If you can imagine a machine's three phase windings with a common point of connection, thus forming a 'star' shape, with each phase winding displaced from each by 120 degrees. The 'free' ends of the three phase windings are then connected, externally, by wires called 'line conductors', while the common point of connection (the 'star point') is (in the case of generators and transformer secondaries) earthed (grounded) and connected, externally, by a wire called the 'neutral conductor'.
The voltages measured between any pair of line conductors are called 'line voltages', and the voltages measured between any single line conductor and the neutral conductor (i.e. across individual phase windings) are called 'phase voltages'. A line voltage is the vector sum of its phase voltages, making in 1.732 times the value of a phase voltage.
i think its use for 3 phase connection.
6
the speed decrease if increasing load..in star connection the speed lower
The power of all three phases can be transmitted on three conductors.A star connection, as opposed to a delta, provides a grounding reference. Also, for ground faults on the secondary (assuming no delta third winding, or source third winding) will be a direct ratio similar to phase faults, instead of 57%. Another reason is to avoid the inherent phase shift involved in a delta/star configured transformer.Another AnswerA 'star-connected' secondary is the standard European connection for a three-phase distribution transformer, as it provides a line voltage of 400 V together with a phase voltage (i.e. line to neutral) of 230 V.
in order to reduce the impact of fault current...
datail for admission datail for admission
The definition of star connection is a connection of the ends of phase windings at the star point.
hahahaa
i think its use for 3 phase connection.
Compared with what?
The term, 'star point', refers to the common point of connection for the three windings of a star-connected (wye-connected) transformer connection. The star point is usually earthed (grounded) and provides the neutral point of the connection.
Probably the reason is in the different voltages between the star and delta connection voltages. An electromagnetic brake designed for the lower voltage of the star connection would burn out or open when introduced to the higher voltage of the delta connection.
Because it is the same current, as you can determine by examining a circuit diagram of a star connection.
6
the speed decrease if increasing load..in star connection the speed lower
The power of a three-phase load is the sum of the three individual loads. It makes no difference whether they are connected in star (wye) or in delta.
Transmission circuits are prone to earth faults.Only star connection permits flow of earth fault current and the operation of earth fault relays.