Low condensing temperatures may result in compressor operational issues and can even lead to failure. Minimum condensing temperatures are generally established by compressor manufacturers in order to ensure that proper reed valve operation and proper sealing of these valves will take place.
Additionally, the capacity of the metering device upstream the evaporator is partially dependent on the pressure difference across it. If the pressure difference is too low then the evaporator will be starved.
Over feeding the evaporator resulting in floodback to the compressor and damaging it. Either quickly due to the compression of hydraulics or more slowly by lubrication loss from oil diluted with liquid refrigerant.