answersLogoWhite

0


Best Answer

Lets liken this to a garden hose, a hose in the normally open position has water flowing through it until it is closed by turning the spigot off, normally closed is the reverse. Oddly enough when it comes to an electronic relay the opposite is true, whereas the switch is in the open (normally open) position therefore having no current passing through it until a switch to close the circuit and allow current to flow. Normally closed has current flowing at all times until the switch interrupts it stopping the flow of electricity.

User Avatar

Wiki User

13y ago
This answer is:
User Avatar
More answers
User Avatar

Wiki User

10y ago

During a loss of pressure in the instrument air, a fail open valve fails to the open position and a fail closed valve fails to the closed position.

This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What is the difference between a fail open valve and a fail closed valve?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Engineering

What is the difference between a Single acting and double acting valve?

Normally a control valve is referred to by its fail position. This means "what position will the valve move to should the supply air or control signal to the valve falls away". This is important to safe guard the process at various places, so some valves will be fail open and some fail close. In order to have a valve as fail open or fail close, the valve actuator has to be spring loaded. So by having the spring on top or bottom of the actuator piston will we determine if it will be an FO or an FC valve. This kind of valve is also called single acting valve since it will only have one output from its positioner to either the top or bottom of the actuator. The positioner on the valve is also setup as a single acting positioner since it will only give a single action to the actuator, the reverse action will be done by the spring. The problem with this setup is that it is possible that the process might be so strong or the pressure so high (during a blow down or ESD shutdown in the plant) that the spring might in certain instances be too weak to push the valve into the fail position quick enough, due to the back pressure from the process, and can cause damage to the plant or even an explosion. To ensure that the valve will go to the fail position, we install a double action positioner with two outputs. One goes to the top of the actuator and one to the bottom. This is also very helpful in having very accurate and stable control on a high flow line since the pressure from the positioner does the actual control unlike spring controlling one way and positioner controlling the other way as is in the single acting control valves. It is also solving the problem that the valve will now be forced into the fail position by the spring as well as the positioner supply pressure during an emergency. In shutdown valves (open/close ESDVs) the same is true and sometimes at critical and high pressure points we use hydraulics instead of pneumatic as the double acting agent to make sure the valve will close during the emergency. So to summarize the double action in ESD and control valve, it suffices to say that this double action is there just to make sure that the valve will do what it was designed for. Call it an extra fail safe if you want. It might not be needed in theory since a single acting valve should do the trick just as well, but in practice you are at times very glad that you did it especially if you look at the kind of pressures the valves are working on. With those kind of flows and pressures you don't want to leave anything to chance.


Makeup gas compressor spill back valve function?

It is a quick response valve, which opens fully in 1.5-2 seconds. basically will be of fail open type. Its opening depends on the surge control.


What is the difference between permitted and granted development?

Permitted DevelopmentThere are no time limits for the development. Granted DevelopmentThere is a specified amount of time to undertake construction. If you fail to meet the deadline you will need to reapply.


What causes a diode to fail on a 240v solenoid valve?

Why would it? And is this the diode across the windings of the coil that supplies the back EMF (inductive kick) supression? There isn't a good reason for it to fail. A bit more information is needed here.


Program in c language using Depth first search DFS to convert each edge in Graph to a directed edge such that graph is strongly connected?

begin open:=[start]; closed:=[]; while open<>[]do begin remove left state from open,call it X. if X is a goal then return SUCCESS else begin generate children of X; put X on closed; discard children of X if already on open or closed; put remaining children on the left end of open; end end return FAIL; end

Related questions

What is difference between lead and gold?

you fail


Is normally open valve and fail open valve the same?

"Normally Open" or "Normally Closed" are classifications that refer to actuated (not manually operated) valves. For an actuated valve, the "normal" state refers to its position when the actuator is not energized.Therefore a normally open valve is one that is open until the actuator is energized to close it; if power to the actuator fails, the valve opens or "fails open".Likewise with a normally closed valve if power to the actuator fails, the valve closes or "fails closed".The "normal" state of an actuated valve must not be confused with the "usual" position of the valve during routine operation of the system. A normally closed valve may be open continuously over a long period of time while a process is running, but it is still a normally closed valve. It just happens that this normally closed valve is usually open.For an actuated valve to return to its "normal" position, there must be some force, often a spring, that moves the valve from its actuated state back to its normal state. If a valve is actuated to open and then actuated to close, it will "fail" in whichever position it is in when the activator is de-energized. This type of a valve is not considered "fail safe".A normally closed valve might be used in an application such as the loading of gasoline transport trucks where in the event of a power or automation system failure, you would want to stop flow.A normally open valve might be used in a situation where you want flow to continue in the event of a power or automation system failure. This might be the case for the cooling water system for a nuclear reactor or for an actuated valve on the water piping to the fire protection system.


What is meant by air to open valve?

An air to open valve is a type of control valve that requires air pressure to be applied in order to open the valve. When the air pressure is removed, the valve will close automatically. This design is commonly used for safety-critical applications where a fail-safe operation is needed.


What is the difference between coleslaw and boiled cabbage?

I have no idea and im going to fail my exam


What wohld happen if valves stoped working?

Completely depends on the system. Often valves are designed to fail in a certain way (open/closed/as is) to prevent larger system failures. Need specifics of valve and application...


What is the difference between collateral and pledge?

There is not much difference between collateral and pledge. If you put something up as collateral, if you fail to pay the loan, the item that you pledged will be taken. Either word can be used.


Did the roman empire fail?

This question is too vague. Closed


What is the difference between an aerobe and an anaerobe?

Aerobes utilize and thrive in oxygen, anaerobes are killed/ fail to thrive in oxygen.


What is the difference between an xbox 360 and a ps3?

PS3 is in hi def and can play blu ray disc and only has a 0.02% fail rate Xbox 360 has a 33% fail rate


What is difference between a club and hotel management?

lol you're in crayton's class. better study or you'll fail XD


In what year did Continental Bank fail?

■Its headquarters closed down in 1952.


Why might a closed ecosystem fail?

Closed ecosystems are self-replenishing ecosystems in which life can be maintained without external factors or outside aid. They can fail through lack of water, over population, and disease.