The Gas Turbine Protection are;
1-High Vibration
2-Exh. temp. high
3-Lube oil temp. high
4-Low lube oil press.
5-Turbine air filter diff. high
6-Hyd. oil press. low
7-Exh. sprad temp. high
8-Fire
when steam flow blockage occured in steam turbine due to damage of blades/nozzles than steam temperature will increase so protect the turbine from high temperature this protection is introduced.
by means of mechanical or electrical overspeed protection mechanism
The Gas Turbine Protection are; 1-High Vibration 2-Exh. temp. high 3-Lube oil temp. high 4-Low lube oil press. 5-Turbine air filter diff. high 6-Hyd. oil press. low 7-Exh. sprad temp. high 8-Fire
MARK6 is used for the protection of steam and gas turbine in electrical generators and process plant applications The main function of Mark6 turbine control system are: -speed control during turbine start up -automatic generator synchronization -turbine load control during normal operations on the grid -protection against turbine -protection against turbine over speed on the loss of land The mark6 system is available as a simplex control or a triple modular redundant (TMR) control with single or multiple racks, and local or remote I/O. The I/O interface is designed for direct interface to the sensors and actuators on the turbine, to eliminate the need for interposing instrumentation, and to avid reliability and maintenance issues associated with that instrument. NOTE : to obtain a highest reliability, MARK6 uses a TMR architecture with sophisticated signal voting techniques.
No these are two different sensors. The thrust bearing temperature trip device measures either the metal temperature of the bearing, or the oil temperature exiting the bearing, or both. If this temperature exceeds recommended temperatures by 10 to 15% the turbine will trip to avoid damaging the bearings or shaft. The rotor position sensor is a proximity cell that monitors the axial position of the turbine rotor, often there is four such sensors mounted at the end of the rotor, if the distance between the sensors and the rotors exceeds a specific distance ( often 15-30 mils) the sensors indicate a failure, if two or three sensors indicate failure the turbine will trip.
HP Turbine is High Performance Turbine LP Turbine is Low Performance Turbine
Turbine is not a change, a turbine is a mechanical device.
in a radial flow turbine the steam enters the turbine in the direction of its radius and leaves it in the direction of the axis of the shaft. in a axial flow turbine the steam enters the turbine in the direction of the axis of the shaft and leaves the turbine in the same direction.
Turbine is the correct spelling.
yes it will be big damages for both that's y fixing differential protection relay between both
gas turbine generator