with a similar plot for a pole-zero diagram with any of the zeros swapped outside the unit circle (non-minimum phase). The overall average slope of the line with all the zeros inside will be lower than the average slope of any other line representing the same LTI system response (e.g. with a zero reflected outside the unit circle). This is because the "wind ups" in phase angle are all mostly cancelled by the "wind downs" in phase angle only when both the poles and zeros are on the same side of the unit circle line. Otherwise, for each zero outside, there will be an extra "wind up" of increasing phase angle that will remain mostly uncancelled as the plot reference point "winds" around the unit circle from 0 to PI. (...or up the vertical axis in the continuous-time case.)
This arrangement, all the zeros inside the unit circle, thus corresponds to the minimum increase in total phase, which corresponds to minimum average total phase delay, which corresponds to maximum compactness in time, for any given (stable) set of poles and zeros with the exact same frequency magnitude response. Thus the relationship between "minimum" and "phase" for this particular arrangement of poles and zeros.
5000 volt
Yes the minimum voltage of an 115vac 400 Hz 3 phase motor will run. You can run a single phase motor on a three service but you cannot be run on a single phase.
A "three-phase system" is a polyphase system having three phases. The term "polyphase system" just means a system having multiple phases. If it is used by itself, "a polyphase system" doesn't mean "a three-phase system".
A two-phase system is archaic and you are unlikely to find it in use anywhere these days, so it is mainly of historical interest. A two-phase, three-wire system, consists of two phase voltages, displaced from each other by 90 electrical degrees, and a phase voltage which is 1.414 x phase voltage.A three-phase system consists of three phase voltages which are displaced from each other by 120 electrical degrees. In the case of a three-phase, three-wire, system, the line voltages are numerically equal to the phase voltages; in the case of a three-phase, four-wire, system, the line voltages are 1.732 x phase voltage.
A two-phase a.c. system is an archaic system, in which two phase voltages are generated 90 electrical degrees apart. It has nothing whatsoever to do with the US 'split phase' system that supplies North American homes. A two-phase system can be a four-wire system, or a three-wire system, and was useful because, unlike a single-phase system, it could create naturally rotating magnetic fields in induction motors. It has long been superseded by the three-phase system.
5000 volt
minimum phase network
For the condition of phase equilibrium the free energy is a minimum, the system is completely stable meaning that over time the phase characteristics are constant. For metastability, the system is not at equilibrium, and there are very slight (and often imperceptible) changes of the phase characteristics with time.
Yes the minimum voltage of an 115vac 400 Hz 3 phase motor will run. You can run a single phase motor on a three service but you cannot be run on a single phase.
127 mm for Indoor
A "three-phase system" is a polyphase system having three phases. The term "polyphase system" just means a system having multiple phases. If it is used by itself, "a polyphase system" doesn't mean "a three-phase system".
No. For three phase, you need a minimum of a two element meter.
3 phase system has more power than a single phase system
A two-phase system is archaic and you are unlikely to find it in use anywhere these days, so it is mainly of historical interest. A two-phase, three-wire system, consists of two phase voltages, displaced from each other by 90 electrical degrees, and a phase voltage which is 1.414 x phase voltage.A three-phase system consists of three phase voltages which are displaced from each other by 120 electrical degrees. In the case of a three-phase, three-wire, system, the line voltages are numerically equal to the phase voltages; in the case of a three-phase, four-wire, system, the line voltages are 1.732 x phase voltage.
A two-phase a.c. system is an archaic system, in which two phase voltages are generated 90 electrical degrees apart. It has nothing whatsoever to do with the US 'split phase' system that supplies North American homes. A two-phase system can be a four-wire system, or a three-wire system, and was useful because, unlike a single-phase system, it could create naturally rotating magnetic fields in induction motors. It has long been superseded by the three-phase system.
2ft 6 inches
The US system is not a two-phase system; it's a split-phase system. But, to answer your question, probably not without damaging the Japanese device.