It would depend on the voltage, because at a higher voltage a larger voltage drop can be tolerated for the same percentage voltage drop. That means a thinner wire could then be used.
And 339 amps is a VERY high current for 120/240 volt system- more than double the peak demand for most houses. Please check your question, and give us the voltage used.
This is a voltage drop question. A voltage at 30 amps needs to be stated to answer the question.
A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.
A 2/0 copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 230 feet on a 240 volt system.
A 3/0 copper conductor with an insulation rating of 75 or 90 degrees C is rated at 200 and 210 amps respectively. A 3/0 copper conductor will limit the voltage drop to 2% or less when supplying 200 amps for 80 feet on a 240 volt system.
Looks like You need to run #10 to get 10 amps at 600 feet. You will have a voltage drop. You might only have aprox. 107.676 volts at the end of the run. You will do a little better if you use strand wire. Good luck.
This is a voltage drop question. A voltage at 30 amps needs to be stated to answer the question.
You will need a 40 amp breaker using AWG # 8 wire running it a distance of no more than 50 feet.
#6 awg copper
A #10 copper wire with an insulation factor of 90 degrees C is rated at 30 amps. If you need the full 30 amps for the load use a #8 copper wire. Loaded to 80% of rating will give you 32 usable amps.
A 400 MCM copper conductor will limit the voltage drop to 3% or less when supplying 100 amps for 700 feet on a 240 volt system. This size will allow the conductor to be loaded to 80 amps. 100 x 80% = 80 amps. Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 100 amps then you would need to use a wire with a rating of 125 amps. 125 x 80% = 100 amps. A 600 MCM copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 700 feet on a 240 volt system.
A #1 copper conductor will limit the voltage drop to 3% or less when supplying 95 amps for 200 feet on a 208 volt system. This size will allow the conductor to be loaded to 76 amps. 95 x 80% = 76 amps Conductors are only allowed to be loaded to 80% or their rated capacity. If you need the full 95 amps then you would need to use a wire with a rating of 120 amps. 120 x 80% = 96 amps. A 1/0 copper conductor will limit the voltage drop to 3% or less when supplying 120 amps for 200 feet on a 208 volt system.
A 2/0 copper conductor will limit the voltage drop to 3% or less when supplying 125 amps for 230 feet on a 240 volt system.
Use AWG # 4 copper and you will have a 2.6% voltage drop which is acceptible.
A 3/0 copper conductor with an insulation rating of 75 or 90 degrees C is rated at 200 and 210 amps respectively. A 3/0 copper conductor will limit the voltage drop to 2% or less when supplying 200 amps for 80 feet on a 240 volt system.
Looks like You need to run #10 to get 10 amps at 600 feet. You will have a voltage drop. You might only have aprox. 107.676 volts at the end of the run. You will do a little better if you use strand wire. Good luck.
10 gauge
You would need to use a #12 copper conductor to continuously draw 14 amps at 120 volts.