A 3/0 copper conductor with an insulation factor of 90 degrees C is rated at 225 amps.
bed
Absolutely not. #2awg conductors are only good for about 100 amps depending on Cu or al. see nec table 310-16.
No, if the UL Rated Listing for the Panel is 200A than that's it. You cannot have 300A flowing through a 200A Panel.
Need to know what voltage the generator is outputing. The maximum voltage a 15kW generator will support at 200A is dependent on service voltage and configuration, the rated generator voltage, the power factor and the load frequency. If this is a typical service to a residential unit, eg. 220V single phase, then the generator will not be able to safely support 200A.
When I went to a 100 amp service I could not find a 100 amp. breaker in stock. I used a 60 amp. breaker and have never blown it. The 200 amp you are using can handle up to 200 amps, but if you use a smaller breaker it will only handle up to that amperage. The 200 amp is usally the total amperage of all the breakers comming out of the box. You will probably never come anywhere near using 200 amps at one time.
4/0 Aluminum or 2/0 Copper type USE.
bed
250 mcm
Copper SE cable gauge 00 from the meter socket to the breaker panel for a 200A service. Then 8, 10, 12, and 14 gauge wire depending on the load.
As long as you do it according to local code, there's no electrical problem with it.
250 MCM aluminum minimum
Absolutely not. #2awg conductors are only good for about 100 amps depending on Cu or al. see nec table 310-16.
Doing it yourself or hiring an electrician? Yourself: About $300. An Electrician: About $2000
200A
200 is composite.
No, if the UL Rated Listing for the Panel is 200A than that's it. You cannot have 300A flowing through a 200A Panel.
The short answer to your question, is "yes" if you are talking about 120 volts. The panel is rated 200A @ 240v. In reality, service panels should be rated in watts (or kilowatts) We are charged by watts and we use electricity in different combinations of volts and amps, but watts remains a constant. (hence the reason we are charged by that value) So, as you noted, there are two legs, that each pass through a pair of interconnected 200 amp breakers. With 240v appliances, power is tapped from each leg, so at no time can 200 amps be exceeded. But with 120v appliances, power is tapped from one leg and terminated to the neutral leg. It is possible to draw a total of 400 amps from both legs, to the neutral. (actually, it's more complicated than that, as the neutral would never see more than 200 amps, and power is actually being routed in series between loads of each leg, so in reality it's still only a max 200A at 240v)So, for further clarification, let's get back to the watts thing. Watts can be calculated mathematically. Watts = volts X amps. So 240v times 200A equals 48,000 watts. That is your service panel's rated wattage. Now, the math can be reversed. 48,000 watts divided by 120v equals 400A.A simple way to present the question would be, "Could you have twenty 20 amp single pole circuit breakers at full load in a 200A service panel?" The answer would be, "yes."