KVA means thousands (K) of volts (V) times Amperes (A). A 100 KVA transformer can deliver 1000 amps at 100 volts or 500 amps at 200 volts etc.
amps=(KVA*1000)/(VOLTAGE*PHASE)
A=100000/(240*1.732)
A=100000/415.68
A=240.569
power=240*240.569*.8
p=46189 kw
The rated secondary current depend on the rated secondary voltage.
the capacity of a transformer is defined as a product of voltage and current flowing through it.AS THE CURRENT IS MEASURED IN AMPERES AND VOLTAGE IN VOLTS, Hence transformers are measured/rated in KVA
Transformer capacity (kvA) shall be identical, Both transformer impedance, secondary voltage and frequency shall be identical.
In 1600 kva transformer we provide NGR (Neutral grounding resistance)
Yes you could use a 20 kva transformer in a home. Stymied as to why it would be done though. You would need at least a 100 amp service to the home to energize the transformer. Primary side of the transformer would draw 83 amps at 240 volts. If the question was to supply the home, again yes. It would be 100 amp service equipment that the transformer would feed into.
Transformers are rated in KVA because that is a more accurate way to measure their capacity requirements. KWH is apparent power, while KVA is true power, and the ratio between them is power factor. The power factor is a function of the load, and not the transformer, so a poor power factor would make KWA look less to the transformer while, in fact, the true power, if not met by the transformer, could overload the transformer.
transformer action doesn't depend on power factor that is why we indicate its rating in KVA
5 kva
the capacity of a transformer is defined as a product of voltage and current flowing through it.AS THE CURRENT IS MEASURED IN AMPERES AND VOLTAGE IN VOLTS, Hence transformers are measured/rated in KVA
Transformer capacity (kvA) shall be identical, Both transformer impedance, secondary voltage and frequency shall be identical.
The 3 kVA transformer will weigh double the 1.5 kVA transformer.
Sounds like the wrong size fuse protection was used. The transformer should be protected to its kva capacity.
In 1600 kva transformer we provide NGR (Neutral grounding resistance)
Depends on the kva rating of the devices to be tested using a transformer.
The result is that the transformer runs cool and contented. The '250 KVA' rating on the transformer is its maximum ability to transfer power from its input to its output without overheating, NOT an amount of power always running through it. If the 3 KVA load happens to be the only thing connected to the transformer at the time, then only 3 KVA flows into the transformer from the primary line, and only 3 KVA leaves the transformer secondary.
Yes you could use a 20 kva transformer in a home. Stymied as to why it would be done though. You would need at least a 100 amp service to the home to energize the transformer. Primary side of the transformer would draw 83 amps at 240 volts. If the question was to supply the home, again yes. It would be 100 amp service equipment that the transformer would feed into.
a kva is 1000 vaK is kilo, which means 1000 similar to how a kilometer is 1000 metersTransformers are usually rated in KVA, so a 45 KVA Transformer is a 45 000 VA Transformer
Wire sizing of a feed conductor is based on the amperage that a device draws. To calculate amperage from KVA a voltage of the supply has to be stated. Without this voltage and whether the transformer is single or three phase an answer can not be given.