answersLogoWhite

0


Best Answer

A 500 MCM copper conductor with an insulation factor of 90 degrees C is rated at 430 amps. Parallel 3/0 copper conductors with an insulation factor of 90 degrees C will give a total capacity of 450 amps.

User Avatar

Wiki User

9y ago
This answer is:
User Avatar

Add your answer:

Earn +20 pts
Q: What size conductors to use for a 400 amp circuit?
Write your answer...
Submit
Still have questions?
magnify glass
imp
Continue Learning about Natural Sciences

What size ground wire is need for a 30 amp circuit?

On a 30 amp circuit, you would use a #10 copper ground. The ground never has to be larger than the ungrounded conductors.


How much loss from power pole to 200 amp breaker box then off 400 feet then split at a pump house then another 30 feet to a 100 amp breaker box?

For an accurate calculation it will be necessary to know what the size of breaker exists in the pump house and what size conductors are used. Power loss is measured using actual amps required, not size of the circuit involved. But the size of circuit (breaker size) can be used. Voltage must also be known.


What size service conductors do you need for a single phase 600 amp commercial panel?

The size of wire for service entrance conductors for a 400 amp 3 phase service could be 500 MCM copper. This is very large size wire and difficult to bend and shape, to connect to terminals in the main disconnect and distribution panel. This problem is solved by using parallel conductors or on higher ampacities triple conductors. Using parallel conductors the wire size would be three ought (3/0) copper.


What size conductors are needed for 800 amp service?

500


Have 30 amp double pole need 15 amp 120v?

Remove the 30 amp double pole breaker and install at least one single pole 15 amp breaker. It is best if the other slot is not left open so if you have another single pole breaker of any size install it in the 2nd spot so it isn't open when you replace the cover on the panel. For your 15 amp circuit you need #14 gauge copper wire or larger with a hot, neutral, and ground. Your 30 amp circuit was probably wired with #10 gauge conductors. These will probably work on your 15 amp circuit but it may be difficult to connect #10 conductors to devices.

Related questions

What size wire for 400 amp distribution panel?

For a distribution panel rated at 400 amps parallel runs of 3/0 conductors will do the job.


What size ground wire is need for a 30 amp circuit?

On a 30 amp circuit, you would use a #10 copper ground. The ground never has to be larger than the ungrounded conductors.


How much loss from power pole to 200 amp breaker box then off 400 feet then split at a pump house then another 30 feet to a 100 amp breaker box?

For an accurate calculation it will be necessary to know what the size of breaker exists in the pump house and what size conductors are used. Power loss is measured using actual amps required, not size of the circuit involved. But the size of circuit (breaker size) can be used. Voltage must also be known.


What size service conductors do you need for a single phase 600 amp commercial panel?

The size of wire for service entrance conductors for a 400 amp 3 phase service could be 500 MCM copper. This is very large size wire and difficult to bend and shape, to connect to terminals in the main disconnect and distribution panel. This problem is solved by using parallel conductors or on higher ampacities triple conductors. Using parallel conductors the wire size would be three ought (3/0) copper.


What size conductors are needed for 800 amp service?

500


What is the cable size required for a 400 amp and 350 amp load?

350mcm


Have 30 amp double pole need 15 amp 120v?

Remove the 30 amp double pole breaker and install at least one single pole 15 amp breaker. It is best if the other slot is not left open so if you have another single pole breaker of any size install it in the 2nd spot so it isn't open when you replace the cover on the panel. For your 15 amp circuit you need #14 gauge copper wire or larger with a hot, neutral, and ground. Your 30 amp circuit was probably wired with #10 gauge conductors. These will probably work on your 15 amp circuit but it may be difficult to connect #10 conductors to devices.


What are the size of the primary switching center fault interrupters?

200 amp and 400 amp


What size wire is needed for 400 amp 480 volt service?

A 500 MCM wire with an insulation factor of 90 degrees C is rated at 430. Most 400 amp services will use parallel wires on each leg to feed the circuit. A 3/0 wire with an insulation factor of 75 and 90 degrees C is rated at 200 and 225 amps respectively. The insulation rating of these conductors will be 600 volts.


What size conductors for a 2 family with 2 100 amp services together?

2


What size amp circuit breaker should be used for a home entertainment system?

You use the correct size breaker depending on the size wire in the circuit. If the circuit is wired with AWG #12 wire use a 20 amp breaker. If it is wired with AWG #14 wire then use a 15 amp breaker.


Is it safe to use a 20 amp circuit for lighting runs?

Yes : but in a residential case a 15 amp circuit would be better