6000amps
<<>>
The above answer must have big lugs to accommodate 6000 amp capacity wire.
In my breaker catalogue the largest 120 volt single pole breaker is 70 amps, 277 volt single pole is 150 amps and 347 volt single pole is 100 amps. The 120 volt single pole breaker occupies two opposed slots because of its length.
From the nameplate on the welder you find the amperage that the welder draws at the three phase voltage that you are going to use. This amperage is used to size the phase converter. This amperage is also used to size the breaker that will feed the phase converter and wire size for the installation.
To answer this question a voltage needs to be stated and whether the load is three phase or single phase. Without the voltage the amperage can not be calculated. For single phase, Amps = kva x 1000/voltage, for three phase, Amps = kva x 1000/1.73 x voltage.
Common usage of a three pole breaker is for use on a three phase distribution panel. Single phase distribution panels only use two pole breakers for a 240 volt load.Remember that the breaker must protect the conductors that connect to the load. If you want to try and use a three pole breaker in a single phase panel just because you have the breaker, this is not a good idea even if it will fit.Purchase the proper single phase two pole breaker to match the wire size and the amperage of the connected 240 volt load. Keep in mind that connected 240 volt motor loads have to be sized to 250% of the motor's full load amperage.By doing what you want to do and a fault occurs from this type of installation your insurance company might not cover the damage that it would cause.If the distribution panel is three phase then just connect the two load wires to any two of the three poles on the breaker.
if you have 200 kva so it's 160 KW then ,you need 400 A MCCB and setting at 0.9 and use cable 4c.185 mm2 if the SMDB is nearby and all this will be change according to the ambient temperature and the electrical code used in your area
Typically single phase motors go up to 10hp. Wouldn't be very efficient at about 100 amps. A 20hp 3 phase motor at 230v pulls 52 amps. The 10hp single phase 230v pulls 50 amps.
From the nameplate on the welder you find the amperage that the welder draws at the three phase voltage that you are going to use. This amperage is used to size the phase converter. This amperage is also used to size the breaker that will feed the phase converter and wire size for the installation.
To answer this question a voltage needs to be stated and whether the load is three phase or single phase. Without the voltage the amperage can not be calculated. For single phase, Amps = kva x 1000/voltage, for three phase, Amps = kva x 1000/1.73 x voltage.
208 volts is not a common single phase voltage but you could just size your breaker to the capabilities of the conductor. 208 is normally a phase to phase voltage <<>> Many 230 volt motors can be connected to lower voltage supplies. These motors can be connected to supplies of 208 and 200 volts. The code requirement is that the 230 volt full load amperage of the motor be increased by 10% and 15% respectively for wire sizing and breaker selection. To answer the question you will need a two pole 15 amp breaker.
please show me how to figure it out.
The job of a breaker is to limit the amount of current that is applied to the size of wire that is connected to the breaker.
Common usage of a three pole breaker is for use on a three phase distribution panel. Single phase distribution panels only use two pole breakers for a 240 volt load.Remember that the breaker must protect the conductors that connect to the load. If you want to try and use a three pole breaker in a single phase panel just because you have the breaker, this is not a good idea even if it will fit.Purchase the proper single phase two pole breaker to match the wire size and the amperage of the connected 240 volt load. Keep in mind that connected 240 volt motor loads have to be sized to 250% of the motor's full load amperage.By doing what you want to do and a fault occurs from this type of installation your insurance company might not cover the damage that it would cause.If the distribution panel is three phase then just connect the two load wires to any two of the three poles on the breaker.
This depends on what voltage the range is rated for and if it is single phase or three phase. At 220 volts single phase it is about 60 amps, 240 v single phase , 53 amps and at 480 v three phase about 15 amps.
A breaker protects the wire size of the feeder that is connected to it. The amperage of the load must be found. Without a voltage stated the amperage from the wattage given can not be calculated. The equation for amperage when the kw is given is A = kW x 1000/1.73 x volts x pf. The pf constant to use is .9.
if you have 200 kva so it's 160 KW then ,you need 400 A MCCB and setting at 0.9 and use cable 4c.185 mm2 if the SMDB is nearby and all this will be change according to the ambient temperature and the electrical code used in your area
Typically single phase motors go up to 10hp. Wouldn't be very efficient at about 100 amps. A 20hp 3 phase motor at 230v pulls 52 amps. The 10hp single phase 230v pulls 50 amps.
To answer these types of questions, a voltage of the single phase motor should be stated. It has to do with the breaker sizing and wire sizing and current load.
The current is limited by the fuse or circuit breaker.